  • Page 2 – INSPECT EQUIPMENT; Step 2—Install on a Solid, Level Mounting Pad; Unit must be level to within; Step 3—Clearance Requirements; Fig. 2—Connecting Tubing Installation; Fig. 4—Accessory Support Feet
  • Page 3 – Fig. 5—Positioning of Sensing Bulb
  • Page 4 – Step 9—Make Electrical Connections; Table 2—Accessory Usage
  • Page 5 – Fig. 8—Line Power Connections; CONTACTOR
  • Page 10 – WIRING DIAGRAM NOTES:; LEGEND; FIELD SPLICE CONNECTION
  • Page 11 – Step 13—Check Charge; Fig. 14−Defrost Control
  • Page 12 – Step 14—Final Checks; Before leaving job, be sure to do the following:; CARE AND MAINTENANCE; LIQUID
Loading the manual

38YSA

Split-System Heat Pump

Installation and Start-Up Instructions

NOTE:

Read the entire instruction manual before starting the

installation.

This symbol

indicates a change since the last issue.

SAFETY CONSIDERATIONS

Improper installation, adjustment, alteration, service, maintenance,
or use can cause explosion, fire, electrical shock, or other
conditions which may cause death, personal injury, or property
damage. Consult a qualified installer, service agency, or your
distributor or branch for information or assistance. The qualified
installer or agency must use factory-authorized kits or accessories
when modifying this product. Refer to the individual instructions
packaged with the kits or accessories when installing.

Follow all safety codes. Wear safety glasses, protective clothing,
and work gloves. Use quenching cloth for brazing operations.
Have fire extinguisher available. Read these instructions thor-
oughly and follow all warnings or cautions included in literature
and attached to the unit. Consult local building codes and National
Electrical Code (NEC) for special requirements.

Recognize safety information. This is the safety-alert symbol

.

When you see this symbol on the unit and in instructions or
manuals, be alert to the potential for personal injury.

Understand the signal words DANGER, WARNING, and CAU-
TION. These words are used with the safety-alert symbol. DAN-
GER identifies the most serious hazards which will result in severe
personal injury or death. WARNING signifies hazards which
could result in personal injury or death. CAUTION is used to
identify unsafe practices which would result in minor personal
injury or product and property damage. NOTE is used to highlight
suggestions which will result in enhanced installtion, reliability, or
operation.

Before installing, modifying, or servicing system, main elec-
trical disconnect switch must be in the OFF position. There
may be more than 1 disconnect switch. Lock out and tag
switch with a suitable warning label. Electrical shock can
cause personal injury or death.

INSTALLATION RECOMMENDATIONS

NOTE:

In some cases noise in the living area has been traced to

gas pulsations from improper installation of equipment.

1. Locate unit away from windows, patios, decks, etc. where unit

operation sounds may disturb customer.

2. Ensure that vapor and liquid tube diameters are appropriate to

capacity of unit.

3. Run refrigerant tubes as directly as possible by avoiding

unnecessary turns and bends.

4. Leave some slack between structure and unit to absorb

vibration.

5. When passing refrigerant tubes through the wall, seal opening

with RTV or other pliable silicon-based caulk. (See Fig. 2.)

6. Avoid direct tubing contact with water pipes, duct work, floor

joists, wall studs, floors, and walls.

7. Do not suspend refrigerant tubing from joists and studs with a

rigid wire or strap which comes in direct contact with tubing.
(See Fig. 2.)

8. Ensure that tubing insulation is pliable and completely sur-

rounds vapor tube.

9. When necessary, use hanger straps which are 1 in. wide and

conform to shape of tubing insulation. (See Fig. 2.)

10. Isolate hanger straps from insulation by using metal sleeves

bent to conform to shape of insulation.

When outdoor unit is connected to factory-approved indoor unit,
outdoor unit contains system refrigerant charge for operation with
indoor unit of the same size when connected by 15 ft of
field-supplied or factory accessory tubing. For proper unit opera-
tion, check refrigerant charge using charging information located
on control box cover.

IMPORTANT:

Maximum liquid-line size is 3/8-in. O.D. for all

residential applications including long line.

IMPORTANT:

Always install a liquid-line filter drier. Refer to

Product Data Digest for appropriate part number. Obtain filter
drier from service parts or your distributor or branch.

INSTALLATION

Step 1—Check Equipment and Job Site

UNPACK UNIT

Move to final location. Remove carton taking care not to damage
unit.

Fig. 1—Model 38YSA

A98516

Visit www.carrier.com

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.

Book 1

4

Tab

5a 5a

PC 101

Catalog No. 533-80022

Printed in U.S.A.

Form 38YSA-4SI

Pg 1

02-02

Replaces: 38YSA3SI

"Loading the manual" means you need to wait until the file loads and becomes available for online reading. Some manuals are very large, and the time they take to appear depends on your internet speed.

Other Manuals for Carrier 38YSA

Summary

Page 2 - INSPECT EQUIPMENT; Step 2—Install on a Solid, Level Mounting Pad; Unit must be level to within; Step 3—Clearance Requirements; Fig. 2—Connecting Tubing Installation; Fig. 4—Accessory Support Feet

INSPECT EQUIPMENT File claim with shipping company prior to installation if shipmentis damaged or incomplete. Locate unit rating plate on unit cornerpanel. It contains information needed to properly install unit.Check rating plate to be sure unit matches job specifications. Step 2—Install on a Solid...

Page 3 - Fig. 5—Positioning of Sensing Bulb

Step 6—Thermostatic Expansion Valve For proper unit operation and reliability, units must beinstalled with field-supplied hard shutoff TXV. Do not installwith evaporator coils having capillary tube metering devicesor pistons. Due to system design, this unit must be installed with afactory-listed ind...

Page 4 - Step 9—Make Electrical Connections; Table 2—Accessory Usage

For buried-line applications greater than 36 in., consult your localdistributor. If refrigerant tubes or indoor coil are exposed to atmosphere, theymust be evacuated to 500 microns to eliminate contamination andmoisture in the system. OUTDOOR UNIT CONNECTED TO FACTORY-APPROVEDINDOOR UNIT Outdoor uni...