iii Contents 1. Before You Start . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1 1.1 Safety Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1 1.2 Symbols . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ...
Page 5 - Figures
v Figures Figure 2-1 Key Switch Positions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-3 Figure 2-2 AC Distribution Unit Power Switch . . . . . . . . . . . . . . . . . . . . . . 2-3 Figure 2-3 Removing the Power Supply Compartment EMI Panel . . . . . 2-5 Figure 2-4 Disconn...
Page 7 - Tables
vii Tables Table 1-1 Safety Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-2 Table 2-1 LED Status Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-25
Page 9 - Preface; How This Book Is Organized; Appendix A, “Access” details how to remove and replace system covers.
ix Preface This manual provides instructions for installing a power supply in aredundant-capable SPARCcenter ™ 2000 ™ or SPARCcenter 2000E ™ system. These instructions are designed for an experienced service provider. How This Book Is Organized Chapter 1, “Before You Start,” is an overview of the ta...
Page 10 - Related Documents
x SPARCserver 2000E Power Supply Installation Manual—April 1995 Related Documents The following documents contain information that may be helpful after theupgrade is installed. Table P-1 Related Documents Application Title Part Number Safety SPARCcenter 2000 Regulatory Compliance Manual 801-3051 Ins...
Page 11 - What Typographic Changes Mean
Preface xi What Typographic Changes Mean The following table describes the typographic changes used in this book. Shell Prompts in Command Examples The following table shows the default system prompt and superuser promptfor the C shell, Bourne shell, and Korn shell. Table P-2 Typographic Conventions...
Page 13 - Before You Start; Safety Precautions; Use properly grounded power outlets only.
1-1 Before You Start 1 This manual provides procedures for installing a power supply in a redundant-capable SPARCcenter 2000 or 2000E system cabinet. 1.1 Safety Precautions For your protection, observe the following safety precautions when setting upyour equipment: • Follow all cautions, warnings, a...
Page 14 - The following symbols mean:; WARNING
1-2 SPARCserver 2000E Power Supply Installation Manual—April 1995 1 To protect both yourself and the equipment, observe the following precautions: 1.2 Symbols The following symbols mean: WARNING Risk of electrical shock.To reducethe risk, follow the instructions. WARNING Risk of personal injury. To ...
Page 15 - Protective earth conductor.
Before You Start 1-3 1 CAUTION Risk of equipment damage. To reducethe risk, follow the instructions. AC A terminal to which alternatingcurrent or voltage may be applied. ON The principal and stand-by switchesare in the ON position. OFF The principal switch is in the OFFposition. STAND-BY The stand-b...
Page 16 - DIP/IC extraction tool
1-4 SPARCserver 2000E Power Supply Installation Manual—April 1995 1 Warning – This equipment contains lethal voltages. Accidental contact canresult in serious injury or death. Caution – Improper handling by unqualified personnel can cause seriousdamage to this equipment. Unqualified personnel who ta...
Page 17 - Power Supply Installation; This chapter provides the complete upgrade procedures.; Perform these tasks in order to install a system power supply.
2-1 Power Supply Installation 2 This chapter provides the complete upgrade procedures. Warning – Risk of electric shock. Do not work inside the cabinet while poweris applied to the system. Power down using the procedure which follows. Perform these tasks in order to install a system power supply. Sa...
Page 18 - Powering Down the System; Notify users that the system is going down.
2-2 SPARCserver 2000E Power Supply Installation Manual—April 1995 2 2.1 Operating System The correct operating system must be installed to support dual power supplyoperation. The operating system must be: Solaris 2.4 or higher, or Solaris 2.3 with the patch: ID# 101318-59 or later revision level (ob...
Page 20 - Installing the Bottom Power Supply
2-4 SPARCserver 2000E Power Supply Installation Manual—April 1995 2 2.4 Access Remove all system cover panels before proceeding with the upgrade. For theseprocedures, refer to Appendix A, “Access.” 2.5 Installing the Bottom Power Supply Note – Read and follow all safety and ESD instructions found in...
Page 21 - Disconnect the top power supply power cord.
Power Supply Installation 2-5 2 2.5.2 Installing the Supply 2.5.2.1 Preparation 1. Remove the power supply compartment EMI panel Part No. 340-3134-xx covering both power supplies. See Figure 2-3.Remove twelve 10-32 screws securing the panel in place and set aside. Figure 2-3 Removing the Power Suppl...
Page 22 - Remove the power supply cage cover panel.
2-6 SPARCserver 2000E Power Supply Installation Manual—April 1995 2 Figure 2-4 Disconnecting the Top Power Supply Power Cord 3. Remove the power supply cage cover panel. Remove six screws securing the panel, Part No. 340-3157-xx to the powersupply cage and remove the panel (it will not be reused). S...
Page 23 - Remove the AC Distribution Unit
Power Supply Installation 2-7 2 Figure 2-5 Removing the Power Supply Cage Cover Panel Remove the AC Distribution Unit 1. Disconnect all AC cables plugged into the unit, and disconnect cables from connectors J2 and J3.See Figure 2-6. Figure 2-6 AC Distribution Unit Removal and Replacement Remove scre...
Page 24 - Remove the Breaker Box; a. Unplug the power cord from the breaker box going to the top power
2-8 SPARCserver 2000E Power Supply Installation Manual—April 1995 2 Note – J3 is located on the top of the AC distribution unit, J2 is on the backside. 2. Remove the three Phillips screws and two #6-32 Phillips screws. 3. Carefully remove the power distribution unit from the system chassis. Remove t...
Page 25 - Filter Cable; supply cage and allow it to hang.; edge enters the power supply cavity first.
Power Supply Installation 2-9 2 Filter Cable 1. Free the filter cable. a. On the inside of the power supply cage, cut the tie wrap and uncoil the cable. See Figure 2-8. b. Pass the cable connector through the rectangular hole in the power supply cage and allow it to hang. Figure 2-8 Freeing the Filt...
Page 28 - Tighten all nuts and screws installed in Step 3 and Step 4.
2-12 SPARCserver 2000E Power Supply Installation Manual—April 1995 2 5. Install the bottom cover panel. Position the panel Part No. 340-3190-xx and install 12 screwsPart No. 240-1372-xx to secure the panel to the cabinet. See Figure 2-11.g Figure 2-11 Installing the Bottom Cover Panel 2.5.2.3 Main B...
Page 29 - Connect the power harness to the top power supply.; Push four spade connectors onto the spade lugs. See Figure 2-13.; Connect the power harness to the bottom power supply.; Push four spade connectors onto the spade lugs.; Secure the power harness to the cover panels.
Power Supply Installation 2-13 2 Figure 2-12 Installing the Main Bus Bar 2.5.2.4 Power Harness Installation Install the power harness, Part No. 530-2164-xx (comprised of four bus wires)to connect the two power supplies. 1. Orient the power harness as shown in Figure 2-13. 2. Connect the power harnes...
Page 31 - Filter Cable, Breaker Box and AC Distribution Unit
Power Supply Installation 2-15 2 2.5.2.5 Cabling Filter Cable, Breaker Box and AC Distribution Unit 1. Plug in the filter cable. Form a service loop in the cable and plug the connector into J2 (the topconnector) on the power supply. See Figure 2-15. 2. Replace the power breaker box. See Figure 2-15....
Page 33 - c. Replace cables in connectors J2 and J3.
Power Supply Installation 2-17 2 b. Replace the three Phillips screws and two #6-32 Phillips screws. c. Replace cables in connectors J2 and J3. 1. Plug in the three power cords: See Figure 2-17. a. Plug the main power cord into the AC distribution box J2 and the other end into breaker box J1 (bottom...
Page 34 - Remove the jumper-connector from the power supply adapter board.
2-18 SPARCserver 2000E Power Supply Installation Manual—April 1995 2 2.5.2.6 Power Supply Sense Cable 1. Remove the jumper-connector from the power supply adapter board. You will find this device plugged into the connector nearest the outsideedge of the cabinet. Remove it. See Figure 2-18. 2. Plug t...
Page 35 - Position the panel against the cabinet and secure using 12 screws.
Power Supply Installation 2-19 2 2.5.2.7 Restore the System 1. Replace the power supply compartment EMI panel. See Figure 2-3. Position the panel against the cabinet and secure using 12 screws. Figure 2-19 Replacing the Power Supply Compartment EMI Panel Screws
Page 36 - Restarting the System; The system key switch must be turned to; Local; Turn on the power switch on the AC distribution unit.; A terminal is required for viewing system messages.; Turn the key switch to; Several things will happen:
2-20 SPARCserver 2000E Power Supply Installation Manual—April 1995 2 2.6 Restarting the System Note – As the system starts up, watch for error messages from the POSTdiagnostic program. If a terminal is not already part of the system, install aTTY terminal before continuing the start up. See the SPAR...
Page 38 - Watch the terminal screen for any POST error messages.
2-22 SPARCserver 2000E Power Supply Installation Manual—April 1995 2 6. Watch the terminal screen for any POST error messages. At the conclusion of testing, POST automatically configures the system,omitting any devices that have failed diagnostics. After POST ends, thesystem will boot using the new ...
Page 39 - If the system displays “not responding” or “no carrier” messages, the; Reading Boot Messages
Power Supply Installation 2-23 2 Figure 2-21 System Reset Switch 8. If the system displays “not responding” or “no carrier” messages, the Link Integrity Test may be set incorrectly. 2.7 Reading Boot Messages Use the boot software messages to verify the presence of options in the system.After POST co...
Page 40 - Table 2-1 summarizes LED status conditions during and after POST.
2-24 SPARCserver 2000E Power Supply Installation Manual—April 1995 2 Note – The following screen display is an example only. The actual messagedisplayed on the screen will vary with the software running on the system. Note – When a system is started for the first time, or if the master board isrepla...
Page 43 - Access; A.1 Removal Procedures
A-1 Access A A.1 Removal Procedures Remove panels to afford access to the power supplies and related components. A.1.1 Opening the Hinged Door 1. Grasp the door at the upper-right corner and pull towards you firmly. See Figure 1-1. The door is secured closed by clips and ball-studs at the side oppos...
Page 44 - Grasp the panel under the vent at one end and pull it outward
A-2 SPARCserver 2000E Power Supply Installation Manual—April 1995 A Figure 1-1 Opening the Hinged Door A.1.2 Removing the Vented Front Panels 1. Grasp the panel under the vent at one end and pull it outward approximately 1 inch (2-3 centimeters) to disengage the ball studs.See Figure 1-2. 2. Repeat ...
Page 45 - To remove the left and right side panels:
Access A-3 A Figure 1-2 Removing the Vented Front Panels A.1.3 Removing the Side Panels To remove the left and right side panels: 1. Loosen two slot-head captive screws near the panel base. 2. Tilt the panel bottom out.
Page 46 - Lift the panel up until free of the tabs at the top of the chassis.; The EMI shield is located behind the front panels.; Grab the handle at the panel top to tilt the panel out to remove it.
A-4 SPARCserver 2000E Power Supply Installation Manual—April 1995 A 3. Lift the panel up until free of the tabs at the top of the chassis. Set the panel aside. Figure 1-3 Removing the Side Panels A.1.4 Removing the EMI Shield The EMI shield is located behind the front panels. 1. Remove the Phillips ...
Page 47 - Remove the two #10 Phillips screws securing the panel to the frame.
Access A-5 A Figure 1-4 Removing the EMI Shield A.1.5 Rear Screen Panel 1. Remove the two #10 Phillips screws securing the panel to the frame. See Figure 1-5. EMI shield #10 Phillips screws
Page 48 - There is a flange on the bottom of the rear screen.; A.2 Closing the System; so the bottom flange fits over the lip at the bottom of the opening.
A-6 SPARCserver 2000E Power Supply Installation Manual—April 1995 A 2. Tilt the panel top out and lift it free of the chassis. Set the panel aside. There is a flange on the bottom of the rear screen. Figure 1-5 Rear Screen Panel Removal A.2 Closing the System A.2.1 EMI Panel 1. Hold the panel by the...
Page 49 - align with tabs at the chassis top.
Access A-7 A A.2.3 Vented Front Panel ♦ Place the panel against the chassis with ball studs aligned with catches onthe panel.At both ends, tap or press the panel into place. A.2.4 Side Panels 1. Place the panel against the cabinet so the notches on the panel inside align with tabs at the chassis top...
Page 51 - Revision History
Revision History Revision Dash Date Comments 802-2700-10 -A April 1995 First Customer Ship
Page 53 - Reader Comments
Reader Comments We welcome your comments and suggestions to help improve this manual. Please let usknow what you think about the SPARCserver 2000E Power Supply Installation Manual,part number 802-2700-10. ■ The procedures were well documented. Strongly Strongly Not Agree Agree Disagree Disagree Appl...