– 2 – ADOPTION OF NEW REFRIGERANT This Air Conditioner is a new type which adopts a new refrigerant HFC (R410A) instead of the conventionalrefrigerant R22 in order to prevent destruction of the ozone layer. WARNING Cleaning of the air filter and other par ts of the air filter involves dangerous work...
– 4 – SAFETY CAUTION The impor tant contents concerned to the safety are described on the product itself and on this Service Manual. Please read this Service Manual after understanding the described items thoroughly in the following contents(Indications/Illustrated marks), and keep them. [Explanatio...
– 5 – Before troubleshooting or repair work, check the earth wire is connected to the earthterminals of the main unit, otherwise an electric shock is caused when a leak occurs.If the ear th wire is not correctly connected, contact an electric engineer for rework. Do not modify the products.Do not al...
– 6 – After the work has finished, be sure to use an insulation tester set (500V mugger) tocheck the resistance is 2M Ω Ω Ω Ω Ω or more between the charge section and the non-charge metal section (Earth position).If the resistance value is low, a disaster such as a leak or electric shock is caused a...
– 7 – • New Refrigerant (R410A) This air conditioner adopts a new HFC type refrigerant (R410A) which does not deplete the ozone layer. 1. Safety Caution Concerned to New Refrigerant The pressure of R410A is high 1.6 times of that of the former refrigerant (R22). Accompanied with change ofrefrigerant...
– 8 – 4. Tools 1. Required Tools for R410A Mixing of different types of oil may cause a trouble such as generation of sludge, clogging of capillary,etc. Accordingly, the tools to be used are classified into the following three types. 1) Tools exclusive for R410A (Those which cannot be used for conve...
– 19 – 1-3. Operation Characteristic Curve • Operation characteristic curve <Digital Inverter> RAV-SM563AT-E, RAV-SM803AT-E <Cooling> <Heating> 0 0 20 40 60 70 80 90 100 2 4 6 8 10 12 14 Compressor speed (rps) Current (A) 0 0 20 40 60 80 100 120 2 4 6 8 10 12 16 14 Compressor speed...
– 20 – • Operation characteristic curve <Super Digital Inverter> RAV-SP562AT-E, RAV-SP802AT-E <Cooling> <Heating> 0 0 20 40 60 50 70 80 100 2 4 6 8 10 12 14 Compressor speed (rps) Compressor speed (rps) Current (A) 0 20 40 60 80 Compressor speed (rps) 0 22 20 18 16 14 12 8 10 6 4 2...
– 21 – • Capacity variation ratio according to temperature RAV-SM563AT-E, RAV-SM803AT-E, RAV-SM1103AT-E, RAV-SM1403AT-ERAV-SP562AT-E, RAV-SP802AT-E, RAV-SP1102AT-E, RAV-SP1402AT-E <Cooling> <Heating> 50 55 60 65 70 75 80 85 90 95 100 105 32 33 34 35 36 37 38 39 40 41 42 43 Outdoor temp. ...
– 22 – 140 120 100 80 60 40 20 0500 700 780 900 Standard air volume 780m³/h Static pressure (P a) Air volume m³/h 140 120 108 100 80 60 40 20 0500 700 780 900 Standard air volume 780m³/h Static pressure (P a) Air volume m³/h 140 120 100 80 60 40 20 0800 1000 1200 1140 1300 Standard air volume 1140m³...
– 26 – 110 129 4449 Knock-out hole Ø125 (Air take-in port) 6-Ø4 Tapping screw undersized hole Ø160 Hanging bolt pitch 700 59 41 Main unit dimension 800 75 Hanging bolt pitch B Main unit dimension A J = M x K H Discharge port flangeN-Ø200 Hanging bolt4-M10 screw (Arranged locally) 60 to 260 9 Suction...
– 28 – 3-2. Outdoor Unit RAV-SM563AT-E, RAV-SM803AT-E ( ) ( ) Drain hole (Ø25) Drain hole (2-Ø20 × 88 long hole) 2-Ø11-14 U-shape hole(For Ø8-Ø10 anchor bolts) 8-Ø6 hole(For fixing outdoor unit) 2-Ø11 × L14 long hole(For Ø8-Ø10 anchor bolts) 54 30 600 108 125 90 30 60 20 320 (Long hole pitch F or an...
– 31 – 4. SYSTEMATIC REFRIGERATING CYCLE DIAGRAM 4-1. Indoor Unit/Outdoor Unit RAV-SM563UT-E, RAV-SM562BT-E, RAV-SM562CT-E / RAV-SM563AT-E * 4 poles are provided to this compressor. The compressor frequency (Hz) measured with a clamp meter is 2 times of revolutions (rps) of the compressor. Indoor un...
– 35 – Indoor unit Outdoor unit TCJ sensor Air heat exchanger Strainer Strainer TC sensor Packed valve Outer dia. ØA Packed valve Outer dia. ØB Max.50m Min.5m TS sensor Accumulator (1500cc) TD sensor TO sensor TE sensor 4-way valve (STF-0213Z) Ø25 × L160 Rotary compressor (DA220A2F-20L1) Heat exchan...
– 39 – 5. WIRING DIAGRAM 5-1. Indoor Unit 5-1-1. 4-Way Air Discharge Cassette Type RAV-SM563UT-E, RAV-SM803UT-E, RAV-SM1103UT-E, RAV-SM1403UT-E, RAV-SP1102UT-E FM TA TC TCJ LM1,LM2 DP FS RY302 : Fan motor: Indoor temp. sensor: Temp. sensor: Temp. sensor: Louver motor: Drain pump motor: Float switch:...
– 41 – 5-1-3. Under Ceiling Type RAV-SM562CT-E, RAV-SM802CT-E, RAV-SM1102CT-E, RAV-SM1402CT-E FM TA TC TCJ LM DP FS RY302 : Fan motor : Indoor temp. sensor : Temp. sensor : Temp. sensor : Louver motor : Drain pump motor : Float switch : Drain control relay NOTE Color Identification BLKBLUREDGRYPNKGR...
– 42 – 5-2. Outdoor Unit (Wiring Dia gram) RAV -SM563A T -E, RA V -SM803A T -E Color Identification BLKBLUREDGRYPNK ::::: BLACKBLUEREDGRAYPINK WHIBRNORNYELPUR ::::: WHITEBROWNORANGEYELLOWPURPLE NOTE CMPMVFMTETDTOTSIGBTDBCT :::::::::: CompressorPulse motor valveFan motorHeat exchanger Temp. SensorDis...
– 43 – RAV -SM1103A T -E, RA V -SM1403A T -E Color Identification BLKBLUREDGRYPNK ::::: BLACKBLUEREDGRAYPINK WHIBRNORNYELPUR ::::: WHITEBROWNORANGEYELLOWPURPLE P.C. board (MCC-1438) SUB P.C. board (MCC-1531) 44 55 22 33 11 2 11 22 11 2 11 44 55 22 33 11 PNK ORN RED BLU WHI 33 11 33 11 2 33 11 YEL BL...
– 46 – 6. SPECIFICATIONS OF ELECTRICAL PARTS 6-1. Indoor Unit 6-1-1. 4-Way Air Discharge Cassette Type RAV-SM563UT-E, RAV-SM803UT-E RAV-SM1103UT-E, RAV-SM1403UT-E, RAV-SP1102UT-E No. 1 2 3 4 5 6 Parts name Fan motor (for indoor) Thermo. sensor (TA-sensor) Heat exchanger sensor (TCJ-sensor) Heat exch...
– 55 – 7-3. Tools 7-3-1. Required Tools Refer to the “4. Tools” (Page 8) 7-4. Recharging of Refrigerant When it is necessary to recharge refrigerant, charge the specified amount of new refrigerant according to thefollowing steps. (INDOOR unit) (Liquid side) Refrigerant cylinder (With siphon pipe) Ch...
– 56 – Gauge manifold [ Cylinder with siphon ] [ Cylinder without siphon ] OUTDOOR unit Gauge manifold OUTDOOR unit Refrigerant cylinder Electronic balance Refriger ant cylinder Electronic balance Siphon 1) Be sure to make setting so that liquid can be charged. 2) When using a cylinder equipped with...
– 57 – Nitrogen gas cylinder Pipe Flow meter M Stop valve From Nitrogen cylinder Nitrogen gas Rubber plug 2. Characteristics required for flux • Activated temperature of flux coincides with the brazing temperature. • Due to a wide effective temperature range, flux is hard to carbonize. • It is easy ...
– 58 – 7-6. Instructions for Re-use Piping of R22 or R407C Instruction of Works:The existing R22 and R407C piping can bereused for our digital inverter R410A productsinstallations. NOTE) Confirmation of existence of scratch or dent of theformer pipes to be applied and also confir mation ofreliabilit...
– 59 – 7-6-5. Final Installation Checks Do not apply the refrigerator oil to the flare surface. Existing pipe: NO * Use a new pipes. Clean the pipes or use the new pipes. Trial run Is it possible to operate the existing air conditioner? Was not largely discolored oil or a large quantity of remains d...
– 60 – 7-6-6. Recovery method of refrigerant for RAV-SM563AT-E, SM803AT-E 1 2 3 L N 2 3 1 ON Refrigerant recovery switch Existing pipe switch SW801 Only when the existing gas pipe Ø19 mm is used on RAV-SM803AT-E model, change the setting of SW801 No. 3. ON 1 2 3 • When recovering refrigerant in case...
– 61 – 8. CONTROL BLOCK DIAGRAM 8-1. Indoor Control Circuit Connection Interfase (Option) Indoor control P.C. board (MCC-1402) Duct type nothing Separately sold parts for Ceiling type Separately sold parts for Ceiling type TA sensor #1 #3 A B Indoor unit Main (Sub) master remote controller Fan motor...
– 62 – +1.5 Tsc or Tsh -1.5 Ta(˚C) COOL (COOL ON) (COOL OFF) HEAT 8-2. Control Specifications No. 1 2 Item When powersupply is reset Operation modeselection Outline of specifications 1) Distinction of outdoor units When the power supply is reset, the outdoors aredistinguished, and control is exchang...
– 63 – +3.0 Ta (˚C) E D C B F G A HH(HH) H (HH) H (HH) L(H) L(H) L(H) L(L) +2.0 +2.5 +1.5 +0.5 Tsc -0.5 +1.0 No. 3 4 5 Item Roomtemperaturecontrol Automaticcapacity control(GA control) Air speedselection Outline of specifications 1) Adjustment range Remote controller setup tem- perature (°C) Wired t...
– 65 – 5 2 A J K I (˚C) A B L N M (˚C) TcTcj No. 7 8 Item Freezepreventivecontrol(Lowtemperaturerelease) High-temprelease control Outline of specifications 1) The cooling operation (including Dry operation) is performed as follows based on the detected tempera-ture of Tc sensor or Tcj sensor.When [J...
– 66 – No. 9 10 11 Item Drain pump control After-heatelimination Louver control (For 4-way airdischarge cassettetype only) Outline of specifications 1) In cooling operation (including Dry operation), the drain pump is usually operated. 2) If the float switch operates while drain pump operates, the c...
– 67 – No. 12 13 Item Frequency fixedoperation(Test run) Filter sign display(Except wirelesstype) Outline of specifications <In case of wired remote controller> 1. When pushing [CHECK] button for 4 seconds or more, [TEST] is displayed on the display screen and themode enters in Test run mode. ...
– 68 – 0˚ Full close 45˚ 103˚ Cooling Heating No. 14 15 16 Item Central controlmode selection Energy-savecontrol(By connectedoutdoor unit) Louver control1) Louver position Outline of specifications 1) Setting at the central controller side enables to select the contents which can be operated on the ...
– 70 – 8-3. Indoor Print Cir cuit Boar d 8-3-1. 4-W a y Air Disc har g e Cassette T ype / Concealed Duct T ype / Under Ceiling T ype <MCC-1402> DC fan output DC fan return Float SW Louver(Used only for 4-way AirDischarge Cassette Type,Under ceiling type) Fan output Optional output TC sensor HA...
– 71 – 9. CIRCUIT CONFIGURATION AND CONTROL SPECIFICATIONS 9-1. Indoor Control Circuit 9-1-1. Indoor P.C. Board Optional Connector Specifications 9-2. Outdoor Controls 9-2-1. Print Circuit Board P.C. Board Comparison Table for Digital Inverter 1: Applied Function Option output Outside errorinput Fil...
– 72 – F01, 02, 25A fuse P.C. board earth lead (Black) DB01:Single-phase rectifier diode Comp. lead (Red) (White) (Black) DB02: High power factor diodeQ404: High power factor circuit IGBT F03: 3.15A fuse C12, 13, 14 electrolytic capacitor CN500: Case thermo connector Fan drive circuitQ300 to Q305:FE...
– 76 – 9-2-2. Outline of Main Controls 1. Pulse Modulating V alve (PMV ) control 1) For PMV with 50 to 500 pulses during operation, respectively. 2) In cooling operation, PMV is controlled with the temperature difference between TS sensor and TC sensor. 3) In heating operation, PMV is controlled wit...
– 77 – 4. Outdoor fan control Allocations of fan tap revolutions [rpm] SM56 SM80 SM110 SM140 W 1 W 2 W 3 W 4 W 5 W 6 W 7 W 8 W 9 W A W B W C W D W E W F 200 300 350 410 480 500 530 560 640 670 700 750 800 840 840 200 300 350 410 480 500 530 560 640 670 700 750 840 940 980 250 280 320 360 410 460 520...
– 78 – 2) Heating fan control Q The outdoor fan is controlled by TE sensor, TO sensor and the operation frequency.(From Min. W1 to Max. are controlled according to the following table.) R During 3 minutes after start-up, the fan is fixedwith the maximum fan tap corresponding tozone in the following ...
– 79 – 6. Defrost control Q In heating operation, defrost operation is performed when TE sensor temperature satisfies any conditionin A zone to D zone. R The defrost operation is immediately finished if TE sensor temperature has become 12°C or more, or italso is finished when condition of 7°C < T...
– 80 – 10. TROUBLESHOOTING 10-1. Summary of Troubleshooting <W ired remote controller type> 1. Before troubleshooting 1) Required tools/instruments • + and – screwdrivers, spanners, radio cutting pliers, nippers, push pins for reset switch • Tester, thermometer, pressure gauge, etc. 2) Confirm...
– 82 – 10-2. Check Code List Error mode detected by indoor and outdoor units ¥ : Flash, ¡ : Go on, l : Go off Wireless sensor lamp display Operation Timer Ready ¥ l l l l ¥ ¥ l l ¥ l l ¥ l l ¥ ¥ l ¥ ¥ l ¥ ¥ ¡ ¥ ¥ ¡ ¥ ¥ ¡ ¥ ¥ l ¥ ¥ l ¥ l l l ¥ l l ¥ l ¥ l ¥ ¥ l ¥ ¥ l ¥ Wired remote controller Check c...
– 86 – Is inter-unit cable of A and B normal? Is there no disconnection or contact error of connector on harness from terminal block of indoor unit? Is group control operation? Is power of all indoor units turned on? Is power supplied to remote controller? AB terminal: Approx. DC18V Are two remote c...
– 91 – CN300 : Motor coil windingCN301 : Motor position detection * CN301, CN303 : Motor coil windingCN300, CN302 : Motor position detection SM110, SM140, SP56, SP80, SP110, SP140 Are connections of CN301 and CN300 of P.C. board correct? Does the fan rotate without trouble when handling the fan with...
– 103 – CN34 MCC-1402 Set Short-circuit-plug on the same position as the P. C. board to replace. Notes)When replacement If short-circuit-plug is inserted inCN34 of the P. C. board to replace,re-use it in service P. C. board. CN112 CN111 CN110 r 1 Readout of the setup data from EEPROM (Data in EEPROM...
– 104 – r 3 Writing of the setup contents to EEPROM (The contents of EEPROM installed on the service P.C. board have been set up at shipment from the factory.) 1. Push SET , CL , and TEST buttons of the remote controller at the same time for 4 seconds or more. 1 (Corresponded with No. in Remote cont...
– 105 – Memorandum for setup contents (Item code table (Example)) Type Item code [10] Setup data 0001* 0004 0007 Type 4-way air discharge cassette Concealed duct Under ceiling Abbreviated name RAV-SM563/803/1103/1403UT-E, RAV-SP1102UT-E RAV-SM562/802/1102/1402BT-E RAV-SM562/802/1102/1402CT-E * Initi...
– 106 – Sensor cover Adjust corner cap 1 2 3 4 ON Sensor P.C. board S003 Bit 1 : OFF to ON 12. SETUP AT LOCAL SITE AND OTHERS 12-1. Indoor Unit 12-1-1. Test Run Setup on Remote Controller RAV-SM563UT-E, RAV-SM803UT-E, RAV-SM562BT-E, RAV-SM802BT-E <Wired remote controller> 1. When pushing TEST ...
– 108 – <In case of wireless remote controller> Procedure 1 2 3 4 5 6 7 Description Turn on power of the air conditioner. The operation is not accepted for 5 minutes when power has been turned on at first time after installation,and 1 minute when power has been turned on at the next time and a...
– 110 – 12-1-2. Cabling and Setting of Remote Controller Control (Setup method) One or multiple indoor units are controlled by tworemote controllers.(Max. 2 remote controllers are connectable.) <Wired remote controller> How to set wired remote controlleras sub remote controller Change DIP swit...
– 111 – 12-1-3. Monitor Function of Remote Controller Switch n Call of sensor temperature display <Contents> Each sensor temperature of the remote controller, indoor unit, and outdoor unit can become known by callingthe service monitor mode from the remote controller. <Procedure> 1 Push ...
– 113 – 12-2. Setup at Local Site / Others Model name: TCB-PCNT30TLE2 12-2-1. TCC-LINK Adapter (For TCC-LINK Central Control) 1. Function This model is an optional P.C. board to connect the indoor unit to TCC-LINK (Central controller). 2. Microprocessor Block Diagram 3. TCC-LINK Wiring Connection CA...
– 114 – 4. Wiring Specifications • Use 2-core with no polar wire. • Match the length of wire to wire length of the central control system. If mixed in the system, the wire length islengthened with all indoor/outdoor inter-unit wire length at side. • To prevent noise trouble, use 2-core shield wire. ...
– 115 – 6. External View of P.C. Board 7. Address Setup In addition to set up the central control address, it is necessary to change the indoor unit number.(Line/Indoor/Group address). For details, refer to TCC-LINK Adapter Installation Manual. 12-3. How to set up central control address number When...
– 117 – Outdoor 1-1 Individual Indoor (Master/Sub) Remote controller 2-1 Sub 1-1 Sub 4-1 Master 3-1 Sub 8-1 Sub 1-1 Individual (Master/Sub) Max. 8 units 2-1 Sub 1-1 Sub 4-1 Master 8-1 Sub 13-2. Address Setup & Group Control <Terminology> Indoor unit No. : N - n = Outdoor unit line address ...
– 118 – (Example of 2-lines cabling)(Real line: Cabling, Broken line: Refrigerant pipe) Line address 1 Indoor unit address 1 Group address 1 For the above example, perform setting by connecting singly the wired remote controller without remote controller inter-unit cable. Group address Individual : ...
– 119 – 1 2 END Operation <Operation procedure> 2 1 ON / OFF FAN TEMP. SWING/FIX TIME MODE VENT UNIT SET CL FILTERRESET TEST TIMER SET UNIT No. 1 2 3 END <Operation procedure> 3 1 2 ON / OFF FAN TEMP. SWING/FIX TIME MODE VENT UNIT SET CL FILTERRESET TEST TIMER SET UNIT No. DATA SET R.C. ...
– 120 – 14. DETACHMENTS 14-1. Indoor Unit 14-1-1. 4-Way Air Discharge Cassette Type RAV-SM563UT-E, RAV-SM803UT-E, RAV-SM1103UT-E, RAV-SM1403UT-ERAV-SP1102UT-E Knob of suction g Knob of suction grille Remo Remove the str e the strap ap. Knob of suction grille Remove the strap. 3 screws ws T Tentative...
– 125 – Hose band Slide to hose side. Pump connecting par Pump connecting part Hooking cla Hooking claw Fixing scre Fixing screw Hose band Slide to hose side. Pump connecting part Hooking claw Fixing screw No. Part name Drain pumpassembly Procedure 1. Detachment 1) Perform works of items 1 of , ...
– 126 – Fixing screws Fixing band Fixing band Fixing screws Fixing screws Fixing band Fixing screws No. Part name Heatexchanger Procedure 1. Detachment 1) Recover refrigerant gas.2) Remove refrigerant pipe at the indoor unit side. 3) Perform works of items 1 of , 1 of , 1 of , 1 of and 1 o...
– 131 – 4 -3 4 -4 4 -5 4 -6 4 -7 Reinforcing bar Screws (Fixing reinforcing bar and main unit) Fan cover (Lower side) Fan cover fixing hook Bearing Hexagon head screws (Fixing bearing and main unit) Hexagon screws (Fixing fan motor and main unit) Fan motor holder Set screw of multi blade fan Multi b...
– 134 – Valve cover Wiring cover Upper cabinet Water-proof cover Cord clamp Rear cabinet Claw 14-2. Outdoor Unit RAV-SM563AT-E, RAV-SM803AT-E No. Part name Commonprocedure Procedure CAUTION Never forget to put on the gloves atworking time, otherwise an injury will becaused by the par ts, etc. 1. D...
– 141 – Front cabinet Upper plate of cabinet Water-proof cove RAV-SM1103AT-E, RAV-SM1403AT-E / RAV-SP562AT-E, RAV-SP802AT-E No. Part name Commonprocedure Procedure CAUTION Never forget to put on the gloves atworking time, otherwise an injury will becaused by the par ts, etc. 1. Detachment 1) Stop ...
– 144 – P.C. board base Inverter box (Metal sheet) Inverter control P.C. board assembly Cycle control P.C. board assembly Cycle control P.C. board assembly No. Part name Inver terassembly(Continued) Cycle P.C.board Procedure 7) Remove connectors which are connected from the cycle P.C. board to o...
– 146 – Flange nut Loosen by turning clockwise Propeller fan Fan motor Fixing claws for fan motor lead wires (3 positions) Motor base No. Part name Fan motor Procedure 1) Perform works of items 1) to 5), 7) of 2) Remove the flange nut fixing the fan motor and the propeller fan.• Loosen the flang...
– 151 – Heat exchanger Finguard Finguard Air-outlet cabinet Inverter Side cabinet Valve fixed plate Side cabinet Upper side of the end plate of heat exchanger Upper side of the end plate of heat exchanger Air-outlet cabinet No. Part name Air-outlet cabinet Side cabinet Procedure 1. Detachment 1)...
– 153 – P.C. board fixing hooks (4 positions) Cycle control P.C. board assembly No. Part name Cycle P.C. board Procedure 1) Perform the works in 1 of and . 2) Remove connectors and lead wires which are connected from the cycle P.C.board to other par ts.1. Connector CN800: Connection with IPDU ...
– 158 – Cord holder Fan motor lead wire Various sensor lead wires Reactor Partition board Reactor Electric parts box Reactor No. 11 Part name Reactor Procedure 1) Perform works of items to . NOTE)The same two reactors are installed to thisoutdoor unit though each installation placeis different.O...
– 159 – 208 225 202 226 211, 213, 219 (SM563UT-E)212, 214, 220 (SM803UT-E) 215, 217, 221 (SM563UT-E)216, 218, 222 (SM803UT-E) 227 (SM563UT-E)228 (SM803UT-E) 206 201 207 223 209 203 (SM563UT-E)204 (SM803UT-E) 210 224 ON / OFF FAN TEMP. SWING/FIX TIME MODE VENT UNIT SET CL FILTERRESET TEST TIMER SET C...
– 161 – 209 225 202 206 226 216, 218, 222 213, 214, 220 228 207 201 208 223 211 205 212 224 ON / OFF FAN TEMP. SWING/FIX TIME MODE VENT UNIT SET CL FILTERRESET TEST TIMER SET CODE No. UNIT No. TEST SETTING DATA SET R.C. No. H 230 232 231 233 ADR ˚C TEST SETTING WEEKLY TIMER ERROR SuMoTu WeTh Fr Sa P...
– 178 – INVERTER BOX INVERTER COVER 704 710 705 711 707 701 702 TE Sensor (Ø6)TS Sensor (Ø6)TO Sensor (Ø6)TD Sensor (Ø4) 708 Location Part Description No. No. 701 43150319 Sensor, TD (F4) 702 43050425 Sensor, TC (F6) 704 43160566 Terminal Block, 6P, 20A 705 43162042 Base, P.C. Board 707 4316V282 P.C...
– 179 – 42 13 14 44 20 11 12 22 21 15 17 16 3,4 6 5 33 1,2 37 38 7,8 19 36 23,24 28,29 32 25 31 30 28 25 26,27 26 23 9 10 34 39 35 Inverter 41 40 43 RAV-SP1102AT-E, RAV-SP1402AT-E Location Part Description No. No. 2 43100343 Base Ass’y 4 43041787 Compressor Ass’y,DA420A3F-21M 5 43049739 Cushion, Rub...
– 180 – 702 TD SENSOR 701 TC SENSOR (F6) 703 SENSOR ASS’Y N L 2 2 1 CN600 CN601 CN604 CN605 CN800 CN12 CN03 CN04 IC800 CN02 CN01 R501 R502 R500 707 706 710 704 P18BLU P20YEL RED P17BLU P28BLK RY01 P19YEL P21ORG P09WHI P12GRY P08WHI P13GRY P24BRW 709 705 Location Part Description No. No. 701 43050425...
– 182 – 1 -2 1 -3 Screw P.C. board cover 15-3-2. Wireless Remote Control Kit RBC-AX22CE2 No. Part name P.C. board Procedure 1. Remove the signal receiving unit from main unit. 2. Remove the set screw (1 position) and P.C. board cover. 3. Remove the p.c. board. Remarks
– 183 – 16. CORD HEATER INSTALLATION WORK This is on installation for 2 HP and 3 HP Products(RAV-SM563AT-E, RAV-SM803AT-E, RAV-SP562AT-E, RAV-SP802AT-E). In case of 4 HP or 5 HP, refer to this installation as reference. 16-1. Required parts for installation work (Recommendation) The above products c...
– 184 – No. 13 14 15 16 17 Part name Power cord Thermostatfixing plate PVC tube Shield tube Bundling tie Q’ty 1 1 1 1 1 Specifications/Vendor 2-cores x 0.75mm² or more, H05RN-F Material: SGCC-Z08, Board thickness: 0.8t Inside diameter Ø8 x outside diameter Ø11 x 70 mm Inside diameter Ø18 x outside d...
– 185 – 3. Cord heater installation wiring diagram NOTE: Separate the cord heater power from the air conditioner power, and connect it to its exclusive breaker. By doing so, the power consumption can be decreased because the breaker can be turned off if there is nopossibility of freezing of the base...
– 186 – 4. Cord heater installation work procedure Upper cabinet Valve cover Wiring cover Water-proof cover Front cabinet Side cabinet (L) Side cabinet (R) Inverter assembly No. 1 Procedure Remove each cabinet, inver ter assembly, motor base assembly, and par tition board assembly.* Do not damage th...
– 187 – Sound insulation board Partition plate assembly Motor base assembly Valve fixing plate Heat exchanger Compressor No. 1-5 1-6 1-7 Photo / Explanatory diagram Procedure Remove the motor base assembly, par tition plateassembly and the sound insulation board. Related par ts / Screws list Part na...
– 188 – Added hole 2- φ 5 Side cabinet (R) 7 5 46 Ø9.1 P-shape clamp PVC tube The PVC tube must be insertedinto the cord heater betweenthe fixing screws in order toprotect the cord heater fromthese screws. Under no circumstances mustthe tube be allowed to ride overthe tip of the fixing screws. Enlar...
– 189 – Fuse Fuse holder Thermostat Thermostat fixing plate P-shape clamp Power cord Cord heater* Transparent L side Close-end connectorinsulation tape Delete Side cabinet (L) No. 2-4 2-5 Photo / Explanatory diagram Procedure Rework the side cabinet (L) to remove par t of it. The area to be removed ...
– 190 – Side cabinet (R) Thermostat fixing plate Perform cable process for collectedcord heater and fan motor lead cables. Power cord for cord heater P-shape clamp To keep the lead wires from coming into contact with theedges of the sheet metal or tips of the screws, wrap the shield tubes around the...
– 191 – 5. Drawing of thermostat fixing plate Material: SGCC-Z08, Thickness: 0.8t 28 24 55 11 11 18 45 18 37 56 36 46 11 11 8 5.8 3-Ø3.4 burring hole (Downward) 2-Ø3.4 burring hole (Upward)
WARNINGS ON REFRIGERANT LEAKAGE For the amount of charge in this example: The possible amount of leaked refrigerant gas inrooms A, B and C is 10kg.The possible amount of leaked refrigerant gas inrooms D, E and F is 15kg. NOTE 2 : The standards for minimum room volume are as follows. (1) No partition...
TOSHIBA CARRIER CORPORATION 2 CHOME 12-32, KONAN, MINATOKU, TOKYO, 108-0075, JAPAN Copyright © 1999 to 2007 TOSHIBA CARRIER CORPORATION, ALL Rights Reserved.
Toshiba Manuals
-
Toshiba 26C100U
User Manual
-
Toshiba 26C100U
Manual
-
Toshiba 55SL412U
User Manual
-
Toshiba 55SL412U
Manual
-
Toshiba 50L5200U
User Manual
-
Toshiba 50L5200U
Manual
-
Toshiba 24V4210U
User Manual
-
Toshiba 24V4210U
Manual
-
Toshiba 40L3400U
User Manual
-
Toshiba 40L3400U
Manual
-
Toshiba 50L1350U
User Manual
-
Toshiba 50L1350U
Manual
-
Toshiba 24SLV411U
User Manual
-
Toshiba 24SLV411U
Manual
-
Toshiba 50L2400U
User Manual
-
Toshiba 58L7350U
User Manual
-
Toshiba 32L2400U
User Manual
-
Toshiba 32L2400U
Manual
-
Toshiba 50L1400U
User Manual
-
Toshiba 50L1400U
Manual