Page 2 - UPS Location Warnings; dust or direct sunlight.; causing product damage not covered under warranty.; UPS Connection Warnings; UPS into itself this will damage the UPS.; Equipment Connection Warnings; battery for your UPS.; SAVE THESE INSTRUCTIONS; warnings will void your warranty.; Important Safety Instructions
UPS Location Warnings • Install your UPS indoors, away from excess moisture or heat, conductive contaminants, dust or direct sunlight. • For best performance, keep the indoor temperature between 32º F and 104º F (0º C and 40º C). • Leave adequate space around all sides of the UPS for proper ventilat...
Page 3 - Installation
Mount your equipment in either a 4-post or 2-post rack or rack enclosure (see next page for 2-post mounting). The user must determine the fitness of hardware and procedures before mounting. If hardware and procedures are not suitable for your application, contact the manufacturer of your rack or rac...
Page 4 - All UPS systems are extremely heavy. Use
4 Installation (continued) 2-Post (Telecom) Mounting If you mount 2U UPS models in 2-post racks, they require the addition of a Tripp Lite 2-Post Rackmount Installation Kit (model: 2POSTKITRMWM, sold separately). See Installation Kit owner’s manual for installation procedure for 2U UPS models. Mount...
Page 5 - Plug your equipment into your UPS.
5 Important Safety Instructions Connection and Start-Up Plug your UPS’s line cord into an electrical outlet. Your UPS must be connected to a dedicated circuit of sufficient amperage. Note, however, that the select models may be fitted with different plug types. Refer to the “OP Rating/ Plug Rating” ...
Page 6 - USB and RS-232 Serial; The EPO port is not a phone line surge; External Battery Connection
6 Optional Connections (continued) USB and RS-232 Serial Communications (all models) Use the included USB cable (see 2a ) and/or DB9 serial cable (see 2b ) to connect the communication port of your computer to the communication port of your UPS. Install on your computer the Tripp Lite PowerAlert Sof...
Page 7 - UPS Power ON; Basic Operation
7 Front Panel Switches “ON/TEST” Button: This switch controls four separate UPS functions: UPS Power ON To turn the UPS on, press this button, hold it for several seconds until you hear a beep, then release it. The “ON LINE” LED will illuminate. UPS Self-Test During normal on-line operation, press t...
Page 8 - “LOAD ACTIVE METER” LED:
8 Front Panel Indicator Lights continued “BYPASS” LED: This yellow light will flash to indicate that the UPS’s DC/AC inverter is deactivated and the UPS is in the “Bypass” mode. During normal operation this LED will light briefly when the unit is plugged in, but if an internal fault or overload occu...
Page 9 - “REPLACE BATT” LED:; on; External Battery Pack Connector (configuration varies by model):
9 Rear Panel “REPLACE BATT” LED: This red light will illuminate constantly and the UPS alarm will beep every 2 seconds if your UPS’s microprocessor detects a battery fault or if your UPS fails the automatic self-test (after you turn your UPS ON) and the UPS battery is less than fully charged. Let th...
Page 10 - Telephone or Telephone/Network Protection Jacks:
Rear Panel continued Input Cord: This permanently attached power cord connects your UPS to a power outlet. AC Receptacles (Varied by Model): These 15-, 20- and 30-amp receptacles provide your connected equipment with pure sine-wave AC output from the AC line during normal operation and from battery ...
Page 11 - having operational difficulties.; Troubleshooting
11 The UPS’s control panel lights will turn on in the sequences below to signal that the UPS is having operational difficulties. Lights (On/Flashing) and Condition Solution On: REPLACE BATT Let the UPS system charge for at least Condition: Replace Battery 12 hours and perform a self test using the &...
Page 13 - Battery Replacement; Battery Replacement Door:; Under normal conditions, the original battery in your UPS will; Procedure; Remove Front
13 Battery Replacement Battery Replacement Door: Under normal conditions, the original battery in your UPS will last several years. Battery replacement should be performed only by qualified service personnel. Refer to “Battery Warnings” in the Safety section. Should your UPS require battery replacem...
Page 14 - Storage and Service; they may suffer permanent loss of capacity.; Warranty Registration
Visit www.tripplite.com/warranty today to register the warranty for your new Tripp Lite product. You'll be automatically entered into a drawing for a chance to win a FREE Tripp Lite product!* * No purchase necessary. Void where prohibited. Some restrictions apply. See website for details. Regulatory...