Page 2 - Refrigeration Piping and Charging

- 1 - 2. Evaporator Unit • The WM25-45SFCR evaporator units shall be installed for rack mount with the air supply from the left front, top or side and air return on the right front, top or side. • Supply and return air flow from the evaporator unit shall be unobstructed for at least 1 foot. • There ...

Page 3 - Pressure, Superheat and Subcooling Readings; Complaint Possible

- 2 - 5. Pressure, Superheat and Subcooling Readings NOTES: THE VALVES MUST BE IN THE MIDDLE POSITIONS TO READ PROPERLY. Complaint Possible Causes a. High suction pressure and low head pressure b. High suction pressure and low head pressure Low superheat and low subcooling c. High suction pressure a...

Page 4 - Back Position; : Process and manometer port closed for normal operation; Front Position; : Main connection to liquid or suction line closed; Middle Position; : All ports open for vacuum, charge and measurement; Electrical Wiring

- 3 - Back Position : Process and manometer port closed for normal operation Front Position : Main connection to liquid or suction line closed Middle Position : All ports open for vacuum, charge and measurement 7. Electrical Wiring Fig. 2.2 VINO2500-4500SSR Electrical Wiring Diagram (VTSTAT) Fig. 2....