Page 2 - NOTICE
1 Estimate of Peak Domestic Hot Water Usage Average Gallons of Times Used During Gallons Used in Use Hot Water per Usage One Hour One Hour Shower 20 x _____________ = _____________ Bath 20 x _____________ = _____________ Shaving 2 x _____________ = _____________ Hands and Face Washing 4 x __________...
Page 3 - Table 1: Peerless Partner Ratings; Domestic water priority.
1. First hour rating based on heating water from 50°F to 140°/115°F with 180°F boiler water temperature. Gas- and oil-fired and electric water heater first hour ratings based on DOE test procedure using 90°F temperature rise (55°F to 145°F). 2. Net I=B=R Output, Water3. Useable hot water based on re...
Page 4 - Pre-Installation Considerations; Table 2: First Hour Ratings for Reduced Boiler Output
Pre-Installation Considerations 3 PP-40 16 14 12 10 9 8 7 6 5.5 5 4.2 3.7 PP-60 ** ** 30 24 20 17 10.3 9.5 8.2 7.8 7.1 6.1 PP-80 ** ** ** ** ** ** 14 13 12 11.1 10.5 8.5 PP-120 ** ** ** ** ** ** 20 18 16 15 14 12.5 Model No. 2.0 2.5 3.0 3.5 4.0 4.5 5.0 5.5 6.0 6.5 7.0 7.5 Domestic Water Flow Rate [g...
Page 5 - Piping; Table 4: Flow Specifications
4 4. Peerless Partner(s) may be located adjacent to boiler to reduce piping heat loss or central to points of use to reduce response time to fixtures. a. Install indoors in an area not exposed to freezing temperatures. Do not install outdoors. b. Position with adequate clearance for service and main...
Page 6 - Domestic Water; Standard Domestic Hot Water Out.; Domestic Hot Water Out with Mixing Valve.; Multiple Water Heaters; Peerless Partner with unfired storage tank.
Figure 3: Hot Water Outlet 2. Domestic Water a. Cold Water In. Install brass tee and drain valve (not provided). Install shutoff valve betweenwater supply and cold water inlet for ease ofservice. See Figure 1. For systems using a back flow preventer or noreturn valve, install a thermal expansion tan...
Page 7 - Electrical
6 Figure 5: Installation of Multiple Water Heaters as Single Unit Figure 6: Unfired Storage Tank 1. The Peerless Partner must be electrically grounded in accordance with local codes. In the absence of local codes follow the National Electrical Code, ANSI/NFPA 70. 2. Install thermostat provided with ...
Page 9 - Maintenance; No Hot Water; Troubleshooting
8 1. General Housekeeping (continuous). Keep area clear of gasoline or other flammable vapors or liquids. Controls on this appliance could ignite vapors causing an explosion. 2. Clean Inside of Tank (monthly). a. Mark temperature setting on Peerless Partner thermostat. Set thermostat to lowest setti...
Page 11 - Dimensions; Table 7: Dimensions and Specifications
10 Thermostat: Honeywell L4080B1295 (Operating range = 120°F to 160°F, 15° fixed differential) Temperature and Pressure Relief Valve: PP-40: Watts 100XL-8 (100 Mbh, 8” element) PP-60/80/120: Watts 40XL-8 (200 Mbh, 8” element) Dimensions Repair Parts Table 7: Dimensions and Specifications Figure 9: C...
Page 12 - Partner; Water Heater; Peerless; I n s t a l l a t i o n ,
Partner ® Water Heater Peerless ® Indirect-Fired I n s t a l l a t i o n , O p e r a t i o n & M a i n t e n a n c e M a n u a l T O T H E I N S TA L L E R : T h i s m a n u a l i s t h e p r o p e r t y o f t h e o w n e r a n d m u s t b e a f f i x e d n e a r t h e w a t e r h e a t e r f o ...