Toshiba MMU-AP0071MH- Manuals
Toshiba MMU-AP0071MH– Manual in PDF format online.
Manuals:
Manual Toshiba MMU-AP0071MH
Summary
CONTENTS SAFETY CAUTION ............................................................................................ 3 1. CONSTRUCTION VIEWS (EXTERNAL VIEWS) ........................................ 8 2. WIRING DIAGRAM ....................................................................................
3 Before troubleshooting or repair work, check the earth wire is connected to the earthterminals of the main unit, otherwise an electric shock is caused when a leak occurs.If the ear th wire is not correctly connected, contact an electric engineer for rework. Do not modify the products.Do not also d...
4 After repair work, surely assemble the disassembled parts, and connect and lead theremoved cables as before. Perform the work so that the cabinet or panel does notcatch the inner cables.If incorrect assembly or incorrect cable connection was done, a disaster such as a leak orfire is caused at user...
5 • New Refrigerant (R410A) This air conditioner adopts a new HFC type refrigerant (R410A) which does not deplete the ozone layer. 1. Safety Caution Concerned to New Refrigerant The pressure of R410A is high 1.6 times of that of the former refrigerant (R22). Accompanied with change ofrefrigerant, th...
6 4. Tools (1) Required Tools for R410A Mixing of different types of oil may cause a trouble such as generation of sludge, clogging of capillary, etc.Accordingly, the tools to be used are classified into the following three types. 1) Tools exclusive for R410A (Those which cannot be used for conventi...
7 5. Recharge of Refrigerant When recharge of the refrigerant is required, charge the new refrigerant with the specified amount in theprocedure as described below. Q Never charge the refrigerant over the specified amount. R Do not charge the additional refrigerant.If charging refrigerant additionall...
9 BLK P301 Fan motorIndoor temp. sensorTemp. sensorTemp. sensorTemp. sensorLouver motorDrain pump motorFloat switchDrain control relayPulse motor valve Symbol FM TA TC1TCJTC2 LM1, LM2 DP FS RY302 PMV Parts name Color indication RED : REDWHI : WHITEYEL : YELLOWBLU : BLUEBLK : BLACKGRY : GRAYPNK : PIN...
10 3. PARTS RATING 3-1. Parts Rating Model MMU- Fan motor Motor for horizontal grille Pulse motor Pulse motor valve TA sensor TC1 sensor TC2 sensor TCJ sensor Float switch Drain pump motor AP0071MH AP0091MH AP0121MH AP0151MH AP0181MH SWF-230-60-1R MP24Z3N EDM-MD12TF-3 EDM-B25YGTF-3 EDM-B40YGTF-3 Lea...
11 1 SET DATA display Displayed during setup of the timer. 2 Operation mode select display The selected operation mode is displayed. 3 CHECK display Displayed while the protective device works or atrouble occurs. 4 Timer time display Time of the timer is displayed. (When a troubleoccurs, the check c...
12 Operation section Push each button to select a desired operation. This remote controller can operate the maximum 8 indoor units. • The details of the operation needs to be set up once, afterward, the air conditioner can be used by pushing ON / OFF button only. 1 Air volume select button Selects t...
13 3-4. Correct Usage When you use the air conditioner for the first time or when you change the SET DATA value, follow the proce-dure below. From the next time, the operation displayed on the remote controller will star t by pushing the ON / OFF button only. Preparation Turn on the main power switc...
14 1 2 3 ON / OFF FAN TEMP. SWING/FIX TIME MODE VENT UNIT SET CL FILTERRESET TEST TIMER SET 3-5. Automatic Operation (Super Heat Recovery Type Only) When you set the air conditioner in mode or switch over from AUTO operation because of some settings change, it will automatically select either coolin...
15 3-6. TIMER Operation A type of timer operation can be selected from the following three types. OFF timer : The operation stops when the time of timer has reached the set time. Repeat OFF timer : Every time, the operation stops after the set time has passed. ON timer : The operation star ts when t...
16 3-7. Adjustment of Wind Direction • While the air conditioner stops, the horizontal flap (Up/Down air direction adjustment plate) automati- cally directs upward. • While the air conditioner is in ready status for heating, the horizontal flap (Up/Down air direction adjustment plate) directs upward...
17 3-8. Information Confirmation before operation • Turn on the power switch 12 hours before star ting the operation. • Make sure whether ear th wire is connected. • Make sure the air filter is connected to the indoor unit. Heating capacity • A heat pump system which absorbs heat from outside of the...
18 3-9. Air Conditioner Operations and Performance 3 minutes protection function 3-minutes protection function prevents the air conditioner from star ting for initial 3 minutes after the main powerswitch/circuit breaker is turned on for re-starting the air conditioner. Power failure Power failure du...
19 3-10. When the Following Symptoms are Found Check the points described below before asking repair servicing. Symptom Outdoor unit • White misty cold air or water is out. • Sometimes, noise “Pushu !” is heard. Indoor unit • “Swish” sound is heard sometimes. • Slight “Pishi!” sound is heard. • Disc...
20 Accessory parts and Parts to be procured locally H Accessory parts Refrigerant piping • Piping material used for the conventional refrigerant cannot be used. • Use copper pipe only with a wall thickness of 0.8 mm or more for Ø6.4, Ø9.5, Ø12.7. • Flare nut and flare operations are also different f...
21 • Install the air conditioner securely in a location where the base can sustain the weight of the unit adequately. • Perform the specified installation work to guard against an earthquake. If the air conditioner is not installed appropriately, accidents may occur due to the unit falling. • If ref...
22 In case of wireless type The wireless remote controller can be operated up to amaximum of 8 m from the infra-red receiver. Therefore ensure that the remote controller will bemounted and used within this stated parameter. • To prevent malfunction do not mount or operate in a location that is subje...
24 4 DRAIN PIPING WORK REQUIREMENT • Ensure insulating of the drain pipes and connecting parts on the indoor units. • The drain pipe should have a downward slope of at least 1/100 and ensure there are no swells or blockages as this will cause abnormal sounds. • The maximum traverse length of drain p...
25 Thermal insulating process • After checking of the draining, using the supplied thermal insulation fit to the flexible hose leaving no clearance at the connecting port of the indoor unit. • Fit locally procured thermal insulation to the drain pipe leaving no clearance between the supplied insulat...
26 Set notching upward. Main unit Pipe side(Required at the site) Attached heat insulating pipe Work using double spanner • Projection margin in flaring : B (Unit : mm) Rigid (Clutch type) Imperial (Wing nut type) Connection of refrigerant pipe Connect all the refrigerant pipes with the flareconnect...
27 Power supply specifications Power supply wiring and communication wiring are to be procured locally. For the power supply specification, follow the table below. Ensure power supply is adequate. An insufficient powersupply could result in unit failure. For specification of the power capacity of th...
28 Remote controller wiring • Strip approximately 14 mm of insulation off of the connecting wires. • As the remote controller wire has no polarity, there is no problem if connections to indoor unit terminal blocks A and B are reversed. Wiring diagram Wiring between indoor and outdoor units NOTE An o...
29 In case of installation to high ceiling When the unit is to be installed at a height that exceeds the standard value, adjustment to the air volume isnecessary. • For the “Setup data” in Procedure 2 , select from the “Installable ceiling height list”. Installable ceiling height list • Select setti...
30 NOTE Do not use a forced operation in cases otherthan test operation because it applies anexcessive load onto the air conditioner. In case of wired remote controller 1, 5 3 2, 4 ON / OFF FAN TEMP. SWING/FIX TIME MODE VENT UNIT SET CL FILTERRESET TEST TIMER SET How to execute test operation • To c...
31 9 TROUBLESHOOTING Confirmation and check When a fault occurs in the air conditioner, the checkcode and the indoor unit No. will appear on the displaypart of the remote controller. The check code will only be displayed while the unit isin operation. If the display disappears, operate the air condi...
33 New check code 1. Difference between the new check code and the current system The displaying method of the check code will change from this model onwards. Display on wired remote controller • [ ] goes on. • [UNIT No.] + Check code + Operation lamp (Green) flash Display on sensor part of wireless...
34 4. REFRIGERATING CYCLE DIAGRAM Air heat exchanger at indoor side Fan M Fan motor Sensor (TA) Sensor (TC1) Gas side Liquid side Strainer Capillary tube Pulse Motor Valve (PMV) Strainer Sensor (TCJ) Sensor (TC2) Functional part name Pulse Motor Valve PMV Temp. sensor 1. TA 2. TC1 3. TC2 4. TCJ Func...
39 6. APPLIED CONTROL 6-1. Setup of Selecting Function in Indoor Unit (Be sure to Execute Setup by a Wired Remote Controller) <Procedure> Execute the setup operation while the unit stops. 1 Push SET , CL , and TEST buttons simultaneously for 4 seconds or more. The firstly displayed unit No. in...
41 TYPE Item code [10] Indoor unit capacity Item code [11] Type Compact 4-way Air Discharge Cassette AbbreviatedModel name MMU-AP XXX MH Setup data 0001 0003 0005 0007 0009 Model 007 009 012 015 018 Setup data 0014 6-2. Applied Control in Indoor Unit n Remote location ON/OFF control box (TCB-IFCB-4E...
42 n Ventilating fan control from remote controller [Function] • The star t/stop operation can be operated from the wired remote controller when air to air heat exchanger or ventilating fan is installed in the system. • The fan can be operated even if the indoor unit is not operating. • Use a fan wh...
43 n Leaving-ON prevention control [Function] • This function controls the indoor units individually. It is connected with cable to the control P.C. board of the indoor unit. • In a group control, it is connected with cable to the indoor unit (Control P.C. board), and the item code - is set to the c...
44 7. TROUBLESHOOTING 7-1. Troubleshooting Summary 1. Before troubleshooting 1) Applied models Q S-MMS Multi type models Indoor unit: MMX-APXXX,Outdoor unit: MMY-MAPXXXHT8, MMY-MAPXXXT7 R Super Heat Recovery Multi type models Indoor unit: MMX-APXXX,Outdoor unit: MMY-MAPXXXFT8 S Mini-S-MMS Multi type...
45 7-2. Check Method On the remote controller (Main remote controller, Central control remote controller) and the interface P.C. boardof the outdoor unit, a check display LCD (Remote controller) or 7-segment display (on the outdoor interface P.C.board) to display the operation is provided. Therefore...
48 The check code 1. The TCC LINK check code The displaying method of the check code. Used characters Characteristics ofcode classification Block display TCC Link Alphabet + Decimal notation, 2 digits Many classification of communication/incorrect setup system Communication/Incorrect setup (4 ways),...
49 7-3. Troubleshooting by Check Display on Remote Controller In case of wired remote controller (RBC-AMT31E) CODE No. UNIT No. R.C. No. Check code Indoor unit No. in which an error occurred 3 2 1 ON / OFF FAN TEMP. SWING/FIX TIME MODE VENT UNIT SET CL FILTERRESET TEST TIMER SET Procedure 1 2 3 Desc...
50 In case of central remote controller (TCB-SC642TLE) 1. Confirmation and check When a trouble occurred on the air conditioner, the check code and the indoor unit No. are displayed on thedisplay section of the remote controller. The check code is displayed while the air conditioner operates. If the...
64 Cautions when servicing for compressor 1. Removing wires of both compressors check output of the inver ter as described below. How to check inverter output 1. Turn off the power supply. 2. Remove the compressor lead cables from the compressors. (Be sure to remove lead cables of both compressors.)...
65 7-5. Diagnosis Procedure for Each Check Code Check code [E01] Check code name Communication error between indoor and remote controller (Detected at remote controller side) Cause of operation 1. Remote controller inter-unit cable error 2. Indoor power error 3. Indoor P.C. board error 4. Remote con...
89 7-6. 7-Segment Display Function n 7-segment display on the outdoor unit (Interface P.C. board) On the interface control P.C. board, 7-segment LED to check the operating status is provided on the control P.C.board. The displayed contents are changed by combining the setup numbers of the rotary swi...
90 1. Data display of system information (Displayed on the header outdoor unit only) ∗ mark: Indicates none on display SW01 1 SW02 1 2 3 4 5 6 7 8 9 SW03 3 Display contents Refrigerant name Displays refrigerant name. A B Model with refrigerant R410A r4 10A Model with refrigerant R407C r4 07C System ...
92 3. Data display of outdoor cycle (Displayed on each outdoor unit) SW01 1 SW02 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 SW03 2 Display contents Pd pressure data Pd pressure (MPaG) is displayed with decimal data.(MPaG: Approx. 1/10 value of kg/cm 2 G data) Ps pressure data Ps pressure (MPaG) is displ...
93 5. Outdoor EEPROM write-in error code display (Displayed on the header unit only) ∗ The latest error code written in EEPROM of each outdoor unit is displayed.(It is used when confirming the error code after power supply has been reset.) Set SW01 to 03 as shown in the following table, and the push...
94 8.CONFIGURA TION OF CONTR OL CIRCUIT 8-1. Indoor Unit 8-1-1. Indoor Contr oller Bloc k Dia gram Compact 4-wa y Air Disc har g e Cassette T ype 1.Connection of wired remote contr oller Sameas left *2 Sameas left *2 #3 A B #2 A B L U1 U2 N Power supply Outdoor unit L U1 U2 N Power supply Outdoor un...
95 2.Connection of wireless remote contr oller kit Compact 4-wa y Air Disc har g e Cassette T ype Emergent operation SW CPU CPU H8/3039 Driver L A B N U1 U2 U1 U2 Sameas left *2 #3 A B L U1 U2 N Power supply Outdoor unit Sameas left *2 #2 A B L U1 U2 N Power supply Outdoor unit Network adaptor (Opti...
99 9. DETACHMENTS 9-1. Indoor Unit MMU-AP0071MH, AP0091MH, AP0121MH, AP0151MH, AP0181MH Ceiling panel: RBC-UM11PG-E Preparing work: 1. Before work, be sure to stop the power supply of the air conditioner and turn off switch of the power supply breaker. (Otherwise an electric shock may be caused.) 2....
100 No. 3 Part name Adjustcorner cover Procedure 1. Detachment 1) Perform work of procedure of 1 -1. 2) Turn clockwise screws (4 positions) at the suction por t corner until adjust cornercover rises up. NOTE) When you work, keep the torque at below 12N•m.Do not use an electric screwdriver ; otherwis...
101 No. 5 Part name Control P.C.board Procedure Remarks 1. Detachment 1) Perform works of procedure 1 -1- and 2 -1. 2) Remove the connectors connected from the control P.C. board to other par ts. CN33 : Flap motor (5P, White)CN34 : Float switch (3P, Red)CN41 : Terminal block of remote controller (3P...
103 No. 7 Part name Fan guard Procedure 1. Detachment 1) Perform work of procedure 1 -1. 2) Take off screws fixing the fan guard. (Ø4 × 10, [Screws for plastic molding] 4 pcs.) NOTE) The specification of fixing screws for the fan guarddiffers from those of other fixing screws.Therefore keep them sep...
106 No. 13 Part name PMV(Pulse Motor Valve) Procedure 1. Detachment 1) Perform work of procedure 11 -1. 2) Take off screws (Ø4 × 10, 3 pcs.) fixing the piping cover to remove the pipingcover. 3) Cut off binding band that binds the PMV lead wires. 4) Peel butyl rubber of PMV a little and remove PMV m...
107 No. 14 Part name Heatexchanger Procedure 1. Detachment 1) Recover refrigerant gas. 2) Remove the refrigerant pipe at indoor unit side. 3) Perform work of procedure 11 -1. 4) Take off screws (Ø4 × 10, 3 pcs.) fixing the piping cover to remove the piping cover. 5) While holding the heat exchanger,...
108 10. P.C. BOARD EXCHANGE PROCEDURES 10-1. Exchange of P.C. Board for Indoor Service Part code 431-6V-269 Model type MMU-AP ✻✻ ✻✻ ✻✻ ✻✻ ✻✻ 1H series MMU-AP ✻✻ ✻✻ ✻✻ ✻✻ ✻✻ 1MH series MMC-AP ✻✻ ✻✻ ✻✻ ✻✻ ✻✻ 1H series MMK-AP ✻✻ ✻✻ ✻✻ ✻✻ ✻✻ 1H series MMD-AP ✻✻ ✻✻ ✻✻ ✻✻ ✻✻ 1SPH/SH series MMU-AP ✻✻ ✻✻ ✻✻...
109 Method 2 Before exchange, it is impossible to read out the setup contents due to EEPROM error. Exchange of P.C. board for service & power ON: Procedure 2 ò Writing-in of the setup data such as the model name, capacity code, indoor unit address high ceiling setup, connection setup of option, ...
110 Procedure 2 : Exchange of P.C. board for service 1. Exchange P.C. board with a P.C. board for service. In this time, the jumper line (cut) setup or the (shor t-circuit) connecting connector setup on the previous P.C.board should be reflected on P.C. board for service. (See the blow figures.) 2. ...
111 Procedure 3 : Writing-in of setup contents to EEPROM (The EEPROM contents which are installed on the service P.C. board have been set up at shipment from the factory.) 1. Push SET + CL + TEST buttons simultaneously for 4 seconds or more. 1 ( is displayed in the UNIT No box.) In this time, is dis...
113 11. EXPLODED VIEWS AND PARTS LIST 11-1. Ceiling Panel RBC-UM11PG(W)E Location Part No. Description No. 301 43109414 Grille, Air Inlet 302 4302C059 Motor, Louver 303 43180332 Air Filter 304 43497012 Screw 305 43100322 Cover, Panel Ass’y 306 43107259 Grille, Catch 307 43122089 Cover, Joint (For Jo...
TOSHIBA CARRIER CORPORATION 2 CHOME 12-32, KONAN, MINATOKU, TOKYO, 108-0075, JAPAN Copyright © 2005 TOSHIBA CARRIER CORPORATION, ALL Rights Reserved.
Toshiba Manuals
-
Toshiba 26C100U
User Manual
-
Toshiba 26C100U
Manual
-
Toshiba 55SL412U
User Manual
-
Toshiba 55SL412U
Manual
-
Toshiba 50L5200U
User Manual
-
Toshiba 50L5200U
Manual
-
Toshiba 24V4210U
User Manual
-
Toshiba 24V4210U
Manual
-
Toshiba 40L3400U
User Manual
-
Toshiba 40L3400U
Manual
-
Toshiba 50L1350U
User Manual
-
Toshiba 50L1350U
Manual
-
Toshiba 24SLV411U
User Manual
-
Toshiba 24SLV411U
Manual
-
Toshiba 50L2400U
User Manual
-
Toshiba 58L7350U
User Manual
-
Toshiba 32L2400U
User Manual
-
Toshiba 32L2400U
Manual
-
Toshiba 50L1400U
User Manual
-
Toshiba 50L1400U
Manual