Page 2 - TABLE OF CONTENTS
ii TABLE OF CONTENTS Product Overview .................................................................... 1 Module Setup .......................................................................... 2 Jumper Settings ...................................................................... 3 Software Dri...
Page 3 - Product Overview; LM104-P50 Network Interface Options
1 Product Overview The Vista Electronics LM104-P50 module provides connectivity between PC/104-based systems and the Echelon Local Operating Network (LON). The module features full compliance with Echelon’s LonMark Interoperability Guidelines, greatly simplifying hardware and software integration in...
Page 4 - Module Setup
2 Module Setup IMPORTANT NOTE! The LM104-P50 module gets all of its electrical power through the PC/104 bus connector. The module requires +5Vdc, ±10% at 420mA. Because it was designed specifically for the PC/104 bus, the module does not support any external power supply, nor is it designed to run a...
Page 5 - Jumper Settings; JP1 SERVICE; –RESET; JP3 TERMINATION
3 Jumper Settings There are five jumper locations, which vary slightly depending on which network interface option is selected. Their functions are as follows: JP1 SERVICE Momentarily shorting this jumper causes the Neuron chip to broadcast its Neuron ID across the network. This jumper should normal...
Page 7 - Software Driver Installation; nn
5 Software Driver Installation The LM104-P50 module includes two MS-DOS software drivers: one that is interrupt driven ( LM104INT.SYS ) and one that uses polling ( LM104POL.SYS ). The interrupt driver is used in most cases. First, copy the files on the distribution diskette to a drive and directory ...
Page 8 - LON
6 For example, adding the following line to the CONFIG.SYS file: DEVICE=C:\LON\LM104INT.SYS /D1 /P1 /Q5 installs the interrupt-driven driver using base I/O address &h1E0 and IRQ5. Adding the following line to the CONFIG.SYS file: DEVICE=C:\LON\LM104POL.SYS /D1 /P3 installs the polling driver at ...
Page 9 - Cable Grounding and Termination; Cable Grounding; Cable Wiring and Termination
7 Cable Grounding and Termination To maintain data transmission performance, network cabling must be terminated correctly. Termination requirements vary depending on the type of cable used for network connections – shielded or unshielded twisted pair - and the type of transceiver used. Cable Groundi...
Page 10 - Options 2 and 3 – Twisted pair transceivers
8 The RS-485 standard further specifies that network cabling have a characteristic impedance of approximately 120 W . The use of coaxial or twinaxial cable is not recommended. VISTA Electronics recommends using a high quality, low loss polyethylene-insulated twisted pair wire (such as Belden 9841) f...
Page 12 - Troubleshooting; NODEUTIL; EEBLANK
10 Troubleshooting • Make sure that the system has power, and make sure that all voltages are within specification. The Neuron chip does not tolerate under- or over-voltage conditions very gracefully. • Make sure that the driver’s command-line switches ( /P# and /Q# ) match the jumper settings on th...
Page 13 - Specifications; Mechanical; Environmental
11 Appendix A Specifications Mechanical Compatible with PC/104 Specification v2.3 Dimensions: 3.55 x 3.80 x 0.95 inches (90.1 x 96.5 x 24.1 mm) (Including PC/104 connectors) Weight 2.8 oz. (79.5 g) User Connectors Network Connection: Options 1/2/3/6 3-pin, 0.100” spacing right angle friction locking...
Page 14 - Appendix B; Bus Signal Assignments
12 Appendix B Bus Signal Assignments PIN Number J1/P1 Row A J1/P1 Row B J2/P2 Row C J2/P2 Row D 0 -- -- 0V 0V 1 -IOCHCHK 0V -SBHE -MEMCS16 2 SD7 RESET LA23 -IOCS16 3 SD6 +5V LA22 IRQ10 4 SD5 IRQ9 LA21 IRQ11 5 SD4 -5V LA20 IRQ12 6 SD3 DRQ2 LA19 IRQ15 7 SD2 -12V LA18 IRQ14 8 SD1 -ENDXFR LA17 -DACK0 9 ...
Page 15 - Appendix C
13 Appendix C Connector and Jumper Locations and Pinouts, LM104-P50 Module Options 1/2/3/6 LM104−P50− 1 JP 3 T ER M . JP 4 JP 5 1 2 2 3 3 4 4 5 6 SE R V IC E R E SE T JP 2 JP 1 I/O AddressRange Select Interrupt Request(IRQ) Select Termination NetworkConnection 2 NET3 NET 1 NO CONNECTION Service LED ...
Page 16 - Appendix D
14 Appendix D Connector and Jumper Locations and Pinouts, LM104-P50 Module Options 5/5C LM104−P50− 1 JP 4 JP 5 1 2 2 3 3 4 4 5 6 SE R VI C E RE SE T JP 2 JP 1 I/O AddressRange Select Interrupt Request(IRQ) Select Transmit Output Level NetworkConnection Packet Detect (Amber) CENELEC Band In Use(Red) ...
Page 17 - Manufacturers of Echelon-approved networking cable and wire.; ConnectAir International
15 Appendix E Manufacturers of Echelon-approved networking cable and wire. General Cable (BICC Cable, Brand-Rex, General Cable, Carol Cable) 4 Tesseneer Drive Highland Heights, KY 41076 Tel: +1-859-572-8000 Fax: +1-859-582-8458 Email: [email protected] Web: http://www.generalcable.com ConnectAir...
Page 18 - Appendix F; Concerning Conformal Coatings
16 Appendix F Concerning Conformal Coatings LM104−P50− 1 J P3 T ER M . JP 4 JP 5 1 2 2 3 3 4 4 5 6 SE R VI C E RE S E T JP 2 JP 1 P3 R11 Certain applications require a conformal coating be applied to the board for additional environmental protection. There are several “keep-out” areas on the LM104-P...
Page 19 - Appendix G; Additional Information; Echelon literature
17 Appendix G Additional Information PC/104 Specification, Version 2.3 This document is available from the PC/104 Consortium, which can be reached through their website at http://www.pc104.org . The specification can be downloaded at http://www.pc104.org/technology/pc104_tech.html . Echelon literatu...
Page 20 - Appendix H; Limited Warranty; Standard Warranty Service
18 Appendix H Limited Warranty VISTA Electronics, Inc., warrants its hardware products to be free from defects in workmanship and materials, under normal use and service, for the period of three (3) years from the date of purchase from VISTA. VISTA makes no warranty that its software products will w...