Carrier 24APA7 Performance- User Manual

Carrier 24APA7 Performance

Carrier 24APA7 Performance– User Manual, read for free online in PDF format. We hope this helps you resolve any issues you may have. If you have further questions, please contact us through the contact form.

1 Page 1
Page: / 1
Loading the manual

of

Project No.

ADDITION TO ZION'S CAUSE BAPTIST CHURCH

11530

DATE
06/20/11

C

COPYRIGHT , 2011 - MARCUM ENGINEERING, LLC

PHONE - 270.444.9274 FAX - 270.443.1904

S

T

A

TE

OF KENTU

C

K

Y

HVAC SCHEDULES

H-5

?

DIFFUSER AND GRILLE SCHEDULE

PHYSICAL DATA

PERFORMANCE DATA

MARK

MFG.

MODEL

SIZE

(INCHES)

NECK

SIZE

(INCHES)

CORE

TYPE

NOM.

CFM

TYPE OF

MOUNTING

THROW

PRESS.

DROP

(IN. H2O)

SOUND

RATING

(NC)

VOLUME

DAMPER

FT. AT

50 FPM

DIR.

S-1

PRICE

SPD

12 X 12

PLAQUE

125

LAY-IN

9

4-WAY

0.097

<15

NO

S-2

PRICE

SPD

24 X 24

PLAQUE

200

LAY-IN

7

4-WAY

0.042

<15

NO

S-3

PRICE

SPD

24 X 24

PLAQUE

300

LAY-IN

9

4-WAY

0.065

<15

NO

S-4

PRICE

SDB100

48

2-SLOT

185

LAY-IN

21

ADJ.

0.087

19

NO

S-5

PRICE

SDB100

48

4-SLOT

310

LAY-IN

27

ADJ.

0.060

20

NO

S-6

PRICE

520

10 X 6

---

LOUVER

200

SURFACE

20

ADJ.

0.058

<15

YES

S-7

PRICE

520

16 X 8

---

LOUVER

250

SURFACE

23

ADJ.

0.017

<15

NO

R-1

PRICE

80

24 X 24

22 X 22

GRID

1,995

LAY-IN

---

---

0.038

<15

NO

R-2

GREENHECK

AFS-120

42 X 60

40 X 58

LOUVER

1,700

SURFACE

---

---

0.020

<15

NO

R-3

PRICE

REMARKS AND ACCESSORIES:

1

FURNISH DIFFUSERS WITH SQUARE-TO-ROUND NECK TRANSITIONS AS REQUIRED.

2

FURNISH ALL DIFFUSERS AND GRILLES WITH POWDER-COATED FINISH IN COLOR AS SELECTED BY ARCHITECT FROM ALL AVAILABLE

OPTIONS.

3

GRILLE TAGGED R-2 SHALL BE CONTRUCTED OF ALUMINUM SIGHT-PROOF BLADES FILLED WITH FORMED FIBERGLASS INSULATION FOR
SOUND ABSORPTION.

4

COORDINATE LOCATION OF DIFFUSERS TAGGED S-7 AND GRILLES TAGGED R-2 AND R-3 WITH ARCHITECTURAL DRAWINGS.

5

SEE HVAC DETAILS FOR THROW DIRECTIONS FOR DIFFUSERS TAGGED S-4 AND S-5.

PRICE, METAL-AIRE, TITUS, OR APPROVED EQUAL

AIR COOLED CONDENSING UNIT SCHEDULE

MARK

MFG.

MODEL

SIZE REFRIG.

COOLING CAPACITY

VOLTAGE

/ PHASE

MCA

(AMPS)

MOCP

(AMPS)

REMARKS AND

ACCESSORIES

TOTAL

(MBH)

SENSIBLE

(MBH)

SEER

CU-1

CARRIER

24APA7

48

R-410A

51.0

36.4

13.6

27.8

40

SEE BELOW

CU-2

CARRIER

24APA7

24

R-410A

25.6

18.7

16.5

13.6

20

SEE BELOW

CU-3

CARRIER

24APA7

36

R-410A

37.1

26.9

16.5

22.1

35

SEE BELOW

CU-4

CARRIER

24APA7

48

R-410A

51.0

36.4

13.6

27.8

40

SEE BELOW

CU-5

CARRIER

24APA7

24

R-410A

25.6

18.7

16.5

13.6

20

SEE BELOW

CU-6

CARRIER

24APA7

36

R-410A

37.1

26.9

16.5

22.1

35

SEE BELOW

REMARKS AND ACCESSORIES:

1

COMPRESSOR(S) SHALL HAVE AT MINIMUM FOUR (4) YEAR EXTENDED WARRANTY.

2

PROVIDE UNIT WITH FACTORY INSTALLED LOW PRESSURE SWITCH, HIGH PRESSURE SWITCH, CRANKCASE
HEATER, AND FILTER DRIER.

3

CONDENSING UNIT AND MATCHING INDOOR DX COIL SHALL BE FURNISHED BY FURNACE MANUFACTURER.

4

5

6

MAINTAIN MINIMUM MANUFACTURERS RECOMMENDED CLEARANCES.

7

PROVIDE UNIT WITH LOUVERED COIL/HAIL GUARD.

8

PROVIDE UNIT WITH THERMAL OVERLOAD PROTECTION.

9

PROVIDE UNIT WITH TWO (2) STAGE SCROLL COMPRESSOR FOR TWO (2) STAGE COOLING.

10

PROVIDE UNIT WITH SOUND BLANKET AND MOTOR/BLOWER VIBRATION ISOLATION TO MINIMIZE UNIT NOISE.

CARRIER, TRANE, YORK, OR APPROVED EQUAL

FURNACE SCHEDULE

MARK

MFG.

MODEL

TYPE

CONFIGURATION

SIZE

CFM

EXT.

S.P.

DRIVE

MOTOR

H.P.

RPM

NATURAL GAS FIRED FURNACE DATA

COND.

UNIT

ELECTRICAL DATA

REMARKS AND

ACCESSORIES

INPUT

(MBH)

OUTPUT

(MBH)

EFF.

FLUE

SIZE

FLUE TYPE

MCA

(AMPS)

MOCP

(AMPS)

VOLTAGE/

PHASE

F-1

CARRIER

58MEC

UPFLOW

100-20

1,600

0.5

DIRECT

1.0

1,050

100.0

93.0

93%

3"

CONCENTRIC

CU-1

15.9

20

SEE BELOW

F-2

CARRIER

58MEC

HORIZONTAL

060-12

800

0.5

DIRECT

1/2

1,050

60.0

56.0

93%

2"

CONCENTRIC

CU-2

11.0

15

SEE BELOW

F-3

CARRIER

58MEC

HORIZONTAL

080-12

1,200

0.5

DIRECT

1/2

1,050

80.0

75.0

94%

2"

CONCENTRIC

CU-3

11.0

15

SEE BELOW

F-4

CARRIER

58MEC

UPFLOW

100-20

1,600

1.0

DIRECT

1.0

1,050

100.0

93.0

93%

3"

CONCENTRIC

CU-4

15.9

20

SEE BELOW

F-5

CARRIER

58MEC

HORIZONTAL

060-12

800

0.5

DIRECT

1/2

1,050

60.0

56.0

93%

2"

CONCENTRIC

CU-5

11.0

15

SEE BELOW

F-6

CARRIER

58MEC

HORIZONTAL

080-12

1,200

0.5

DIRECT

1/2

1,050

80.0

75.0

94%

2"

CONCENTRIC

CU-6

11.0

15

SEE BELOW

REMARKS AND ACCESSORIES

1

FURNISH UNIT WITH A TWENTY (20) YEAR LIMITED HEAT EXCHANGER WARRANTY AND ONE (1) YEAR PARTS AND LABOR WARRANTY.

2

PROVIDE WITH MATCHING CASED DX COOLING COIL BY FURNACE MANUFACTURER. UNIT SHALL BE SUITABLE FOR TWO (2) STAGE COOLING.

3

PROVIDE UNIT WITH 1" THICK FIBERGLASS FILTERS.

4

MAINTAIN MANUFACTURER'S MINIMUM CLEARANCES.

5

PROVIDE UNIT WITH AT MINIMUM FIVE (5) SPEED ECM MOTOR.

6

PROVIDE UNIT WITH AT MINIMUM TWO (2) STAGE NATURAL GAS HEAT.

7

PROVIDE UNIT WITH MANUFACTURER'S CONENTRIC VENT.

8

PROVIDE UNIT WITH 7-DAY PROGRAMMABLE THERMOSTAT CAPABLE OF CONTROLLING ALL UNIT FUNCTIONS.

CARRIER, TRANE, YORK, OR APPROVED EQUAL

ELECTRIC UNIT HEATER SCHEDULE

MARK

MFG.

SERVICE

MODEL

SIZE

CFM

MOUNTING

HEIGHT

KW

VOLTAGE/

PHASE

MCA

(AMPS)

MOCP

(AMPS)

REMARKS AND

ACCESSORIES

UH-1

QMARK

STORAGE &

EQUIPMENT 108

MUH

05-81

350

7' - 6"

5.0

30.0

35

SEE BELOW

UH-2

QMARK

MECH. ROOM 134

MUH

03-21

350

7' - 6"

2.2

13.8

20

SEE BELOW

REMARKS AND ACCESSORIES:

1

MOUNTING HEIGHT IS FROM FINISHED FLOOR TO BOTTOM OF UNIT.

2

PROVIDE UNIT WITH THERMAL OVERLOAD PROTECTION.

3

PROVIDE WITH NON-FUSED ELECTRICAL DISCONNECT SWITCH WITH SINGLE POINT ELECTRICAL CONNECTION.

4

PROVIDE UNIT WITH AUTOMATIC RESET CONTROL.

5

PROVIDE UNIT WITH ADJUSTABLE DISCHARGE LOUVERS.

6

MAINTAIN MANUFACTURER'S MINIMUM RECOMMENDED CLEARANCES.

7

PROVIDE WITH UNIT MOUNTED THERMOSTAT.

MARKEL, QMARK, REZNOR, OR APPROVED EQUAL

LOUVER SCHEDULE

MARK

MFG.

DESCRIPTION

MODEL/TYPE

SIZE

(INCHES)

CFM

FREE AREA

(SQ. FT.)

FACE VELOCITY

(FPM)

PRESSURE

DROP

(IN. H2O)

TYPE OF

FRAME AND

MOUNTING

MOUNTING

HEIGHT

SERVICE

REMARKS AND

ACCESSORIES

L-1

GREENHECK

COMBINATION

LOUVER/DAMPER

EAC-601

32 X 16 X 6

155

0.75

207

0.01

CHANNEL

16' - 4"

VENT. AIR INTAKE

SEE BELOW

L-2

GREENHECK

COMBINATION

LOUVER/DAMPER

EAC-601

32 X 16 X 6

460

0.75

614

0.05

CHANNEL

16' - 4"

VENT. AIR INTAKE

SEE BELOW

L-3

GREENHECK

COMBINATION

LOUVER/DAMPER

EAC-601

16 X 16 X 6

230

0.34

678

0.06

CHANNEL

8' - 0"

VENT. AIR INTAKE

SEE BELOW

REMARKS AND ACCESSORIES:

1

MOUNTING HEIGHT MEASURED FROM BOTTOM OF LOUVER TO TOP OF FINISHED FLOOR. REFER TO ARCHITECTURAL PLANS FOR FINISHED MOUNTING HEIGHT AND LOCATION.

2

SIZES ARE SPECIFIED AS: FIRST FIGURE-WIDTH, SECOND FIGURE-HEIGHT, AND THIRD FIGURE- DEPTH.

3

PROVIDE UNIT WITH EXTENDED SILL.

4

PROVIDE UNIT IN ALUMINUM CONSTRUCTION.

5

PROVIDE UNIT WITH ALUMINUM BIRD SCREEN.

6

PROVIDE UNIT WITH 70% KYNAR FINISH. COLOR TO BE SELECTED BY ARCHITECT.

7

INSTALL UNIT IN 18 GAUGE SHEETMETAL WALL SLEEVE.

8

GREENHECK, NCA, RUSKIN, OR APPROVED EQUAL

VENTILATING FAN SCHEDULE

PHYSICAL DATA

PERFORMANCE DATA

UNIT OPERATION CONTROL

ELECTRICAL DATA

REMARKS AND

ACCESSORIES

MARK

MFG.

AREA SERVED

MODEL/

TYPE

SIZE

APPROX.

UNIT

WEIGHT

(LBS.)

MOUNTING

RATED

CFM

ESP

(IN. H2O)

DRIVE

FRPM

MOTOR

TYPE

MOTOR

RPM

dBA

SWITCH

OCC.

T-STAT

WATTS

HP

ELECT.

CHAR.

EF-1

GREENHECK

MENS TOILET 133

SP

A410

50

CEILING

300

0.15

DIRECT

826

ODP

1,000

36

X

121

---

1-6

EF-2

GREENHECK

JANITOR 131

SP

A70

20

CEILING

40

0.15

DIRECT

697

ODP

850

29

X

20

---

1-6

EF-3

GREENHECK

WOMENS TOILET 113

SP

A410

50

CEILING

300

0.15

DIRECT

826

ODP

1,000

36

X

121

---

1-6

EF-4

GREENHECK

TOILET 117

SP

A90

20

CEILING

50

0.15

DIRECT

709

ODP

900

27

X

29

---

1-6

EF-5

GREENHECK

TOILET 124

SP

A90

20

CEILING

50

0.15

DIRECT

709

ODP

900

27

X

29

---

1-6

EF-6

GREENHECK

TOILET 127

SP

A90

20

CEILING

50

0.15

DIRECT

709

ODP

900

27

X

29

---

1-6

EF-7

GREENHECK

STORAGE & EQUIPMENT 108

AP

A200

35

CEILING

200

0.15

DIRECT

850

ODP

900

39

X

48

---

1-6

EF-8

GREENHECK

TOILET 208

SP

A90

20

CEILING

50

0.15

DIRECT

709

ODP

900

27

X

29

---

1-6

EF-9

GREENHECK

ALTERNATE TOILET

SP

A110

25

CEILING

75

0.15

DIRECT

834

ODP

950

30

X

49

---

1-7

EF-10

GREENHECK

ALTERNATE TOILET

SP

A110

25

CEILING

75

0.15

DIRECT

834

ODP

950

30

X

49

---

1-7

REMARKS AND ACCESSORIES:

1

PROVIDE UNIT WITH ALUMINUM INTAKE GRILLE WITH WHITE ENAMEL FINISH.

2

PROVIDE UNIT WITH ROUND DUCT CONNECTOR.

3

PROVIDE UNIT WITH CAST ALUMINUM BRICK VENT TERMINATION WITH 70% MINIMUM KYNAR FINISH AND INTEGRAL BACKDRAFT DAMPER (GREENHECK MODEL BVC OR EQUAL). COLOR TO BE SELECTED BY ARCHITECT.

4

PROVIDE UNIT WITH SOLID-STATE FAN SPEED CONTROL.

5

PROVIDE UNIT WITH VIBRATION ISOLATION KIT.

6

PROVIDE UNIT WITH THERMAL OVERLOAD PROTECTION.

7

THIS UNIT SHALL BE FURNISHED AS AN ALTERNATE. REFERENCE ARCHITECTURAL DRAWINGS FOR APPROPRIATE ALTERNATE NUMBER.

UNIT OPERATION CONTROL:

SWITCH - UNIT SHALL BE CONTROLLED BY INDEPENDENT PILOT LIT SWITCH.

OCC. - UNIT SHALL BE ELECTRICALLY INTERLOCKED WITH AND CONTROLLED BY ZONE LIGHT CONTROL.

T-STAT - NOT USED.

COOK, GREENHECK, PENNBARRY, OR APPROVED EQUAL

PACKAGED AIR CONDITIONING UNIT WITH NATURAL GAS HEAT SCHEDULE

UNIT PHYSICAL DATA

COOLING PERFORMANCE

NATURAL GAS HEAT PERFORMANCE

ELECTRICAL DATA

REMARKS AND

ACCESSORIES

MARK

MFG.

MODEL

SIZE

CONFIG.

REFRIG.

APPROX.

UNIT

WEIGHT

(LBS.)

OUTSIDE

AIR

(CFM)

SUPPLY FAN DATA

COOLING CAP.

(S)EER @

AHRI COND.

INPUT

(MBH)

OUTPUT

(MBH)

AFUE

EFFICIENCY

(%)

TEMP.

RISE

VOLTAGE /

PHASE

MCA

(AMPS)

MOCP

(AMPS)

CFM

ESP

(IN. H20)

MOTOR

POWER

(BHP)

MOTOR

RPM

TOTAL

(MBH)

SENSIBLE

(MBH)

AC-1

CARRIER

48TCE

09

HORIZONTAL

R-410A

1,000

335

3,400

0.8

1.2

750

100.4

72.0

11.0

180.0

147.6

82%

46

40.0

50

1-24

AC-2

CARRIER

48TCE

09

HORIZONTAL

R-410A

1,000

335

3,400

0.8

1.2

750

100.4

72.0

11.0

180.0

147.6

82%

46

40.0

50

1-24

AC-3

CARRIER

48TCE

04

HORIZONTAL

R-410A

500

250

1,200

0.6

0.5

855

35.7

26.3

13.0

115.0

93.0

81%

72

19.4

25

1-21

AC-4

CARRIER

48TCE

05

HORIZONTAL

R-410A

600

230

1,600

0.8

0.7

973

46.8

32.8

13.0

115.0

93.0

81%

59

23.5

30

1-21

AC-5

CARRIER

48ES

024

HORIZONTAL

R-410A

300

95

800

0.5

0.3

1,050

23.0

17.0

13.2

40.0

32.0

80%

50

19.7

30

1-16, 25

REMARKS AND ACCESSORIES:

1

TEMPERATURE.

2

PROVIDE UNIT WITH THERMOSTATIC EXPANSION VALVES (TXV) ON ALL DX COILS.

3

PROVIDE UNIT WITH AT MINIMUM TWO (2) STAGE HEATING.

4

PROVIDE UNIT WITH STAINLESS STEEL HEAT EXCHANGER.

5

PROVIDE UNIT WITH HINGED, GASKETED CABINET ACCESS DOORS.

6

PROVIDE UNIT WITH AT MINIMUM 1" THICK, DOUBLE-WALL INSULATED HOUSING.

7

PROVIDE UNIT WITH 2" THICK, 30% EFFICIENT PLEATED FILTERS.

8

PROVIDE UNIT WITH MOTOR/BLOWER VIBRATION ISOLATION.

9

PROVIDE UNIT WITH HAIL-GUARD ON CONDENSING COIL.

10 PROVIDE UNIT WITH UNIT-MOUNTED, NON-FUSED WEATHERPROOF DISCONNECT SWITCH WITH SINGLE-POINT ELECTRICAL CONNECTION.

11 PROVIDE UNIT WITH THERMAL OVERLOAD PROTECTION.

12 PROVIDE UNIT WITH ONE (1) YEAR PARTS AND LABOR WARRANTY, FIVE (5) YEAR COMPRESSOR WARRANTY, AND TEN (10) YEAR HEAT EXCHANGER WARRANTY.

13 THE CONTRACTOR SHALL FURNISH AND INSTALL AN ADDITIONAL SHEAVE, IF NECESSARY, TO BRING AIR SYSTEM TO WITHIN 10% OF DESIGN.

14 MAINTAIN MANUFACTURER'S RECOMMENDED MINIMUM CLEARANCES.

15 PROVIDE UNIT WITH MANUFACTURER'S START-UP AND CERTIFIED REPORT. INSTALLING CONTRACTOR START-UP IS NOT ACCEPTABLE.

16 PROVIDE UNIT WITH 7-DAY PROGRAMMABLE THERMOSTAT CAPABLE OF CONTROLLING ALL UNIT FUNCTIONS.

17 PROVIDE UNIT WITH ELECTRICAL PHASE LOSS PROTECTION.

18 PROVIDE UNIT WITH MODULATING HOT GAS REHEAT FOR HUMIDITY CONTROL.

19 PROVIDE UNIT WITH RETURN AIR HUMIDITY SENSOR FOR CONTROL OF DEHUMIDIFICATION CYCLE.

20 PROVIDE UNIT WITH MODULATING OUTSIDE AIR DAMPER FOR CO2 DEMAND VENTILATION CONTROL.

21 PROVIDE UNIT WITH RETURN AIR MOUNTED CO2 SENSOR FOR DEMAND VENTILATION CONTROL.

22 PROVIDE UNIT WITH SMOKE DETECTOR MOUNTED IN THE RETURN-AIR STREAM TO SHUT DOWN UNIT OPERATION AND INITIATE AN ALARM CONDTION AT THE PRESENCE OF SMOKE.

23 PROVIDE UNIT WITH TWO (2) INDEPENDENT REFRIGERANT CIRCUITS FOR TWO (2) STAGE COOLING.

24 PROVIDE UNIT WITH FULLY-MODULATING ECONOMIZER WITH COMPARATIVE ENTHALPY CONTROL FOR AIRSIDE ECONOMIZER OPERATION.

25 PROVIDE UNIT WITH MANUAL OUTSIDE AIR DAMPER.

CARRIER, TRANE, YORK, OR APPROVED EQUAL

"Loading the manual" means you need to wait until the file loads and becomes available for online reading. Some manuals are very large, and the time they take to appear depends on your internet speed.