Carrier 38CKX- User Manual
Carrier 38CKX– User Manual, read for free online in PDF format. We hope this helps you resolve any issues you may have. If you have further questions, please contact us through the contact form.
Table of Contents:
- Page 2 – Fig. 2—Unit Reference Drawing; UNIT SIZE
- Page 3 – Step 5—Make Electrical Connections; Operation of unit on improper line voltage constitutes; Fig. 3—Piping Installation
- Page 4 – Fig. 4—Line Power Connections
- Page 5 – Fig. 5—24v Control Circuit Connection
38CKX—50 Hz
Air Conditioning Unit
Installation and Start-Up Instructions
NOTE:
Read the entire instruction manual before starting the
installation.
SAFETY CONSIDERATIONS
Improper installation, adjustment, alteration, service, maintenance,
or use can cause explosion, fire, electrical shock, or other
conditions which may cause death, personal injury, or property
damage. Consult a qualified installer, service agency, or your
distributor or branch for information or assistance. The qualified
installer or agency must use factory-authorized kits or accessories
when modifying this product. Refer to the individual instructions
packaged with the kits or accessories when installing.
Follow all safety codes. Wear safety glasses, protective clothing,
and work gloves. Use quenching cloth for brazing operations.
Have fire extinguisher available. Read these instructions thor-
oughly and follow all warnings or cautions included in literature
and attached to the unit. Consult local building codes and national
electric codes for special requirements.
Recognize safety information. This is the safety-alert symbol
.
When you see this symbol on the unit and in instructions or
manuals, be alert to the potential for personal injury.
Understand the signal words DANGER, WARNING, and CAU-
TION. These words are used with the safety-alert symbol. DAN-
GER identifies the most serious hazards which will result in severe
personal injury or death. WARNING signifies hazards which
could result in personal injury or death. CAUTION is used to
identify unsafe practices which would result in minor personal
injury or product and property damage.
Before installing, modifying, or servicing system, main elec-
trical disconnect switch must be in the OFF position. There
may be more than 1 disconnect switch. Lock out and tag
switch with a suitable warning label. Electrical shock can
cause personal injury or death.
INSTALLATION
Step 1—Check Equipment and Jobsite
UNPACK UNIT — Move to final location. Remove carton taking
care not to damage unit.
INSPECT EQUIPMENT — File claim with shipping company
prior to installation if shipment is damaged or incomplete. Locate
unit rating plate on unit service panel. (See Fig. 2.) It contains
information needed to properly install unit. Check rating plate to
be sure unit matches job specifications.
Step 2—Install on a Solid, Level Mounting Pad
If conditions or local codes require the unit be attached to pad,
tiedown bolts should be used and fastened through knockouts
provided in unit base pan. Refer to unit mounting pattern in Fig. 2
to determine base pan size and knockout hole location.
When installing, allow sufficient space for airflow clearance,
wiring, refrigerant piping, and service. Allow 30-in. (762mm)
clearance to service end of unit and 48 in. (1219mm) above unit.
For proper airflow, a 6-in. (152mm) clearance on 1 side of unit and
12 in. (305mm) on all remaining sides must be maintained.
Maintain a distance of 24 in. (610mm) between air conditioners.
Position so water, snow, or ice from roof or eaves cannot fall
directly on unit.
On rooftop applications, locate unit 6 in. (152mm) above roof
surface. Where possible, place unit above a load-bearing wall.
Arrange supporting members to adequately support unit and
minimize transmission of vibration to building. Consult local
codes governing rooftop applications.
Step 3—Replace Indoor AccuRater® Piston, if Required
Check indoor coil piston to see if it matches the required piston
shown on outdoor unit rating plate. If it does not match, replace
indoor coil piston with piston shipped with the outdoor unit. The
piston shipped with outdoor unit is correct for any approved indoor
coil combination.
Remove indoor coil piston if unit is to be installed on system
with a TXV metering device.
Step 4—Make Piping Connections
Outdoor units may be connected to indoor sections using accessory
tubing package or field-supplied refrigerant grade tubing of correct
Fig. 1—Model 38CKX
A97005
IP24
Visit www.carrier.com
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1
4
Tab
3a 2a
PC 101
Catalog No. 013-890
Printed in U.S.A.
Form 38CKX-C1SI
Pg 1
1-97
Replaces: New
"Loading the manual" means you need to wait until the file loads and becomes available for online reading. Some manuals are very large, and the time they take to appear depends on your internet speed.
Summary
size and condition. For tubing requirements beyond 50 ft (15.24m),consult Long-Line Application Guideline which is available atyour local distributor. NOTE: In some cases, noise in the living area has been traced to gas pulsations from improper installation of equipment. INSTALLATION RECOMMENDATIONS...
Relieve pressure and recover all refrigerant before systemrepair or final unit disposal to avoid personal injury or death.Use all service ports and open all flow-control devices,including solenoid valves. Do not operate unit in the vicinity of toxic or flammablematerial. Failure to follow this warni...
Use furnace transformer, fan-coil transformer, or accessory trans-former for control power, 24-v/40-va minimum. NOTE: Use of available 24-v accessories may exceed the mini- mum 40-va power requirement. Determine total transformer load-ing and increase the transformer capacity or split the load with ...