Page 2 - Duct-Free Systems Digest; Control Circuit Connections (Under Development) 21
Maintenance /Repair Application Product Installation Installation Application Product ? ? HELP HELP Duct-Free Systems Digest Duct-Free Systems Digest Maintenance /Repair ARI Capacities 1 Application Data 2 Electrical Data 3 System Charges 4 Features & Accessories 5 Guide Specifications 6 Model N...
Page 6 - CLICK HERE FOR HYDRONIC CASSETTE
ARI* Capacities In Ceiling Cassette Applications Indoor Outdoor Std. Net Cooling Total SEER EER Heating Heating Heating Heating Heating Section Section CFM BTUH kW High High High Low Low BTUH COP HSPF BTUH COP 40QKB024 38HDC018 525 18,300 1.76 11.0 10.4 40QKB024 38HDL018 525 17,800 1.68 11.4 10.8 40...
Page 7 - CLICK HERE FOR IN-CEILING CASSETTE
ARI* Capacities Hydronic Cassette Applications Unit Pipe Std. Net Cooling Sensible Heating Gallons Pressure Size Version CFM (Btuh) Cooling (Btuh) Per Drop (Btuh) Minute 004 2 420 6,900 6,100 13,600 1.4 1.3 008 2 420 13,200 10,100 23,000 2.7 3.1 010 2 400 13,700 9,600 20,700 2.9 6.0 4 440 13,280 9,8...
Page 11 - total heating requirement. For; For reliable operation, units should be level in all planes.
APPLICATION DATA 1 . Unit selection Select equipment to either match or be slightly less than anticipated peak cooling load. This provides better humidity control, fewer unit cycles, and less part-load operation. Heating and cooling design loads must both be checked. To meet heating requirements, ca...
Page 12 - These units should be mounted in the ceiling, preferably; These; Specifications Section #1; OUTDOOR
HIGH WALL UNITS — These units should be positioned as high as possible on the wall for best air circulation. Allow adequate clearances above the unit for servicing (removing unit covers). Place the unit in the middle (horizontally) of the wall selected (if possible). Select an outside wall if availa...
Page 13 - FAN COIL UNITS; Winter Start Kit; DO NOT; Drain connections
FAN COIL UNITS CONDITION 40QN 40QA 40QK 40CG 40CS 40HD Maximum Room Temperature (F) 84 84 95 Minimum Room Temperature (F) 64 64 55 Maximum Return Air (F) Dry-Bulb 85 85 85 Wet-Bulb 72 72 72 Minimum Return Air (F) Heat Pump 28 28 28 Maximum Saturated Suction Temperature (F) 55 55 55 Minimum Saturated...
Page 14 - POWER VENTILATION KIT AVAILABLE STATIC PRESSURE
11. Fresh air and ducting a. The ceiling-suspended fan coil units may bring in up to 30% fresh air. The percentage of air allowable iscalculated based on the unit high speed cfm. Air quan-tities above this level may exceed compressor maxi-mum saturated suction temperatures. A power ventilation kit i...
Page 32 - Accessories – Field Installed; Winter Start Control:; MORE ON NEXT PAGE
Accessories – Field Installed Low Ambient Kit: The Low Ambient Kit is a solid state head pressure controller designed to control condenser fan cycling, and is activated by a pressure sensor. It is specifically designed to control fan motor cycles in response to saturated condensing pressure. This de...
Page 33 - Filter Rack Package; Electric Heat Package; Boot Diffuser
Filter Rack Package – A fully assembled 2” Filter Rack and 1” T.A.W. filter with side access Multi-zone Adapter – Duct collars, internal insulation, and mounting holes. (3) Outlets for 024, (5) outlets for the 036, and (6) outlets for the 048 Electric Heat Package – Pre-assembled electric strip heat...
Page 34 - Fresh Air Intake & Filter Kit with Power Vent Fan Motor Kit:
Charcoal Filter Kit: The charcoal (carbon) filter kit is available for High Wall fan coils. This accessory improves indoor air quality by removing volatile organic compounds (VOCs), orders, and micro-particles from the air. The filter kit can be installed before or after the unit has been mounted on...
Page 36 - Dimensional Drawing; Two Way Air Conditioner
Dimensional Drawing OPEN SIZE BACK OPENINGS 2 3 4 5 6 7 6 A (in.) 9.1 13.4 17.7 22.1 26.4 30.7 (mm) 230 340 450 560 670 780 B (in.) 11.2 15.5 19.85 24.2 28.5 32.8 (mm) 284 394 504 514 724 834 A01101 WALL W W THICKNESS A B 173(6.8 ”) 45 (1.8 ") 112(4. 4 ”) Two Way Air Conditioner A01102 WALL W W ...
Page 37 - Guide Specifications – Section 6; Product
Guide Specifications – Section 6 Product Product High-Wall Heat Pump Units High-Wall Cooling Only Units Ceiling-Suspended Cooling Only Units Ceiling Suspended Heat Pump Units In-Ceiling Cassette Cooling Only Units In-Ceiling Cassette Heat Pump Units Outdoor Heat Pump Only Units Outdoor Cooling Only ...
Page 38 - Part 1 – General; QUALITY ASSURANCE; Part 2 – Products
Guide Specifications High-Wall Heat Pump Units HVAC Guide Specifications Size range: ¾ to 2 Tons Cooling Capacity Carrier Model Number: 40QNE/H & 38BK Part 1 – General 1.01 SYSTEM DESCRIPTION Indoor, wall-mounted, direct-expansion fan coil to be matched with the commercial condensing or heat pum...
Page 50 - 0CG and 38CG Cooling Only System -; 0CS and 38SB Heat Pump Two-Zone System -
1 Guide Specifications Console/Ceiling Suspended Cooling Only System Heat Pump System (With Supplemental Electric Heat) Multi-Zone System (Cooling Only & Heat Pump) HVAC Guide Specifications: 40CG and 38CG Cooling Only System - 1 ½, 2, and 2 ½ Tons Capacity 40CS and 38CS Heat Pump System - 1 ½, ...
Page 51 - internal spring isolation.
2 1.04 WARRANTY One-year parts, 5-year compressor limited warranty Part 2 – Product 2.01 EQUIPMENT A. Unit Cabinet: Outdoor cabinet shall be zinc-coated steel finished with baked enamel paint. Inlet grilles shall be attractively styled. Indoor cabinet is made up of high impact plastic. Mounting brac...
Page 52 - setpoint and space temperature.
3 MORE ON NEXT PAGE 5. Filter needs cleaning status indication. 6. Automatic airsweep control to provide on or off activation of airsweep louvers. 7. Auto mode to provide modulating fan speed based on difference between temperature setpoint and space temperature. 8. Fan only operation to provide air...
Page 58 - piston refrigerant metering device in the indoor
D. Coil: Coil shall be copper tube with aluminum fins and galvanized steel tube sheets. Fins shall be bonded to the tubes by mechanical expansion. A drip pan under the coil shall have a factory-installed condensate pump and drain connection for hose attachment to remove condensate. Note: The units u...
Page 60 - or an approved ducted cooling fan coil unit.
Guide Specifications Outdoor Heat Pump Only Units Commercial Condensing Units HVAC Guide Specifications Size range: ¾ to 5 Tons Cooling Capacity Carrier Model Number: 38BK, 38QR Part 1 – General 1.01 SYSTEM DESCRIPTION A. Outdoor-mounted, air-cooled split system outdoor section suitable for on-the-g...
Page 61 - have internal spring isolation.
Part 2 – Products 2.01 EQUIPMENT A. General: Factory assembled, single piece, air-cooled outdoor unit. Contained within the unit enclosure shall be all factory wiring, piping, controls, compressor, full (38BK009,012) or holding (38BK018,024 and 38QR) charge of R-22 refrigerant, and special features ...
Page 65 - horizontally. Fans shall blow air through the outdoor coil.
Part 2 – Products 2.01 EQUIPMENT A. General: Factory assembled, single piece, air-cooled outdoor unit. Contained within the unit enclosure shall be all factory wiring, piping, controls, compressor, full charge of R-22 refrigerant, and special features required prior to field start-up. B. Unit Cabine...
Page 68 - SYSTEM DESCRIPTION; One year parts, 5-year compressor limited warranty
Guide Specifications Satellite Systems Cooling Only Units HVAC Guide Specifications Size range: 2, 3, & 4 Tons Cooling Capacity Carrier Model Number: 40HD and 38HDC/HDL Part 1 – General 1.01 SYSTEM DESCRIPTION Indoor, above-ceiling mounted, direct-expansion fan coil to be matched with the 38 HDC...
Page 69 - Internal Condensate Pump:; adapter; Operating Characteristics:
E. Motors: Motors shall be permanently lubricated ball bearing with inherent overload protection. Fan motors shall be 3-speed. F . Internal Condensate Pump: The condensate pump shall remove condensate from the drain pan when gravity drainage cannot be used. The lift capability of the condensate pump...
Page 70 - Electronic Programmable Thermostat-; Thermostat shall be commercial grade and
K. Special Features (Field Installed): Electronic Programmable Thermostat- Thermostat shall be commercial grade and shall provide 7-day, 4-event scheduling. Integral sub-base shall be included. Thermostat shall also provide 3-speed fan switchover capability, air sweep auto changeover, and shall not ...
Page 72 - Physical Data : High Wall – Section 8; Cooling and Heat Pump Models
Physical Data : High Wall – Section 8 Product Product Cooling and Heat Pump Models
Page 74 - Cooling Only and Heat Pump Models – Under Ceiling; Cooling Only and Heat Pump Models – Console
Physical Data : Under Ceiling/Console -- Section 8 Product Product Cooling Only and Heat Pump Models – Under Ceiling Cooling Only and Heat Pump Models – Console
Page 77 - Physical Data : Cassette – Section 8
Physical Data : Cassette – Section 8 Product Product Cooling and Heat Pump Models Hydronic Cassette
Page 79 - Duct Free Systems - Physical Data - Hydronic Cassette
Duct Free Systems - Physical Data - Hydronic Cassette Unit 42WKN 004 008 010 016 020 Pipe Version 2 2 2 4 2 2 4 Operating Weight (lb) 57.8 60 64.4 65.6 108.9 115.6 117.8 Max Entering Water Temp Deg. F 180 180 180 180 180 180 180 Fan (qty) 1 1 1 1 2 2 2 RPM High 755 755 1015 1015 755 1140 1140 Med 54...
Page 80 - Physical Data : Satellite – Section 8; Cooling Only and Heat Pump Models
Physical Data : Satellite – Section 8 Product Product Cooling Only and Heat Pump Models
Page 82 - Physical Data : Condenser – Section 8; 8 Series AN & BK Condensers
Physical Data : Condenser – Section 8 Product Product 38 Series AN & BK Condensers 38 Series HDC Condensers 38 Series HDL Condensers 38 Series QRC Condensers 38 Series HDS Condensers 38 Series CG, CS, SB, and SC
Page 92 - dBa - Decibels on the A scale n/a - Not Available
Sound Data "Console" Fan Coils (A Weighted) Model Sound Sound Fan Sound Power Data Octave Band (dBa) Pressure (dBa) Power (dBa) Speed 125 250 500 1000 2000 4000 8000 n/a 65.0 High n/a n/a n/a n/a n/a n/a n/a 40CG-018---301RM n/a 58.0 Medium n/a n/a n/a n/a n/a n/a n/a 38.0 55.0 Low n/a n/a n...
Page 95 - NOT AVAILABLE AT THIS TIME
Sound Data "Satellite" Fan Coils (A Weighted) Model Sound Sound Fan Sound Power Data Octave Band (dBa) Pressure (dBa) Power (dBa) Speed 125 250 500 1000 2000 4000 8000 40HD-024 40HD-036 40HD-048 NOT AVAILABLE AT THIS TIME
Page 97 - System Cross Match
System Cross Match Cooling Only High Wall Heat Pump High Wall Nominal Indoor Indoor Outdoor Outdoor Nominal Indoor Indoor Outdoor Outdoor Capacity Unit Unit Unit Unit Capacity Unit Unit Unit Unit Carrier Bryant Carrier Bryant Carrier Bryant Carrier Bryant 9,000 40QNB009-1 619EAX0090E0 38AN-009-1 538...
Page 102 - System & Unit Specifications; Cooling Only System Specifications
System & Unit Specifications – Section 11 Product Product Cooling Only System Specifications Heat Pump System Specifications Unit Specifications
Page 109 - Heat Pump System Specifications
Heat Pump System Specifications High Wall Nominal Indoor Outdoor ARI Capacities ARI Sound Rating (dBa) Capacity Unit Unit C/O H/P CFM SEER EER HSPF Indoor Indoor Outdoor Outdoor Tons Btuh Btuh Power Pressure Power Pressure 0.8 40QNE009-1 38BK-009-1 8,700 9,000 252 10.0 9.2 6.8 50.6 42.3 63.4 55.1 1....
Page 115 - Unit Specifications
Unit Specifications Vert Vert Max Tube Connections Dimensions Model Voltage MCA MOCP Lift Drop Tube Liquid Vapor Width Height Depth Weight Note #1 Note #1 Lgth 40QNB009-1 115-1-60 Note #2 Note #2 -- -- -- -- -- 33.5 11.0 6.3 18.7 40QNB012-1 115-1-60 Note #2 Note #2 -- -- -- -- -- 33.6 11.8 7.3 24.2 ...
Page 116 - Condenser Only Ratings – Section 12; Application; HDC
Condenser Only Ratings – Section 12 Application Application HDC HDL
Page 117 - MORE
Condenser Only Ratings SST Air Temperature Entering Condenser (F) (F) 55 65 75 85 95 105 115 125 38HDC018 TCG 19.7 18.0 16.4 14.8 13.3 11.8 10.4 9.0 30 SDT 77.6 86.9 96.4 106.0 115.8 125.6 135.5 146.2 KW 1.1 1.2 1.3 1.4 1.4 1.5 1.5 1.5 TCG 22.1 20.3 18.6 16.9 15.2 13.7 12.1 10.5 35 SDT 78.8 87.8 97....
Page 118 - MORE ON PREVIOUS PAGE
Condenser Only Ratings SST Air Temperature Entering Condenser (F) (F) 55 65 75 85 95 105 115 125 38HDC036 TCG 33.6 32.1 30.5 28.7 25.7 23.1 20.6 18.3 30 SDT 80.9 90.2 99.6 110.2 127.2 141.4 154.4 166.5 KW 1.8 2.0 2.3 2.6 3.1 3.6 4.1 4.6 TCG 36.9 35.2 33.6 31.6 28.3 25.5 22.9 20.3 35 SDT 82.7 92.0 10...
Page 119 - Performance Data
38HDL CONDENSER-ONLY RATINGS See Legend on next page. Click here to view the next page of condenser-only performance data . SST (F) AIR TEMPERATURE ENTERING CONDENSER (F) 55 65 75 85 95 105 115 125 38HDL018 30 TCG 17.8 16.9 16.0 15.1 14.3 13.4 12.6 12.0 SDT 78.8 88.3 98.0 107.7 117.5 127.4 137.3 145...
Page 122 - Performance Data & Expanded Ratings - Systems Index Table
Performance Data & Expanded Ratings - Systems Index Table Multi Split 4 Ton 38HDS048 Click here to return to System Index Table. Indoor Section Net System Model Circuit Qty Cooling Index Capacity Table # 40QNB018 A 2 46,000 45 40QNB018 B 2 45 40QNB024 A 1 45,800 45 40QNB018 B 2 52 40QNB024 A 1 4...
Page 194 - Duct Free Systems - Piston/Charge Combinations
Duct Free Systems - Piston/Charge Combinations Cooling Only High Wall Heat Pump High Wall Indoor Outdoor AccuRater Charge Indoor Outdoor AccuRater AccuRater Charge Unit Unit Piston Lbs Unit Unit Piston Piston Lbs No Note #1 Indoor Outdoor Note #1 40QNB009 38AN-009-1 Cap Tube 1.5 40QNE009 38BK-009-1 ...
Page 199 - Refrigerant and Long Line Applications
Refrigerant and Long Line Applications – Section 15 Application Application AN009/012 & BK009/012 38HDC 38HDL38HDS 38QRC & 38BK018/024 38 C & S Series
Page 201 - Refrigerant Lines – 38HDC; Closed cell insulation is
Refrigerant Lines – 38HDC 1. The 38HDC units are shipped with a full charge of R-22 refrigerant based on the smallest charge combination. 2. All charges, line sizes, and capacities are based on the fan coil with the smallest charge and 25 feet ofrefrigerant lines. For system charge see Piston/Charge...
Page 202 - Long Line Applications – 38 HDC (continued); MORE INFO ON PREVIOUS PAGE. CLICK HERE TO RETURN.
Long Line Applications – 38 HDC (continued) 7. Changes in piston size. The metering device for long line applications must be adjusted to compensate for thefrictional losses due to the long refrigerant lines, refrigerant line accessories, and indoor coils above or belowthe outdoor unit. The AccuRate...
Page 203 - Refrigerant Lines - 38HDL
Refrigerant Lines - 38HDL 1. The 38HDL units are shipped with a full charge of R-22 refrigerant based on the smallest charge combination. 2. All charges, line sizes, and capacities are based on the fan coil with the smallest charge and 25 feet ofrefrigerant lines. For system charge see Piston/Charge...
Page 217 - Diagram #3
GROUND LEVEL TRAP "B" Solenoid* Diagram #3 *Not required for AN/BK009/012 – 38 CG, SC, CS, SB
Page 219 - Expanded Rating Section #13; Builder Module
SELECTION PROCEDURE (With Example) Rev “A” 09/19/01 I Determine the type of fan coil, which best suits the application (refer to Systems Index table in the Expanded Rating Section #13 ). Duct-free split systems have many types of fan coils to choose from with overlapping capacities. Select the syste...
Page 220 - Drawings – Section 17; Cooling Only & Heat Pump
Drawings – Section 17 Application Application 40QN - 009 40QN - 012 Cooling Only & Heat Pump 40QN - 018 40QN - 024 40QA - 024 40QA - 036 40QA - 048 40QA - 060 40QK - 024 40QK - 036 40QK - 048 40HD - 024 40HD - 036 40HD - 048 40CG 40CS
Page 221 - DIMENSIONAL DRAWING, BASE UNIT – 40QN009, 012 FAN COIL UNITS
DIMENSIONAL DRAWING, BASE UNIT – 40QN009, 012 FAN COIL UNITS UNIT 40QN WEIGHT A B C Lb Kg in. mm in. mm in. mm 009 18.7 8.5 33.46 850 11.02 280 6.29 160 012 24.2 11.0 36.61 930 11.81 300 7.28 185 NOTES:1. Dimensions are in inches. Dimensions in [ ] are in millimeters. 2. Direction of airflow. 3. Ref...
Page 222 - DIMENSIONAL DRAWING, BASE UNIT – 40QN018, 024 FAN COIL UNITS
DIMENSIONAL DRAWING, BASE UNIT – 40QN018, 024 FAN COIL UNITS UNIT 40QN WEIGHT 018 39 Lb [17.5 Kg] 024 43 Lb [19.5 Kg] NOTES:1. Dimensions in [ ] are in millimeters. 2. Direction if airflow. 3. Refrigerant, drain, and power connections may be made in unit rear, bottom, left side, or right side. 4. Re...
Page 228 - 8 HDC 018
Drawings – Section 17 Application Application 38 AN 009 38 AN - 012 38 HDC 018 Cooling Only 38 HDC 024 38 HDC 030 38 HDC 036 38 HDC 048 38 HDC 060 38 CG 38 HDS 024 Cooling Only 38 HDS 048 Multi-Split 38 SC 38 BK 009 38 BK 012 Heat Pump 38 BK 018 38 BK 024 38 QR 018 38 QR 024 38 QR 030 Heat Pump 38 Q...
Page 230 - DIMENSIONAL DRAWING, BASE UNIT — 38HDS CONDENSING UNITS
DIMENSIONAL DRAWING, BASE UNIT — 38HDS CONDENSING UNITS UNIT A B C D E F G H Ft-in. mm Ft-in. mm Ft-in. mm Ft-in. mm Ft-in. mm Ft-in. mm Ft-in. mm Ft-in. mm 024 2-1 1 ⁄ 8 638 3-0 15 ⁄ 16 938 1-2 9 ⁄ 16 370 1-4 406 1-11 7 ⁄ 16 595 1-5 3 ⁄ 16 437 1-5 1 ⁄ 2 445 1-8 1 ⁄ 8 511 048 3-1 3 ⁄ 16 945 3-8 9 ⁄ ...
Page 231 - DIMENSIONAL DRAWING, BASE UNIT – 38BK018, 024 HEAT PUMP UNITS
DIMENSIONAL DRAWING, BASE UNIT – 38BK018, 024 HEAT PUMP UNITS UNIT A B C D E F ft-in. mm ft-in. mm ft-in. mm ft-in. mm ft-in. mm ft-in. mm 018 2-1 1 ⁄ 8 638.2 3-0 15 ⁄ 16 938.2 1-2 9 ⁄ 16 369.9 1-4 406.4 1-11 7 ⁄ 16 595.3 1-5 3 ⁄ 16 436.6 024 2-1 1 ⁄ 8 638.2 3-0 15 ⁄ 16 938.2 1-2 9 ⁄ 16 369.9 1-4 40...
Page 235 - AccuRater; Cleaning and/or Replacing
AccuRater It is extremely important that all refrigerant lines and the AccuRater metering device be insulated on heat pumps. On cooling only units, the liquid line may be left un-insulated. Use any acceptable heat resistant closed-cell foam insulation (minimum 3/8-in. wall thickness). When insulatin...
Page 237 - Charge Verification – Section 19; Installation
Charge Verification – Section 19 Installation Installation 38HDC, HDL, QR, CG, CS 38 HDS SB, SC (MULTISPLIT)
Page 241 - Subcooling Charging Method; use the
REFRIGERANT CHARGING (Multi Split) WARNING: To prevent personal injury, wear safety glasses and gloves when handling refrigerant. Do not overcharge system this can cause compressor flooding. WARNING: Service valves must be fully back seated to close service port. There is no Schrader valve at the se...
Page 243 - Controls – Section 20; High Wall
Controls – Section 20 Installation Installation High Wall Under Ceiling, Cassette, & Satellite 38HDS Console
Page 244 - 0QNB/QNE control system; Off Mode; Cooling Mode
Controls — systems using high wall fan coils 40QNB/QNE control system The 40QN unit is equipped with a microprocessor control, which operates the system. This control is located in the control box of the fan coil unit, with thermistors located in the fan coil inlet and on the indoor coil. The 40QNE ...
Page 245 - Maximum Dehumidification Mode; Heat Pump Heating Mode; Sleep Mode
• Maximum Dehumidification Mode — When the dehumidification mode is selected, the indoor fan will operate continuously at the selected speed if the speed is high, medium, or low. If the indoor fan is in auto mode, the fan changes operating speeds depending on the room temperature. If the room temper...
Page 247 - Electronic Control Defrost Regions Map --
*Minimum unit run time starts when outdoor coil temperature drops below 34 F, then accumulates run time regardless of coil temperature. Electronic Control Defrost Regions Map -- GO TO PAGE 2
Page 249 - Fan operation
Controls — systems using Under Ceiling, Cassette or Satellite fan coils Automatic air sweep All Under Ceiling units are equipped with an automatic air sweep feature, which automatically directs the airflow louvers up and down to provide optimum room air circulation. If the auto sweep feature is not ...
Page 250 - System safeties
DFB switches the unit back to normal heating operation. If the DFT remains closed the DFB switches the unit back to heating operation after 10 minutes. When the DFB changes back to heating mode, the RVR (reversing valve relay) is de-energized and the reversing valve switches back to heating operatio...
Page 251 - Unit operation; Fan coil units
Controls - 38HDS Unit operation NOTE: AUTO fan mode is used as the unit operation example for ALL fan coil units in this section. Contact your local Carrier dealer for operation information in other fan modes. Fan coil units — Each fan coil unit has a self-contained control system that determines th...
Page 252 - 8HDS-microprocessor control of outdoor fan; Status indicator lights
the 38HDS microprocessor if the other refrigerant circuit is still operating. The outdoor fan only stops when both compressors are off. Refer to 38HDS Microprocessor Control of Outdoor Fan section below for more details. 38HDS-microprocessor control of outdoor fan — The microprocessor control has a ...
Page 253 - Thermostat
Thermostat Installation Installation Operation Photographs and illustrations
Page 255 - Menu Select Button; Operation Mode; Timer Set Buttons
4 • When transmitting a command from the remote controller,point the transmitter toward the receiver on the right side of theair conditioner. • The air conditioner confirms the receipt of a command bysounding two beeps. • Make sure that no objects block the clear line of sight betweenthe remote cont...
Page 256 - CHANGING THE FAN SPEED; CAUTION
5 INSERTING BATTERIES IN THE REMOTE CONTROLLER Before using the remote controller you must insert two 1.5VAAA Alkaline batteries, as follows: • Slide off and remove the battery compartment cover. • Insert the batteries, making sure to follow the polarity (+,-)markings. • Replace the battery compartm...
Page 257 - IMPORTANT; PM
6 • Press the On/Off button 3 to transmit your selections to theair conditioner 1. If you choose to place the airflow deflector in a fixed posi- tion, the deflector stops at the angle in which it was locatedwhen you pressed the On/Off button. NOTE: When you have finished selecting the various menus ...
Page 258 - SETTING A DAILY TIMER PERIOD; The daily timer operates only when there is a direct; CANCELING A DAILY TIMER PERIOD; • Press the TIMER button; ROOM AIR TEMPERATURE DISPLAY; When the remote controller is ON:; DELAYED START/STOP OPERATION
7 • Scroll through the Timer periods as explained in the previoussection • Choose the SLEEP Timer period • Enter the desired Start/Stop times (SLEEP-START andSLEEP-STOP). • Press the SET button. SETTING A DAILY TIMER PERIOD You can set the Timer periods so that the air conditioner operatesautomatica...
Page 259 - WARNING
8 When the air conditioner is OFF: • Press DELAY button. The clock advances one hour, while theword START and the number 3 flash. • Each additional pressing of the DELAY button advances theclock by one hour. • Make sure you point the remote controller at the air condi-tioner while you press the DELA...
Page 260 - THE DISPLAY PANEL; Diagram Callout
9 MORE ON NEXT PAGE airborne particles. More frequent cleaning may be neces-sary depending on indoor air quality. 3. Use drapes, curtains, or shades to keep direct sunlight from heating room. 4. Do not obstruct front grille air intake section. 5. Start your air conditioner before outdoor temperature...
Page 262 - Installation Diagrams – Section 22
Installation Diagrams – Section 22 Installation Installation 40 QN 009 & 012 40 QN 018 & 024
Page 265 - Installation Diagram
Installation Diagram s – Section 22 Installation Installation 40 QA 40 C
Page 266 - TYPICAL INSTALLATION — CEILING-SUSPENDED SYSTEMS
TYPICAL INSTALLATION — CEILING-SUSPENDED SYSTEMS LEGEND f — Phase NEC — National Electrical Code PipingLine Voltage24 VThermistor *Standard. †Accessory item. **Field supplied. NOTES:1. All piping must follow standard refrigerant piping techniques. 2. All wiring must comply with the applicable local ...
Page 268 - HD
Installation Diagram s – Section 22 Installation Installation 40 Q K 40 HD
Page 269 - TYPICAL INSTALLATION — IN-CEILING CASSETTE SYSTEMS
TYPICAL INSTALLATION — IN-CEILING CASSETTE SYSTEMS LEGEND f — Phase NEC — National Electrical Code PipingLine Voltage24 V *Standard. †Accessory item. **Field supplied. NOTES:1. All piping must follow standard refrigerant techniques.2. All wiring must comply with applicable local and national codes.3...
Page 271 - Service – Section 23; 0 QN – High Wall
Service – Section 23 Installation Installation 40 QN – High Wall 40 QA – Under Ceiling 40 CG and CS – Console 40 HD – Satellite 40 QK – Cassette
Page 272 - SERVICE – High Wall Systems; SYSTEM SAFETIES AND INTERLOCKS
SERVICE – High Wall Systems WARNING: When servicing unit, turn off all electric power to unit to avoid shock hazard or injury from rotating parts. CAUTION: Do not vent refrigerant to atmosphere when servicing unit. Recover refrigerant during system repair or unit removal. DIAGNOSTIC CODES This unit ...
Page 275 - SERVICE; BEFORE CALLING FOR SERVICE; If System Fails To Operate
SERVICE Under Ceiling, Cassette, Console, & Satellite Fan Coils WARNING: When servicing unit, turn off all electric power to unit to avoid shock hazard or injury from rotating parts. CAUTION: Do not vent refrigerant to atmosphere when servicing unit. Recover refrigerant during system repair or u...
Page 277 - OUTDOOR FAN; HIGH-PRESSURE RELIEF VALVE
SERVICE – 38HDC, 38QR, & 38BK018,024 WARNING: Before performing recommended maintenance, be sure unit main power switch is turned off. Failure to do so may result in electrical shock or injury from rotating fan blade. OUTDOOR FAN A reinforced wire mount holds the outdoor fan assembly in position...
Page 278 - CRANKCASE HEATER (If Unit is so Equipped); SERVICE VALVES; REVERSING VALVE
NOTE: If pressure switch needs to be replaced, there is a Schrader valve located under the switch so that system will not need to be evacuated. CRANKCASE HEATER (If Unit is so Equipped) Heater prevents refrigerant migration and compressor oil dilution during shutdown when compressor is not operating...
Page 281 - SERVICE – 38HDL
SERVICE – 38HDL WARNING: Before performing recommended maintenance, be sure unit main power switch is turned off. Failure to do so may result in electrical shock or injury from rotating fan blade. OUTDOOR FAN A reinforced wire mount holds the outdoor fan assembly in position. See Fig. 11 for proper ...
Page 282 - Fig. 11 – Condenser Fan Mounting Positions
Page 283 - SERVICE – Multi Split
SERVICE – Multi Split WARNING: Before performing recommended maintenance, be sure unit main power switch is turned off, and be sure all disconnects for indoor fan coil units are open. These systems typically have one disconnect per fan coil unit. Failure to turn off unit main power and open all disc...
Page 285 - Figure 13 – Condenser-Fan Mounting Positions
Page 287 - Start-Up Instructions – Section 24; Check List
Start-Up Instructions – Section 24 Installation Installation 40 QN Check List
Page 289 - 0 C – Console
Start-Up Instructions – Section 24 Installation Installation 40 C – Console 40 QA – Under Ceiling Check List
Page 290 - START-UP – Under Ceiling Systems; may result. Make the following checks and complete the; AFTER EXTENDED SHUTDOWN; Automatic Air Sweep; OPERATING MODE MEMORY
START-UP – Under Ceiling Systems WARNING: Never operate unit without a filter or with grille removed; damage to the unit or personal injury may result. Make the following checks and complete the Start-Up Checklist before system start-up. Refer to Installation, Start-Up and Service Instructions for s...
Page 291 - START-UP – Console Systems
START-UP – Console Systems WARNING: Never operate unit without a filter or with grille removed; damage to the unit or personal injury may result. Make the following checks and complete the Start-Up Checklist before system start-up. Refer to Installation, Start-Up and Service Instructions for system ...
Page 297 - DO NOT open valves that do not have fan coil units connected to them.
START-UP - Multi-Split LEAK TEST Field piping and all tubing connections must be leak tested by the pressure method. Use R-22 at approximately 25 psig backed up with an inert gas to reach a total system pressure not to exceed 245 psig. EVACUATE AND DEHYDRATE Field piping and fan coil must be evacuat...
Page 299 - Outdoor Unit; Piping; Units with Wired Remote Controller; Red
START-UP CHECKLIST Outdoor Unit: Model Number ________________ Serial Number ____________________ Indoor Unit: Model Number __________________ Serial Number ____________________ PRE-START-UP (For One or More Systems) Outdoor Unit IS THERE ANY SHIPPING DAMAGE? (Y/N) ___________________ IF SO, WHERE? ...
Page 300 - Cassette Fan Coil Units
CHECK MOUNTING OF SUBBASE TO WALL, IS IT TIGHT (DO NOT APPLY EXCESSIVE FORCE TO MOUNTING SCREW)? (Y/N) _____ Units with Wireless Remote Controller CHECK MOUNTING OF INTERFACE BOARD; ARE STANDOFFS USED (TO MAINTAIN FIXED SEPARATION ABOVE SHEET METAL CHASSIS)? (Y/N) _____ CHECK CONNECTION OF POWER SUP...
Page 304 - Cleaning & Maintenance – Section 26
Cleaning & Maintenance – Section 26 Maintenance/Repair Maintenance/Repair 40QN
Page 305 - Table 9 — Cleaning and Maintenance Schedule
40 QN CLEANING AND MAINTENANCE To avoid the possibility of electric shock, before per-forming any cleaning and maintenance operations al-ways turn off power to the system by pressing theorange ON/OFF button on the remote controller. Turnoff the outdoor disconnect switch located near the out-door uni...
Page 306 - To Clean Indoor Unit Front Panel —; To Clean Indoor Coil —; Fig. 18 — Installing or Replacing Batteries
To Clean Indoor Unit Front Panel — If the front panel of the unit becomes dirty or smudged, wipe the out-side of the front panel with a soft dry cloth. If necessary, usea mild liquid detergent and wipe off carefully with a dry cloth. When cleaning the front panel, NEVER use water hot-ter than 105 F,...
Page 307 - Cleaning & Maintenace – Section 26
Cleaning & Maintenace – Section 26 Maintenance/Repair Maintenance/Repair 40 QA 40 CG, CS
Page 308 - 0 QA CLEANING AND MAINTENANCE; Lubrication —; Fig. 23 — Cleaning Filters
40 QA CLEANING AND MAINTENANCE To avoid the possibility of electric shock, before per-forming any cleaning and maintenance operations, al-ways turn off power to the system by pressing the modebutton on the remote thermostat until the display shows‘‘OFF,’’ and turning off the outdoor disconnect switc...
Page 309 - Table 8 – Cleaning and Maintenance Schedule; To Clean Indoor Unit Bottom Panel –
Table 8 – Cleaning and Maintenance Schedule TASK MONTHLY QUARTERLY YEARLY INDOOR UNIT Clean Air Filters X Clean Drain Pipe X Clean Condensate Drain Pan X Clean Indoor Coil X Clean Indoor Unit Front Panel X OUTDOOR UNIT Clean the Fins From Outside X Open the Unit and Clean Fins Inside X Remove Dust F...
Page 312 - Fig. 18 – Intake Grille Slotted Screws
40 QK SERVICE AND MAINTENANCE Remove unit grille, filter, and condensate pan for clean- ing, lubricating, or replacing parts. To avoid personal injury or damage to unit, do not ser- vice until all power sources are shut down, locked out, and tagged out. Failure to do so could result in personal inju...
Page 316 - Table 7 – Recommended Compressor Oils
38 HDC, 38 HDL, 38 QR MAINTENANCE WARNING Before performing recommended maintenance, be sure unit main power switch is turned off. Failure to do so may result in electric shock or injury from rotating fan blade. I. LUBRICATION A. Fan-Motor Bearings Oiling hole are provided at each end of outdoor-fan...
Page 317 - 8 HDS MAINTENANCE
38 HDS MAINTENANCE WARNING Before performing recommended maintenance, be sure unit main power switch is turned off. Failure to do so may result in electric shock or injury from rotating fan blade. I. LUBRICATION A. Fan-Motor Bearings Oiling hole are provided at each end of outdoor-fan motor. Remove ...
Page 320 - CE
38 CG, CS, SB, SC CARE AND MAINTENA N CE Step 1 – Maintenance (Outdoor Unit) WARNING Before performing recommended maintenance, be sure unit main power switch is turned off. Failure to do so may result in electric shock or injury from rotating fan blade. CLEANING COILS Coil should be washed out with...
Page 321 - Troubleshooting & Fault Codes – Section 27; 0 QN – Troubleshooting
Troubleshooting & Fault Codes – Section 27 Maintenance/Repair Maintenance/Repair 40 QN – Troubleshooting 40 QN – Fault Codes
Page 322 - Troubleshooting; Failure; Fan coil does not power up
HWError Code.doc MORE ON NEXT PAGE 2/09/01 Troubleshooting Failure Check/Action Fan coil doesn’t receive signal from remote. No BEEP heard from fan coil. Unit runs in TEST mode. • Check plug connection at receiver board and main board(CN12) • Check remote for signal transmission indicator • Operate ...
Page 323 - Unit stops during operation
HWError Code.doc 02/09/01 • Check CN1 plug for voltage If voltage is recorded at the CN1 plug and LED does not flash, replace board. Insufficient cooling, Insufficient Heating (Heat Pump) • Check for blocked air filter – clean filter • Outdoor unit obstructed – remove obstruction • Check temperature...
Page 324 - High Wall Diagnostic Codes; Error Code; Reversing Valve malfunction; Relay; board. Continue if voltage
HWError Code.doc MORE ON NEXT PAGE 02/09/01 High Wall Diagnostic Codes Error Code Flashes * Error Check/Action 2 Room Air thermistor malfunction If system reads thermistor value: Short condition: greater or = 194 deg F Open condition: less or = -40 deg F Check plug connection on main circuit board (...
Page 325 - Indoor Fan failure
HWError Code.doc 02/09/01 7 Outdoor Air thermistor malfunction If the following occurs with thermistor: Short condition: greater or = 194 deg F Open condition: less or = -40 deg F Check plug connection on main circuit board (CN17). Check termistor cable connection at terminal board on indoor and out...
Page 326 - 0 QA – Troubleshooting
Troubleshooting & Fault Codes – Section 27 Maintenance/Repair Maintenance/Repair 40 QA – Troubleshooting Thermostat – see Controls 40 CG, CS Troubleshooting (for Remote, see Control s )
Page 327 - TROUBLESHOOTING; Table 9 –
TROUBLESHOOTING If the under-ceiling fan coil unit fails to start or operate properly, sometimes the problem is minor and can be handled without a service call. Refer to Table 9 for some common problems, causes, and typical solutions. See Fig. 25 and 26 for additional system troubleshooting details....
Page 331 - 0 QK – Troubleshooting
Troubleshooting & Fault Codes – Section 27 Maintenance/Repair Maintenance/Repair 40 QK – Troubleshooting Thermostat – see Controls
Page 332 - Trouble Shooting – Cassette
Trouble Shooting – Cassette If any of the original wire furnished must be replaced, it must be replaced with type 90 deg C or its equivalent. Wire in accordance with National Electric Code (NEC) and any local codes. Transformer is thermally protected and will reset automatically. Indoor fan motors h...
Page 333 - 0 HD – Troubleshooting
Troubleshooting & Fault Codes – Section 27 Maintenance/Repair Maintenance/Repair 40 HD – Troubleshooting Thermostat – see Controls
Page 334 - Trouble Shooting – Satellite
Trouble Shooting – Satellite If any of the original wire furnished must be replaced, it must be replaced with type 90 deg C or its equivalent. Wire in accordance with National Electric Code (NEC) and any local codes. Transformer is thermally protected and will reset automatically. Indoor fan motors ...
Page 335 - 8 HDC – Troubleshooting
Troubleshooting & Fault Codes – Section 27 Maintenance/Repair Maintenance/Repair 38 HDC – Troubleshooting 38 HDL – Troubleshooting 38 HDS – Troubleshooting 38 HDS – Fault Codes38 QR – Troubleshooting, Cooling Cycle 38 QR – Troubleshooting, Heating Cycle 38 CG, CS, SB, SC – Troubleshooting