SBD TANK TYPE HEATERS SERVICE HANDBOOK Technical Training Department Ashland City, TN ©2003 1 SBD HANDBOOK TABLE OF CONTENTS PAGE PAGE Troubleshooting (continued) Introduction 1-2 Troubleshooting the Efflkal 28-30 Wire Harness Test 31 Installation 3 IID Module 32 Clearances 4 Pilot Spark 33 Air Requ...
Page 3 - CUSTOM COMMERCIAL STORAGE TANK MODEL NUMBER BREAKDOWN; Model Breakdown
SBD TANK TYPE HEATERS SERVICE HANDBOOK Technical Training Department Ashland City, TN ©2003 2 Qualifications: Installation or service of this water heater requires ability equivalent to that of a licensed tradesman in the field involved. Plumbing, air supply, venting, gas supply and electrical testi...
Page 4 - INSTALLATION; Clearance to Combustibles Table; applicable to your specific model.; CLEARANCES FROM COMBUSTIBLES
SBD TANK TYPE HEATERS SERVICE HANDBOOK Technical Training Department Ashland City, TN ©2003 3 INSTALLATION This portion of the handbook will review some often overlooked installation considerations, taking note of necessary installation requirements for the SBD 71120 through SBD 85500 model heaters....
Page 5 - EXTERIOR CLEARANCE
SBD TANK TYPE HEATERS SERVICE HANDBOOK Technical Training Department Ashland City, TN ©2003 4 EXTERIOR CLEARANCE This illustrates the exterior roof clearances for SBD units with natural draft venting. The vent shall extend at least 3 feet above the highest point where it passes through a roof of a b...
Page 6 - AIR FOR COMBUSTION; input applies to natural and propane gas models.; EXCESS; AIR; BTU
SBD TANK TYPE HEATERS SERVICE HANDBOOK Technical Training Department Ashland City, TN ©2003 5 AIR FOR COMBUSTION 10 CUBIC FEET OF AIR PER 1,000 BTU Stoichiometric or theoretical complete combustion requires 10 cubic feet of air per 1000 BTUH input of the gas input. The National Fuel Gas Code also re...
Page 7 - minimum free area of:
SBD TANK TYPE HEATERS SERVICE HANDBOOK Technical Training Department Ashland City, TN ©2003 6 MAKE-UP AIR DIRECT COMMUNICATION A fresh supply of make-up air for combustion can be supplied to the heater through make- up air ducts which directly communicate with the out of doors. Two openings are requ...
Page 9 - INSUFFICIENT MAKE-UP AIR; BACKDRAFT
SBD TANK TYPE HEATERS SERVICE HANDBOOK Technical Training Department Ashland City, TN ©2003 8 INSUFFICIENT MAKE-UP AIR BACKDRAFT Insufficient make-up air is a major cause of combustion problems. One common example is in a restaurant installation where exhaust vent equipment was not considered in siz...
Page 10 - CONTAMINATED AIR; hydrofluoric acid and other corrosive byproducts.; should not be stored or used in the same room with the heater.
SBD TANK TYPE HEATERS SERVICE HANDBOOK Technical Training Department Ashland City, TN ©2003 9 CONTAMINATED AIR Along with adequate make-up air, the quality of the air is important. Contaminants in combustion air can lead to premature heater failure. Vapors from bleaches, soaps, waxes, salts, etc. ar...
Page 11 - GAS PRESSURE REQUIREMENTS; Natural Gas; Maximum Supply Pressure
SBD TANK TYPE HEATERS SERVICE HANDBOOK Technical Training Department Ashland City, TN ©2003 10 GAS PRESSURE REQUIREMENTS Natural Gas Propane Gas Maximum Supply Pressure 10.5" W.C. 13.8" W.C. Minimum Supply Pressure 5.0" W.C. 11" W.C. Manifold Pressure 4.0 " W.C. 10" W.C. The ...
Page 12 - SBD GAS VALVE; See step 18 for SBD-500 gas valve illustration
SBD TANK TYPE HEATERS SERVICE HANDBOOK Technical Training Department Ashland City, TN ©2003 11 SBD GAS VALVE The gas valves used on all SBD water heaters are 24 volt AC combination step opening gas valves. They incorporate the pilot valve, main valve, and gas pressure regulators into one body. The i...
Page 13 - VENTING
SBD TANK TYPE HEATERS SERVICE HANDBOOK Technical Training Department Ashland City, TN ©2003 12 VENTING Atmospheric, Single, and Multiple Heaters All SBD water heaters are classified by ANSI as category I (non-condensing, negative pressure venting) appliances. They are approved for type B vent. For l...
Page 16 - POWER VENT KITS FOR SIDEWALL VENTING
SBD TANK TYPE HEATERS SERVICE HANDBOOK Technical Training Department Ashland City, TN ©2003 15 POWER VENT KITS FOR SIDEWALL VENTING SBD water heaters can be used with power vent kits for sidewall venting. State offers power vent kits for use on installations with a maximum of 100 equivalent feet of ...
Page 17 - SBD SEQUENCE OF OPERATION; operation is necessary.
SBD TANK TYPE HEATERS SERVICE HANDBOOK Technical Training Department Ashland City, TN ©2003 16 SBD SEQUENCE OF OPERATION 1. Thermostat calls for heat 2. Flue damper opens 3. Intermittent Ignition Control 5. Main gas valve opens 7. Thermostat satisfies 4. Pilot gas opens, Pilot sparks and flame prove...
Page 18 - SBD ELECTRICAL SEQUENCE
SBD TANK TYPE HEATERS SERVICE HANDBOOK Technical Training Department Ashland City, TN ©2003 17 SBD ELECTRICAL SEQUENCE 100 – 109 Series
Page 19 - SBD ELECTRICAL SEQUENCE OF OPERATION
SBD TANK TYPE HEATERS SERVICE HANDBOOK Technical Training Department Ashland City, TN ©2003 18 SBD ELECTRICAL SEQUENCE OF OPERATION 115/60/12A
Page 20 - TROUBLESHOOTING SBD WATER HEATERS; STEP 1 - TO TEST THE TRANSFORMER
SBD TANK TYPE HEATERS SERVICE HANDBOOK Technical Training Department Ashland City, TN ©2003 19 TROUBLESHOOTING SBD WATER HEATERS To troubleshoot a SBD water heater check that: • 120 VAC is supplied to the heater • the tank is full of water • gas is supplied to the unit STEP 1 TEST THE TRANSFORMER ST...
Page 21 - HIGH LIMIT, LEFT TERMINAL TEST; Test for 24 VAC between the left high; Ground
SBD TANK TYPE HEATERS SERVICE HANDBOOK Technical Training Department Ashland City, TN ©2003 20 STEP 2 HIGH LIMIT, LEFT TERMINAL TEST STEP 2. HIGH LIMIT, LEFT TERMINAL TEST. Test for 24 VAC between the left high limit terminal and ground. N E H T F I The meter does not read 24 VAC: • Check wiring bet...
Page 23 - INSPECT THE DAMPER
SBD TANK TYPE HEATERS SERVICE HANDBOOK Technical Training Department Ashland City, TN ©2003 22 STEP 4 INSPECT THE DAMPER STEP 4. INSPECT THE DAMPER. Lower the thermostat setting so the unit will not be calling for heat, then inspect the damper. N E H T F I If the damper is open: • Go to step 5. If t...
Page 24 - PC BOARD MOTOR TEST
SBD TANK TYPE HEATERS SERVICE HANDBOOK Technical Training Department Ashland City, TN ©2003 23 STEP 6 PC BOARD MOTOR TEST STEP 6. PC BOARD/MOTOR TEST. Check for 24 VAC between the two motor lead terminals of the PC board. Disconnect the wires for this test. N E H T F I 24 VAC is not present: • Repla...
Page 25 - THERMOSTAT TEST
SBD TANK TYPE HEATERS SERVICE HANDBOOK Technical Training Department Ashland City, TN ©2003 24 STEP 7 THERMOSTAT TEST STEP 7. THERMOSTAT TEST. Set the thermostat to call for heat. Using your multimeter, test for 24 VAC between right terminal and ground. N E H T F I The meter does not read 24 VAC and...
Page 26 - EFFIKAL DAMPER
SBD TANK TYPE HEATERS SERVICE HANDBOOK Technical Training Department Ashland City, TN ©2003 25 EFFIKAL DAMPER The wiring colors from the damper PC Board are different colors than the wires on the heater wiring harness. The male/female plugs to connect the damper board to the heater harness join in o...
Page 27 - HARNESS CHART; Heater Harness; NORMAL OPERATION
SBD TANK TYPE HEATERS SERVICE HANDBOOK Technical Training Department Ashland City, TN ©2003 26 HARNESS CHART Heater Harness Function Damper Harness Black 24V Hot 1-Brown Yellow 24V from Thermostat 2-Orange Red 24V from damper 3-Yellow White 24V common 4-Black NORMAL OPERATION Condition: • Heater on ...
Page 28 - Thermostat closed, damper in process of opening; STEP 8A; Thermostat closed, damper fully open; STEP 8B
SBD TANK TYPE HEATERS SERVICE HANDBOOK Technical Training Department Ashland City, TN ©2003 27 NORMAL OPERATION (continued) Condition: • Thermostat closed, damper in process of opening STEP 8A TEST FOR 24VAC BETWEEN BLACK AND ORANGE N E H T F I . B 8 p e t S o t e u n it n o C t n e s e r p s i C A ...
Page 29 - TROUBLESHOOTING THE EFFIKAL DAMPER
SBD TANK TYPE HEATERS SERVICE HANDBOOK Technical Training Department Ashland City, TN ©2003 28 TROUBLESHOOTING THE EFFIKAL DAMPER Condition: Thermostat closed, damper closed STEP 9A TEST BETWEEN BLACK (COMMON) AND BROWN ON THE DAMPER BOARD N E H T F I t c e rr o c s i s i h T t n e s e r p s i C A V...
Page 30 - TROUBLESHOOTING THE EFFIKAL DAMPER (continued); Switch is incorrect position; Service
SBD TANK TYPE HEATERS SERVICE HANDBOOK Technical Training Department Ashland City, TN ©2003 29 TROUBLESHOOTING THE EFFIKAL DAMPER (continued) Condition: Thermostat closed, damper open. STEP 9B A1 IS CORRECT, CHECK SERVICE SWITCH POSITION N E H T F I Switch is incorrect position Replace damper board/...
Page 32 - WIRE HARNESS TEST; Test for 24 VAC between terminal 24V on the IID
SBD TANK TYPE HEATERS SERVICE HANDBOOK Technical Training Department Ashland City, TN ©2003 31 STEP 11 WIRE HARNESS TEST STEP 11. WIRE HARNESS TEST. Test for 24 VAC between terminal 24V on the IID module, and 24V GND. N E H T F I 24 VAC is not present: • Check the wiring harness. 24 VAC is present: ...
Page 33 - IID MODULE TEST
SBD TANK TYPE HEATERS SERVICE HANDBOOK Technical Training Department Ashland City, TN ©2003 32 STEP 12 IID MODULE TEST STEP 12. IID MODULE TEST (Power to the Pilot Valve). Using a multimeter, test for 24 VAC between terminal PV and 24V (GND) on the IID during the 90 second trial for ignition. N E H ...
Page 34 - PILOT SPARK TEST; Power To Module May Be Interrupted To Reset .
SBD TANK TYPE HEATERS SERVICE HANDBOOK Technical Training Department Ashland City, TN ©2003 33 STEP 13 PILOT SPARK TEST STEP 13. PILOT SPARK TEST. Visually check for spark at the pilot assembly. Note: The pilot burner mounts on the left side of the main burner. N E H T F I The igniter is not sparkin...
Page 35 - PILOT VALVE - OHM TEST
SBD TANK TYPE HEATERS SERVICE HANDBOOK Technical Training Department Ashland City, TN ©2003 34 STEP 14A PILOT VALVE - OHM TEST SBD 120 – 400 GAS VALVE STEP 14A. PILOT VALVE - OHM TEST. If pilot assembly is sparking but no pilot flame is established, disconnect the pilot valve solenoid leads. Using a...
Page 36 - PILOT VALVE TEST – SBD 500 ONLY; STEP 14B. PILOT VALVE TEST – SBD 500 ONLY.
SBD TANK TYPE HEATERS SERVICE HANDBOOK Technical Training Department Ashland City, TN ©2003 35 STEP 14B PILOT VALVE TEST – SBD 500 ONLY STEP 14B. PILOT VALVE TEST – SBD 500 ONLY. Testing the two coils of the Honeywell VR8404P 5004 gas valve used on the model SBD 500 only. Because of built in diodes,...
Page 37 - MAIN BURNER TEST; Visually check for main burner.
SBD TANK TYPE HEATERS SERVICE HANDBOOK Technical Training Department Ashland City, TN ©2003 36 STEP 15 MAIN BURNER TEST STEP 15. MAIN BURNER TEST. Visually check for main burner. N E H T F I The main burner ignites: • Sequence is complete The main burner does not ignite • Go to step 16
Page 38 - FLAME RECTIFICATION; STEP 16. FLAME RECTIFICATION
SBD TANK TYPE HEATERS SERVICE HANDBOOK Technical Training Department Ashland City, TN ©2003 37 STEP 16 FLAME RECTIFICATION STEP 16. FLAME RECTIFICATION Note: Flame rectification means that an alternating current (AC) signal is changed to a direct current (DC) signal. The pilot flame is the 'switch' ...
Page 39 - Using a multimeter, test for
SBD TANK TYPE HEATERS SERVICE HANDBOOK Technical Training Department Ashland City, TN ©2003 38 STEP 17 IID MODULE TEST Pilot is lit - Sparking has stopped. STEP 17. IID MODULE TEST (Power to the Main Valve). Using a multimeter, test for 24 VAC between terminal MV on the IID and 24V (GND). N E H T F ...
Page 40 - MAIN GAS VALVE CHECK
SBD TANK TYPE HEATERS SERVICE HANDBOOK Technical Training Department Ashland City, TN ©2003 39 STEP 18A MAIN GAS VALVE CHECK SBD 120 – 400 GAS VALVE STEP 18A. MAIN GAS VALVE CHECK. Disconnect wires from gas valve TH and TR terminals. Using a multimeter, test for 68 ohms plus or minus 5 between TH an...
Page 41 - MAIN GAS VALVE COIL CHECK; STEP 18B. MAIN GAS VALVE COIL CHECK – SBD 500 ONLY
SBD TANK TYPE HEATERS SERVICE HANDBOOK Technical Training Department Ashland City, TN ©2003 40 STEP 18B MAIN GAS VALVE COIL CHECK STEP 18B. MAIN GAS VALVE COIL CHECK – SBD 500 ONLY Condition: • Pilot lights • Sparking stops • No main burner ignition Test Procedure: • Power off • Disconnect red, main...
Page 42 - GENERAL SERVICE CHART
SBD TANK TYPE HEATERS SERVICE HANDBOOK Technical Training Department Ashland City, TN ©2003 41 GENERAL SERVICE CHART N O I T U L O S E S U A C N O I T I D N O C DAMPER OPENS NO POWER TO IID MODULE . DAMPER NOT FULLY OPEN . DEFECTIVE PROTECTOR SWITCH .EFFIKAL – REPLACE DAMPER CONTROL ASSEMBLY . REPLA...
Page 43 - GENERAL QUESTIONS AND ANSWERS
SBD TANK TYPE HEATERS SERVICE HANDBOOK Technical Training Department Ashland City, TN ©2003 42 GENERAL QUESTIONS AND ANSWERS Q. What is unique about the Canadian – SBC-CGA – models vs. U.S. SBD models? A. The Canadian models have different dimensions to meet Canadian code requirements. Q: How much e...
Page 52 - COMPONENT PART INFORMATION; NAME
SBD TANK TYPE HEATERS SERVICE HANDBOOK Technical Training Department Ashland City, TN ©2003 51 COMPONENT PART INFORMATION NAME SPECIFICATIONS DUAL CONTROLLER THERMOST AT 120-180 O RANGE, + 4 O , 5 O DIFFERENTIAL, LIQUID FILLED, ANTI- STACKING HIGH LIMIT (ECO) OPENS - 205 O FIXED, MANUAL RESET BELOW ...
Page 53 - SBD SERVICE CHECKLIST
SBD TANK TYPE HEATERS SERVICE HANDBOOK t n e m t r a p e D g n i n i a r T l a c i n h c e T Ashland City, TN ©2003 52 SBD SERVICE CHECKLIST (This service checklist may be photo copied to assist with SBD service call.) This checklist is intended to aid the Service Agent in determining that the State...
Page 55 - COMMENTS; Author: Terry Mulder
SBD TANK TYPE HEATERS SERVICE HANDBOOK t n e m t r a p e D g n i n i a r T l a c i n h c e T Ashland City, TN ©2003 54 COMMENTS Author: Terry Mulder
Page 56 - State Water Heaters; Prepared by the State Water Heaters Training Department.