Page 2 - Please read this page first!; Hazard definitions; Note to the installer
Part Number 550-110-032/0607 EG-30 thru 75 Series 4 and PEG-30 thru 65 Series 4 EG-30 thru 75 Series 4 and PEG-30 thru 65 Series 4 Please read this page first! Hazard definitions The following defined terms are used throughout these instructions to bring attention to the presence of hazards of vario...
Page 3 - Standing Pilot Boilers — Control Supplement; Table of contents
Part Number 550-110-032/0607 Standing Pilot Boilers — Control Supplement Table of contents Hazard definitions and Note to the installer .................................................................................... 2 Control installation — EG-30 thru -75 water boilers without tankless heaters ...
Page 5 - EG-75 water boilers without tankless heaters; EG-30 thru -65 water boilers without tankless heaters; Control installation
Part Number 550-110-032/0607 Standing Pilot Boilers — Control Supplement Figure 2 EG-75 water boilers without tankless heaters Figure 1 1. Mount and wire controls per wiring diagram, page , and Figure 1. a. Attach junction box inside left jacket panel with #8- x ½” machine screws provided. b. Instal...
Page 7 - EG-30 thru -65 water boilers with tankless heaters; continued
Part Number 550-110-032/0607 Standing Pilot Boilers — Control Supplement Note: Tankless heater not available on EG-75 standing pilot boilers. EG-30 thru -65 water boilers with tankless heaters Control installation continued 1. Mount and wire controls per wiring diagram, page , and Figure . a. Instal...
Page 9 - EG-75 steam boilers with probe-type low water cutoff
Part Number 550-110-032/0607 Standing Pilot Boilers — Control Supplement 1. Mount and wire controls per wiring diagram, page 8, and Figure . a. Attach junction box inside left jacket panel with #8- x ½” machine screws and green ground nuts provided. b. Install transformer with plug-in relay receptac...
Page 11 - EG-75 steam boilers with float-type low water cutoff
11 Part Number 550-110-032/0607 Standing Pilot Boilers — Control Supplement 1. Mount and wire controls per wiring diagram, page 10, and Figure . a. Attach junction box inside left jacket panel with #8- x ½” machine screws and green ground nuts provided. b. Install transformer with plug-in relay rece...
Page 12 - The following boiler models must have damper; Damper installation
1 Part Number 550-110-032/0607 EG-30 thru 75 Series 4 and PEG-30 thru 65 Series 4 Figure 8 Vent damper assemblies The following boiler models must have damper installed: • EG-30 thru EG-65, natural or propane gas. • PEG-30 thru PEG-65, steam, natural gas. The following boiler models may have damper ...
Page 13 - Minimum clearances to
1 Part Number 550-110-032/0607 Standing Pilot Boilers — Control Supplement Damper installation continued . Read and apply the harness plug warning label (shown above) so that it is visible after installa- tion. . Plug damper harness receptacle into damper harness plug. Bypassing (jumpering) vent dam...
Page 14 - Checkout procedure; Room thermostat anticipator settings
1 Part Number 550-110-032/0607 EG-30 thru 75 Series 4 and PEG-30 thru 65 Series 4 Checkout procedure Room thermostat anticipator settings Water without tankless heater — 0.40 amps Water with tankless heater — 0.20 amps Steam — Select based on gas valve and damper. See table below. 1. See pages 1-18 ...
Page 15 - Lighting instructions — Robertshaw 7200
1 Part Number 550-110-032/0607 Standing Pilot Boilers — Control Supplement Lighting instructions — Robertshaw 7200
Page 16 - Natural gas boilers only
1 Part Number 550-110-032/0607 EG-30 thru 75 Series 4 and PEG-30 thru 65 Series 4 Lighting instructions — Honeywell VR8200/VR8300 Natural gas boilers only
Page 17 - Propane boilers only
1 Part Number 550-110-032/0607 Standing Pilot Boilers — Control Supplement Lighting instructions — Honeywell VR8200/VR8300 Propane boilers only
Page 18 - Lighting instructions — Robertshaw 7000ERHC
18 Part Number 550-110-032/0607 EG-30 thru 75 Series 4 and PEG-30 thru 65 Series 4 Lighting instructions — Robertshaw 7000ERHC
Page 19 - In event of vent damper failure:; Before troubleshooting; Troubleshooting
1 Part Number 550-110-032/0607 Standing Pilot Boilers — Control Supplement Figure 9 Manually opening vent damper In event of vent damper failure: Effikal vent damper If troubleshooting chart recommends replacing actuator and actuator is not immediately available, damper blade can be fixed in an open...
Page 24 - Replacement parts
Part Number 550-110-032/0607 EG-30 thru 75 Series 4 and PEG-30 thru 65 Series 4 Only dampers listed below are approved for use on EG-0 thru Series , and PEG-0 thru Series , standing pilot ignition system boilers. Any other damper installed can cause severe personal injury or death. Replacement parts...