Carrier 33CSPREMLK - Manual

Carrier 33CSPREMLK

Carrier 33CSPREMLK – Manual, read for free online in PDF format. We hope this helps you resolve any issues you may have. If you have further questions, please contact us through the contact form.

1 Page 1
2 Page 2
3 Page 3
4 Page 4
5 Page 5
6 Page 6
7 Page 7
8 Page 8
9 Page 9
10 Page 10
11 Page 11
12 Page 12
13 Page 13
14 Page 14
15 Page 15
16 Page 16
17 Page 17
18 Page 18
19 Page 19
20 Page 20
21 Page 21
22 Page 22
23 Page 23
24 Page 24
25 Page 25
26 Page 26
27 Page 27
28 Page 28
29 Page 29
30 Page 30
31 Page 31
32 Page 32
33 Page 33
34 Page 34
35 Page 35
36 Page 36
37 Page 37
38 Page 38
39 Page 39
40 Page 40
41 Page 41
42 Page 42
43 Page 43
44 Page 44
Page: / 44

Table of Contents:

  • Page 3 – The PremierLink controller can be; Fig. 1 — PremierLinkTM Control Module
  • Page 4 – Fig. 2B — Typical PremierLink Control Wiring — 38AKS013-024 Units
  • Page 5 – Fig. 2C — Typical PremierLinkTM Control Wiring — 38ARD012 Units; Fig. 2D — Typical PremierLink Control Wiring — 38AKS028-044 Units
  • Page 6 – Fig. 2E — Typical PremierLinkTM Control Wiring — 38AH024-034 Units; Fig. 2F — Typical PremierLink Control Wiring — 38AH004-104 Units
  • Page 7 – Fig. 2G — Typical PremierLinkTM Control Wiring — 38AQ007 Units
  • Page 8 – Table 1 — PremierLink Controller Inputs and Outputs; PremierLink Connections; Fig. 2I — Typical PremierLinkTM Control Wiring — 38AQS012-016 Units
  • Page 9 – Table 2 — Color Code Recommendations
  • Page 10 – Cool
  • Page 11 – FIELD WIRING; Fig. 5 — T58 Communicating Sensor
  • Page 12 – SPACE TEMPERATURE AVERAGING — 4 SENSOR APPLICATION; Fig. 6 — Space Temperature Averaging
  • Page 18 – Con nect to CCN Commu nication Bus —; The; Table 4 — Recommended Cables; The communication bus shields must be tied together at; Fig. 16 — Outdoor Air Temperature Sensor; OUTSIDE AIR DUCT; Fig. 17 — Outdoor Air Temperature Sensor
  • Page 21 – Economizer —; Fig. 21 — Differential Enthalpy Control Wiring
  • Page 22 – Sensor and Mounting Plate (33AMKITENT006); Fig. 23 — Location of Differential Enthalpy; Fig. 24 — Outside and Return Air Sensor Wiring
  • Page 28 – UHDB; Password Protection —
  • Page 29 – Table 7 — Points Display
  • Page 31 – Controller Identification Screen —; Table 10 — Controller Identification; Holiday Configuration Screen —
  • Page 32 – Table 11 — Holiday Configuration; Occupancy Configuration Screen —; Table 12 — Occupancy Configuration; Set Point Screen —
  • Page 33 – Table 13 — Set Point Configuration; Service Configuration Selection Screen —; DESCRIPTION
  • Page 34 – Table 14 — Service Configuration Selection
  • Page 37 – P r e m i e r L in k TM C o n f ig u r a t io n S c r e e n —; Table 15 — PremierLink Control Configuration
  • Page 39 – Occupancy Maintenance Screen —
  • Page 40 – Table 16 — Occupancy Maintenance; Maintenance Screen —
  • Page 42 – Table 17 — Maintenance
Loading the manual

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.

PC 111

Catalog No. 533-80072

Printed in U.S.A.

Form 38-54SI

Pg 1

11-02

Replaces: 38-52SI

Book 1

4

Tab

3a

2a

Installation, Star t-Up and

Configuration Instructions

Par t Number 33

CSPREMLK

CONTENTS

Page

SAFETY CONSIDERATIONS

. . . . . . . . . . . . . . . . . . . . . . 1

GENERAL

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1,2

INSTALLATION

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-26

Inspection

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2

PremierLink Controller Hardware

. . . . . . . . . . . . . . . . . 2

Field-Supplied Hardware

. . . . . . . . . . . . . . . . . . . . . . . . . 2

• SPACE TEMPERATURE (SPT) SENSOR
• SUPPLY AIR TEMPERATURE (SAT) SENSOR
• INDOOR AIR QUALITY CO

2

SENSOR

• OUTDOOR AIR QUALITY CO

2

SENSOR

• OUTDOOR AIR TEMPERATURE SENSOR
• OUTDOOR AIR ENTHALPY SWITCH
• RETURN AIR ENTHALPY SENSOR

Mount PremierLink Control

. . . . . . . . . . . . . . . . . . . . . . . 2

• LOCATION
• MOUNTING

PremierLink Controller Inputs and Outputs

. . . . . . 3

Control Wiring

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3

Install Sensors

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9

• SPACE TEMPERATURE (SPT) SENSOR

INSTALLATION

• SUPPLY AIR TEMPERATURE (SAT) SENSOR

INSTALLATION

• INDOOR AIR QUALITY CO

2

SENSOR

INSTALLATION

• OUTDOOR AIR QUALITY CO

2

SENSOR

INSTALLATION

• OUTDOOR AIR TEMPERATURE SENSOR

Connect to CCN Communication Bus

. . . . . . . . . . . 18

• COMMUNICATIONS BUS WIRE SPECIFICATIONS

Enthalpy and Differential Enthalpy Control

. . . . . . 18

• ENTHALPY SWITCH/RECEIVER
• OUTDOOR AND RETURN AIR ENTHALPY

SENSOR

Economizer

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21

• Q769B
• Q769C

Economizer with Johnson 4 to 20 mA

Actuator

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24

• DRIVE DIRECTION
• SWITCH SELECTION
• WIRING

START-UP

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26-28

Perform System Check-Out

. . . . . . . . . . . . . . . . . . . . . 26

Initial Operation and Test

. . . . . . . . . . . . . . . . . . . . . . . . 26

Install Navigator™ Display Module

. . . . . . . . . . . . . 26

Password Protection

. . . . . . . . . . . . . . . . . . . . . . . . . . . . 28

Forcing Values and Configuring Items

. . . . . . . . . . 28

Page

CONFIGURATION

. . . . . . . . . . . . . . . . . . . . . . . . . . . . 28-42

Points Display Screen

. . . . . . . . . . . . . . . . . . . . . . . . . . . 28

Thermostat Control Input Screen

. . . . . . . . . . . . . . . . 30

Alarm Service Configuration Screen

. . . . . . . . . . . . 30

Controller Identification Screen

. . . . . . . . . . . . . . . . . 31

Holiday Configuration Screen

. . . . . . . . . . . . . . . . . . . 31

Occupancy Configuration Screen

. . . . . . . . . . . . . . . 32

Set Point Screen

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32

Service Configuration Selection Screen

. . . . . . . . . 33

PremierLink Configuration Screen

. . . . . . . . . . . . . . 37

Occupancy Maintenance Screen

. . . . . . . . . . . . . . . . 39

Maintenance Screen

. . . . . . . . . . . . . . . . . . . . . . . . . . . . 40

SAFETY CONSIDERATIONS

GENERAL

The PremierLink Controller is a field retrofit split system

control compatible with the Carrier Comfort Network (CCN).
This control is designed to allow users the access and ability to
change factory-defined settings thus expanding the function of
the standard unit control board. The complete PremierLink
package (part number 33CSPREMLK) consists of a control
circuit board with plastic cover and label, wire harnesses, spade
connectors, wire nuts and 4 mounting screws.

SAFETY NOTE

Air-handling equipment will provide safe and reliable service
when operated within design specifications. The equipment
should be operated and serviced only by authorized person-
nel who have a thorough knowledge of system operation,
safety devices and emergency procedures.
Good judgement should be used in applying any manufac-
turer’s instructions to avoid injury to personnel or damage to
equipment and property.

Disconnect all power to the unit before performing mainte-
nance or service. Unit may automatically start if power is
not disconnected. Electrical shock and personal injury
could result.

Damage to equipment may result. An individual field-
supplied 24-vac power transformer is required for each
PremierLink controller. The transformer must be less than
100 va to meet UL (Underwriters’ Laboratories) Class 2.

PremierLink™

Retrofit Split System

Controller

"Loading the manual" means you need to wait until the file loads and becomes available for online reading. Some manuals are very large, and the time they take to appear depends on your internet speed.

Summary

Page 3 - The PremierLink controller can be; Fig. 1 — PremierLinkTM Control Module

3 PremierLink Controller Inputs and Outputs — The PremierLink controller inputs and outputs are shown inTable 1. Control Wiring — The PremierLink controller can be connected to either a Carrier-approved thermostat or CCNcompatible temperature sensor. 1. Turn off power to the control box. 2. Strip th...

Page 4 - Fig. 2B — Typical PremierLink Control Wiring — 38AKS013-024 Units

4 RED RED BRN GRN FAN CMP1 CMP2 HS2 HS1 PWR HS3/EXH/RVS RED RED J8 J1 PWR CUT T O ISOLA TE CONTROLLER POWER CUT FOR DUAL TRANSFORMER EQUIPTMENT RELA YS WHT BLU YEL RED ORN PNK PremierLink Connections 40RM Connections 38AK, AKS, ARZ, ARS Terminal Board (TB) W2 R Y1 Y2 W1 G C X WHT WHT IFC C2 C1 CCR 4...

Page 5 - Fig. 2C — Typical PremierLinkTM Control Wiring — 38ARD012 Units; Fig. 2D — Typical PremierLink Control Wiring — 38AKS028-044 Units

5 RED RED BRN GRN FAN CMP1 CMP2 HS2 HS1 PWR HS3/EXH/RVS RED RED J8 J1 PWR CUT T O ISOLA TE CONTROLLER POWER CUT FOR DUAL TRANSFORMER EQUIPTMENT RELA YS WHT BLU YEL RED ORN PNK PremierLink Connections 40RM Connections 38ARD Terminal Board (TB) W2 R Y1 Y2 W1 G C X WHT WHT IFC C2 C1 40RM, 40RMQ, 40RMS ...

Other Carrier Models