Installation, Start-Up and
Service Instructions
Part No. 09DK900004, 09DK900006
SAFETY CONSIDERATIONS
When installing this accessory, observe precautions in the
literature and on any labels attached to the equipment, and
all other safety precautions that may apply.
• Follow all safety codes.
• Wear safety glasses and work gloves.
• Use care in handling and installing this accessory.
ELECTRIC SHOCK HAZARD
Separate power sources (main and control
circuit power) are used for these units. Be
sure both main power and control circuit
power are disconnected before installing the
Motormaster III Relay/Sensor Kit.
GENERAL
These instructions are for field installation of the acces-
sory Motormaster III Relay/Sensor kit. The kit is used to pro-
vide efficient control of the primary fans (fans 1 and 2) on
09DK condensers with 67/33%, 33/33/33%, and 33/33/17/
17% typical capacity split applications. On 67/33% appli-
cations, fan no. 2 is shared by the 67% and 33% refrigerant
circuits. With 33/33/33% and 33/33/17/17% applications, fan
no. 1 and 2 are shared by either the 33% or 17% refrigerant
circuits. This accessory ensures that the first circuits on and
the last circuits off control the Motormaster III device. One
kit is required for 67/33% applications. Two kits are re-
quired for 33/33/33% and 33/33/17/17% applications. See
Table 1 for voltage and kit number information.
Table 1 — Motormaster III Relay/Sensor
Kit Information
MAIN SUPPLY
VOLTAGE
MOTORMASTER III
RELAY/SENSOR PART NO.
208/230-3-60
09DK900004
460-3-60
575-3-60
380-3-60
09DK900006
380/415-3-50
INSTALLATION
Use these instructions in conjunction with the accessory
Motormaster III control installation instructions.
The accessory fan control kit must be used for efficient
unit operation with 67/33%, 33/33/33%, and 33/33/17/17%
capacity split applications. Refer to the fan control kit in-
stallation instructions for more information. Install the fan
control kit
before
installing the Motormaster III Relay/
Sensor kit.
Step 1 — Examine Package Contents —
Check
kit for shipping damage or missing parts. If damage is found,
file a claim with the shipping agency immediately. Each kit
includes a relay, a sensor, and the fastener hardware for in-
stallation. See Table 2 for kit contents. If any item is miss-
ing, notify your Carrier representative.
Table 2 — Motormaster III Relay/Sensor
Kit Contents
QUANTITY
ITEM
1
Relay
1
Sensor*
2
Pan Head Screw, Type B
(no. 6-20 x
3
⁄
4
in. long)
*Each Motormaster III accessory controller also comes with one
sensor.
Step 2 — Mount Relay in Control Box
1. Open control box door.
2. Remove and save 4 corner holddown screws and detach
control box cover.
3. Mount relay on the fan control kit control panel in the
control box using the screws provided. See Fig. 1 and 2
for specific locations. Each kit contains one relay. Two
kits are required for 33/33/33% and 33/33/17/17%
applications.
NOTE: For 67/33% applications, the relay (CR2A) is mounted
on the right side of the control panel. Relay CR1A is not
needed for 67/33% applications. See Fig. 1 and 2.
09DK054-084
Accessory Motormaster
T
III
Relay/Sensor Kit
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 2
Tab
4a
PC 111
Catalog No. 530-957
Printed in U.S.A.
Form 09DK-8SI
Pg 1
5-93
Replaces: New
"Loading the manual" means you need to wait until the file loads and becomes available for online reading. Some manuals are very large, and the time they take to appear depends on your internet speed.
Other Manuals for Carrier 09DK054-084
Summary
LEGEND AND NOTES FOR FIG. 1 ATS — Air Temperature Switch CR — Control Relay DU — Dummy Terminal EQUIP — EquipmentFC — Fan Contactor FCPS — Fan Cycling Pressure Switch FIOP — Factory-Installed Option FM — Fan Motor GND — Ground MMSN — Motormaster T Sensor PL — Plug Assembly PRI — Primary SEC — Second...
Fig. 1 — Wiring Diagram and Component Arrangement; 054 and 064 Units 4
LEGEND AND NOTES FOR FIG. 2 ATS — Air Temperature Switch CR — Control Relay DU — Dummy Terminal EQUIP — EquipmentFC — Fan Contactor FCPS — Fan Cycling Pressure Switch FIOP — Factory-Installed Option FM — Fan Motor GND — Ground MMSN — Motormaster T Sensor PL — Plug Assembly PRI — Primary SEC — Second...