Carrier 38AKS013-024- Manual
Carrier 38AKS013-024– Manual, read for free online in PDF format. We hope this helps you resolve any issues you may have. If you have further questions, please contact us through the contact form.
Table of Contents:
- Page 10 – TXV — Thermostatic Expansion Valve
- Page 12 – System Check
- Page 13 – Fig. 9 — Operating Oil Levels
- Page 17 – Fan cycling is a standard; Fig. 13 — Compressor Capacity Control Unloader
- Page 20 – TROUBLESHOOTING; PROBLEM
- Page 23 – A. Preliminary Information; OUTDOOR UNIT
Installation, Start-Up and
Service Instructions
CONTENTS
Page
SAFETY CONSIDERATIONS
. . . . . . . . . . . . . . . . . . . 1
INSTALLATION
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-12
Step 1 — Complete Pre-Installation
Checks
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Step 2 — Rig and Mount the Unit
. . . . . . . . . . . . . 8
Step 3 — Complete Refrigerant Piping
Connections
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Step 4 — Install Accessories
. . . . . . . . . . . . . . . . 10
Step 5 — Complete Electrical
Connections
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
PRE-START-UP
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
System Check
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Leak Test and Dehydration
. . . . . . . . . . . . . . . . . . 12
Turn On Crankcase Heater
. . . . . . . . . . . . . . . . . . . 12
Preliminary Charge
. . . . . . . . . . . . . . . . . . . . . . . . . . 12
START-UP
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13-16
Preliminary Checks
. . . . . . . . . . . . . . . . . . . . . . . . . 13
Preliminary Oil Charge
. . . . . . . . . . . . . . . . . . . . . . 13
Start Unit
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Adjust Refrigerant Charge
. . . . . . . . . . . . . . . . . . . 13
Check Compressor Oil Level
. . . . . . . . . . . . . . . . 13
Final Checks
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
OPERATING SEQUENCE
. . . . . . . . . . . . . . . . . . . . 17
Cooling
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Heating
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Fan Cycling
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Winter Start Control
. . . . . . . . . . . . . . . . . . . . . . . . . 17
SERVICE
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17-19
Capacity Control
. . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Head Pressure Control
. . . . . . . . . . . . . . . . . . . . . . 17
Time Guard
T
II Circuit
. . . . . . . . . . . . . . . . . . . . . . . 17
Winter Start Control
. . . . . . . . . . . . . . . . . . . . . . . . . 18
Crankcase Heater
. . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Compressor Protection
. . . . . . . . . . . . . . . . . . . . . . 18
High-Pressure Switches
. . . . . . . . . . . . . . . . . . . . . 18
Low-Pressure Switches
. . . . . . . . . . . . . . . . . . . . . 18
Outdoor Fans
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Lubrication
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Cleaning Coils
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
TROUBLESHOOTING
. . . . . . . . . . . . . . . . . . . . . . 20,21
START-UP CHECKLIST
. . . . . . . . . . . . . . . . CL-1,CL-2
SAFETY CONSIDERATIONS
Installing, starting up, and servicing air-conditioning equip-
ment can be hazardous due to system pressures, electrical
components, and equipment location (roofs, elevated struc-
tures, etc.).
Only trained, qualified installers and service mechanics
should install, start-up, and service this equipment (Fig. 1).
Untrained personnel can perform basic maintenance func-
tions such as cleaning coils. All other operations should be
performed by trained service personnel.
When working on the equipment, observe precautions in
the literature and on tags, stickers, and labels attached to the
equipment.
Follow all safety codes. Wear safety glasses and work gloves.
Keep quenching cloth and fire extinguisher nearby when braz-
ing. Use care in handling, rigging, and setting bulky equip-
ment.
ELECTRIC SHOCK HAZARD
Separate power sources (main and control
power circuits) are used for these units. Be
sure both main and control power circuits are
disconnected before servicing.
INSTALLATION
Step 1 — Complete Pre-Installation Checks
UNCRATE UNIT — Remove unit packaging except for the
top skid assembly, which should be left in place until after
the unit is rigged into its final location.
INSPECT SHIPMENT — File claim with shipping com-
pany if shipment is damaged or incomplete.
CONSIDER SYSTEM REQUIREMENTS
• Consult local building codes and National Electrical Code
(NEC, U.S.A.) for special installation requirements.
• Allow sufficient space for airflow clearance, wiring,
refrigerant piping, and servicing unit. See Fig. 1. See
Fig. 2 for unit component locations.
• Locate unit so that outdoor coil (condenser) airflow is un-
restricted on all sides and above.
• Unit may be mounted on a level pad directly on the base
channels or mounted on raised pads at support points. See
Tables
1A-1D
for
unit
operating
weights.
See
Table 2 for weight distribution based on recommended sup-
port points.
NOTE: If vibration isolators are required for a particular
installation, use the data in Table 2 to make the proper
selection.
38AKS013-024
Air-Cooled Condensing Units
50/60 Hz
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1
4
Tab
3a 2a
PC 111
Catalog No. 563-701
Printed in U.S.A.
Form 38AKS-3SI
Pg 1
9-98
Replaces: 38AKS-2SI
"Loading the manual" means you need to wait until the file loads and becomes available for online reading. Some manuals are very large, and the time they take to appear depends on your internet speed.
Other Manuals for Carrier 38AKS013-024
Summary
INSTALL FILTER DRIER(S) AND MOISTURE INDICA-TOR(S) — Every unit should have a filter drier and liquid-moisture indicator (sight glass). In some applications, dependingon space and convenience requirements, it may be desirableto install 2 filter driers and sight glasses. One filter drier andsight gla...
Table 6B — Electrical Data (3 Ph/50 Hz) UNIT 38AKS UNIT COMPR FAN MOTORS 230 v (Single Phase) Model Volts MCA ICF MOCP (Fuse Only) RLA LRA TotalFans FLA (ea) Fan No. kW Nameplate Supplied* Min Max 1 2 013 803 230 198 264 47.5 134 75 32.9 128 2 2.9 3.5 1.20 903 400 342 457 31.4 80 50 20.0 74 014 803 ...
START-UP Compressor crankcase heater must be on for 24 hours before start-up. After the heater has been on for 24 hours,the unit can be started. If no time has elapsed since the pre-liminary charge step has been completed, it is unnecessaryto wait the 24-hour period. Preliminary Checks 1. Ensure tha...