40QAQ060 with 38QRR060

13 SEER Underceiling System

Performance

t

Series Heat Pump

with Puron

Refrigerant

Submittal Data

Job Data:_________________________________________________ Location:________________________________________

Buyer:________________________________________ Buyer P.O.#_______________________Carrier # _________________

Unit Number:__________________________________ Model Number: _____________________________________________

Performance Data Certified By: _________________________________________ Date: _______________________________

40QAQ

38QRR

the environmentally sound refrigerant

FEATURES

S

Mounting bracket

S

Electro mechanical controls

S

Built--in electric heat

S

Auto restart after power failure

S

User selectable fan speeds plus auto

S

Cleanable filters

S

Motorized louvers

S

Accessory wired user interfaces

S

Capable of connecting to an Energy Management system

S

Up to 200 ft (61 m) total piping (accessories required)

S

Accessory fresh air intake kit

S

Low ambient operation down to --20

_

F (28.9

_

C)

w/accessory

S

Accessory condensate pump

S

Power ventilation accessory

S

Limited Warranty: 1--year parts / 5--year compressor

S

Optional extended parts and labor warranty

Indoor Unit -- 40QAQ / Outdoor Unit -- 38QRR

(Unless otherwise indicated, data applies to both indoor and outdoor models)

SYSTEM SIZE

060

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

REFRIGERANT

R --410A

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

PERFORMANCE

Cooling Nominal Capacity (Btuh)

60,000

. . . . . . . . . . . . . . . . . . . . . . . .

Heating Nominal Capacity (Btuh)

60,000

. . . . . . . . . . . . . . . . . . . . . . . .

SEER

13

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

HSPF

7.7

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Moisture Removal Rate(Pints/hr)

14.5

. . . . . . . . . . . . . . . . . . . . . . . . . . .

Airflow (Low/Med/High)

1040 / 1220 / 1600

. . . . . . . . . . . . . . . . . . . . .

SOUND PRESSURE (dBA)

Indoor (Low/Med/High)

54.8 / 57.8 / 59.1

. . . . . . . . . . . . . . . . . . . . .

Outdoor

61

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

SOUND POWER (dBA)

Indoor (Low/Med/High)

65.8 / 68.8 / 70.1

. . . . . . . . . . . . . . . . . . . . .

Outdoor

72

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

PERFORMANCE AT ACTUAL CONDITIONS:

Attached

j

Not Attached

j

ELECTRICAL

System Voltage

208/230 --1; 208/230 --3; 460 --3 V

. . . . . . . . . . . . . . . . . . .

MCA

Indoor

34.5; 21.5; 10.6

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Outdoor (208/230 --1; 208/230 --3; 460 --3)

28.7

. . . . . . . . . . . . . . . . . .

MOCP

30

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Indoor

15

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Outdoor (208/230 --1; 208/230 --3; 460 --3)

60; 35; 15

. . . . . . . . . . . . .

Fan Motor (Indoor) (FLA)

2.6

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Electric Heat (kW)

5.00

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

CONTROLS

Control Remote

Wired

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Control Voltage

24v

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Control Wiring (0 --75 ft.)

18 AWG

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Control Wiring (75 --200 ft.)

16 AWG

. . . . . . . . . . . . . . . . . . . . . . . . . . . .

REFRIGERANT LINES (Insulate vapor line)

Liquid Line (in.) OD

3/8

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Vapor Line (in.) OD

7/8

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Metering/Control Device

Accurater at outdoor unit

. . . . . . . . . . . . . . . .

* Refer to NEC and local codes for compliance requirements.

Thermostat Slim Line 7 --day Programmable:

Required

j

Not Required

j

Flat Stat 7 --day Programmable:

Required

j

Not Required

j

Thermostat Super T2 5 --1 --1 Commercial:

Required

j

Not Required

j

Remote Room Sensor Kit:

Required

j

Not Required

j

Condensate Pump:

Required

j

Not Required

j

Fresh Air Intake Kit:

Required

j

Not Required

j

Low Ambient Kit:

Required

j

Not Required

j

Isolation Relay:

Required

j

Not Required

j

Crankcase Heater:

Required

j

Not Required

j

Wind Baffle:

Required

j

Not Required

j