Carrier 38AE016 - Manual
Carrier 38AE016 – Manual, read for free online in PDF format. We hope this helps you resolve any issues you may have. If you have further questions, please contact us through the contact form.
Table of Contents:
- Page 6 – Table 2 — Weight Distribution; If it is necessary to roll the unit into position, mount the; Table 3 — Liquid Line Data; Table 4B — Refrigerant Piping Sizes — 50 Hz; Fig. 3 — Compressor Mounting
- Page 7 – Select the filter drier for maximum unit capacity and mini-; Step 4 — Install Accessories —; Route power wires through opening in unit end panel to; TXV — Thermal Expansion Valve; — National Electrical Code; Fig. 6 — Main Power Supply Wiring
- Page 8 – — Compressor Contactor; HD; IFC; Fig. 7 — Remote Thermostat Wiring
- Page 9 – Fig. 8 — Operating Oil Levels
- Page 13 – Fan cycling is a standard; Fig. 12 — Compressor Capacity Control Unloader
- Page 14 – Fig. 14 — Outdoor Fan
- Page 15 – TROUBLESHOOTING; PROBLEM
- Page 18 – PACKAGED SERVICE TRAINING; • Unit Familiarization
- Page 19 – A. Preliminary Information; OUTDOOR UNIT
Installation, Start-Up and
Service Instructions
CONTENTS
Page
SAFETY CONSIDERATIONS
. . . . . . . . . . . . . . . . . . . 1
INSTALLATION
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-8
Step 1 — Complete Pre-Installation Checks
. . . . 1
Step 2 — Rig and Mount the Unit
. . . . . . . . . . . . . 6
Step 3 — Complete Refrigerant Piping
Connections
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Step 4 — Install Accessories
. . . . . . . . . . . . . . . . . 7
Step 5 — Complete Electrical Connections
. . . . 7
PRE-START-UP
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Evacuate and Dehydrate
. . . . . . . . . . . . . . . . . . . . . . 9
Leak Test
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Turn On Crankcase Heaters
. . . . . . . . . . . . . . . . . . 9
Add Preliminary Charge
. . . . . . . . . . . . . . . . . . . . . . 9
Before Starting Unit
. . . . . . . . . . . . . . . . . . . . . . . . . . 9
START-UP
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-13
To Start Unit
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Oil Charge
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Refrigerant Charge
. . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Check Operation
. . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
OPERATING SEQUENCE
. . . . . . . . . . . . . . . . . . . . 13
Cooling
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Heating
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Fan Cycling
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Winter Start Control
. . . . . . . . . . . . . . . . . . . . . . . . . 13
SERVICE
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13,14
Capacity Control
. . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Head Pressure Control
. . . . . . . . . . . . . . . . . . . . . . 13
Time Guard
T
II Circuit
. . . . . . . . . . . . . . . . . . . . . . . 13
Winter Start Control
. . . . . . . . . . . . . . . . . . . . . . . . . 13
Crankcase Heater
. . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Outdoor Fan
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Lubrication
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Cleaning Coils
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
TROUBLESHOOTING
. . . . . . . . . . . . . . . . . . . . . . 15,16
START-UP CHECKLIST
. . . . . . . . . . . . . . . . CL-1,CL-2
SAFETY CONSIDERATIONS
Installing, starting up, and servicing air-conditioning equip-
ment can be hazardous due to system pressures, electrical
components, and equipment location (roofs, elevated struc-
tures, etc.).
Only trained, qualified installers and service mechanics
should install, start-up, and service this equipment (Fig. 1).
Untrained personnel can perform basic maintenance func-
tions such as cleaning coils. All other operations should be
performed by trained service personnel.
When working on the equipment, observe precautions in
the literature and on tags, stickers, and labels attached to the
equipment.
Follow all safety codes. Wear safety glasses and work gloves.
Keep quenching cloth and fire extinguisher nearby when
brazing. Use care in handling, rigging and setting bulky
equipment.
ELECTRIC SHOCK HAZARD
Separate power sources (main and control
power circuits) are used for these units. Be
sure both main and control power circuits are
disconnected before servicing.
INSTALLATION
Step 1 — Complete Pre-Installation Checks
UNCRATE UNIT — Remove unit packaging except for the
top skid assembly, which should be left in place until after
the unit is rigged into its final location.
INSPECT SHIPMENT — File claim with shipping com-
pany if shipment is damaged or incomplete.
CONSIDER SYSTEM REQUIREMENTS
• Consult local building codes and National Electrical Code
(NEC, U.S.A.) for special installation requirements.
• Allow sufficient space for airflow clearance, wiring, re-
frigerant piping, and servicing unit. See Fig. 1. See
Fig. 2 for unit component locations.
• Locate unit so that outdoor coil (condenser) airflow is un-
restricted on all sides and above.
• Unit may be mounted on a level pad directly on the base
channels or mounted on raised pads at support points. See
Table 1A-1D for unit operating weights. See Table 2 for
weight distribution based on recommended support points.
NOTE: If vibration isolators are required for a particular
installation, use the data in Table 2 to make the proper
selection.
38AE012,014,016
38AKS024
Air-Cooled Condensing Units
50/60 Hz
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1
4
Tab
3a 2a
PC 111
Catalog No. 563-746
Printed in U.S.A.
Form 38A-4SI
Pg 1
4-94
Replaces: 38AE-17SI
"Loading the manual" means you need to wait until the file loads and becomes available for online reading. Some manuals are very large, and the time they take to appear depends on your internet speed.
Summary
Table 2 — Weight Distribution UNIT WEIGHT — lb (kg) Total Operating Support Point A B C D 38AE012 732 (333) 142 (65) 138 (63) 225 (102) 227(103) 38AE014 779 (354) 143 (65) 140 (64) 247 (112) 249 (113) 38AE016 789 (359) 143 (65) 143 (65) 250 (114) 253 (115) 38AKS024 900 (408) 178 (81) 168 (76) 269 (1...
INSTALL FILTER DRIER(S) AND MOISTURE INDICA-TOR(S) — Every unit should have a filter drier and liquid-moisture indicator (sight glass). In some applications, dependingon space and convenience requirements, it may be desirableto install 2 filter driers and sight glasses. One filter drier andsight gla...
Table 5A — Electrical Data (3 Ph/60 Hz) UNIT UNIT COMPR FAN MOTORS (Single Phase) Model Volts MCA ICF MOCP(Fuse) RLA LRA TotalFans FLA (ea) Fan No. kW Nameplate Supplied* Min Max 1 2 38AE012 501 208-230 187 253 62.5 178 100 43.6 170 2 4.3 3.7 1.41 201 380 342 418 35.0 101 50 24.0 93 4.3 3.7 601 460 ...