40QAQ060 with 38QRR060
13 SEER Underceiling System
Performance
t
Series Heat Pump
with Puron
Refrigerant
Submittal Data
Job Data:_________________________________________________ Location:________________________________________
Buyer:________________________________________ Buyer P.O.#_______________________Carrier # _________________
Unit Number:__________________________________ Model Number: _____________________________________________
Performance Data Certified By: _________________________________________ Date: _______________________________
40QAQ
38QRR
the environmentally sound refrigerant
FEATURES
S
Mounting bracket
S
Electro mechanical controls
S
Built--in electric heat
S
Auto restart after power failure
S
User selectable fan speeds plus auto
S
Cleanable filters
S
Motorized louvers
S
Accessory wired user interfaces
S
Capable of connecting to an Energy Management system
S
Up to 200 ft (61 m) total piping (accessories required)
S
Accessory fresh air intake kit
S
Low ambient operation down to --20
_
F (28.9
_
C)
w/accessory
S
Accessory condensate pump
S
Power ventilation accessory
S
Limited Warranty: 1--year parts / 5--year compressor
S
Optional extended parts and labor warranty
Indoor Unit -- 40QAQ / Outdoor Unit -- 38QRR
(Unless otherwise indicated, data applies to both indoor and outdoor models)
SYSTEM SIZE
060
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
REFRIGERANT
R --410A
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
PERFORMANCE
Cooling Nominal Capacity (Btuh)
60,000
. . . . . . . . . . . . . . . . . . . . . . . .
Heating Nominal Capacity (Btuh)
60,000
. . . . . . . . . . . . . . . . . . . . . . . .
SEER
13
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
HSPF
7.7
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Moisture Removal Rate(Pints/hr)
14.5
. . . . . . . . . . . . . . . . . . . . . . . . . . .
Airflow (Low/Med/High)
1040 / 1220 / 1600
. . . . . . . . . . . . . . . . . . . . .
SOUND PRESSURE (dBA)
Indoor (Low/Med/High)
54.8 / 57.8 / 59.1
. . . . . . . . . . . . . . . . . . . . .
Outdoor
61
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
SOUND POWER (dBA)
Indoor (Low/Med/High)
65.8 / 68.8 / 70.1
. . . . . . . . . . . . . . . . . . . . .
Outdoor
72
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
PERFORMANCE AT ACTUAL CONDITIONS:
Attached
j
Not Attached
j
ELECTRICAL
System Voltage
208/230 --1; 208/230 --3; 460 --3 V
. . . . . . . . . . . . . . . . . . .
MCA
Indoor
34.5; 21.5; 10.6
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Outdoor (208/230 --1; 208/230 --3; 460 --3)
28.7
. . . . . . . . . . . . . . . . . .
MOCP
30
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Indoor
15
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Outdoor (208/230 --1; 208/230 --3; 460 --3)
60; 35; 15
. . . . . . . . . . . . .
Fan Motor (Indoor) (FLA)
2.6
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Electric Heat (kW)
5.00
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
CONTROLS
Control Remote
Wired
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Control Voltage
24v
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Control Wiring (0 --75 ft.)
18 AWG
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Control Wiring (75 --200 ft.)
16 AWG
. . . . . . . . . . . . . . . . . . . . . . . . . . . .
REFRIGERANT LINES (Insulate vapor line)
Liquid Line (in.) OD
3/8
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Vapor Line (in.) OD
7/8
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Metering/Control Device
Accurater at outdoor unit
. . . . . . . . . . . . . . . .
* Refer to NEC and local codes for compliance requirements.
Thermostat Slim Line 7 --day Programmable:
Required
j
Not Required
j
Flat Stat 7 --day Programmable:
Required
j
Not Required
j
Thermostat Super T2 5 --1 --1 Commercial:
Required
j
Not Required
j
Remote Room Sensor Kit:
Required
j
Not Required
j
Condensate Pump:
Required
j
Not Required
j
Fresh Air Intake Kit:
Required
j
Not Required
j
Low Ambient Kit:
Required
j
Not Required
j
Isolation Relay:
Required
j
Not Required
j
Crankcase Heater:
Required
j
Not Required
j
Wind Baffle:
Required
j
Not Required
j
"Loading the manual" means you need to wait until the file loads and becomes available for online reading. Some manuals are very large, and the time they take to appear depends on your internet speed.