Sanyo CHDXR07263 - Manuals
Sanyo CHDXR07263 – Manual in PDF format online.
Manuals:
Manual Sanyo CHDXR07263
Summary
Please Read Before Starting This air conditioning system meets strict safety and operat-ing standards. As the installer or service person, it is animportant part of your job to install or service the system so it operates safely and efficiently. Carefully read this instruction booklet before beginni...
Check of Density Limit The room in which the air conditioner is to beinstalled requires a design that in the event of refrig-erant gas leaking out, its density will not exceed a setlimit. The refrigerant (R410A), which is used in the aircondition-er, is safe, without the toxicity or combustibility o...
— CONTENTS — Section 1: CONTROL FUNCTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1 1. Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 -2 2. Selecting Outdoor Unit f...
Section 5: TROUBLE DIAGNOSIS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-1 1. Contents of Remote Controller Switch Alarm Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 -2 2. Outdoor Unit Control Panel LED Display . . . . . . . . . . . . ...
1 1 - 1 W-2WAY ECO-i SYSTEM Control Functions Contents 1. CONTROL FUNCTIONS 1. Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 -2 2. Selecting Outdoor Unit for Operation . . . . . . . . . . . . . . . . . . . . . . ....
1 Outdoor unit No.1 1 11 1 1 11 1 At time of shipment At time of shipment System address No. of indoor units No. of outdoor units Unit No. On-site setting On-site setting Not necessary Not necessaryNot necessary The W-2WAY ECO-i is a system that allows multiple outdoor units to be connected. The out...
1 (2) Delayed start for each system * For information concerning EEPROM settings, refer to the field application functions. (1) (2) Stopping individual outdoor units The last unit to stop operating is the outdoor unit that contains the inverter compressor with the shortestamount of operating time . ...
1 3-1. Compressors Mounted in the Outdoor Units Constant speed 5 hp ––– Scroll 72 96 DC Inverter DC Inverter Capacity Rotary hp = horsepower * Immediately after installation, all compressors have an operating time of zero. In this case, the compressors start in the following sequence: Inverter compr...
1 (1) (2) The inverter frequency during operation may be lower than the frequency listed above due to overload current protection control. * If Quiet mode is selected, the inverter may stabilize at a frequency lower than those stated above. For information about Quiet mode, refer to the field applic...
1 PX=125.6 °F PX –0.1 Thermostat OFF Horsepower increase prohibited Horsepower increase permitted Horsepower increase permitted Maximum requirement level [L] * Depending on the maximum requirement level of the indoor unit, the judgment temperatures for each area may vary as shown in the figure (exam...
1 (2) Heating control when outdoor unit heat exchanger is acting as an evaporator * When the above operation is finished, normal operation starts at the horsepower determined by the indoor units where thermostats are ON. Control time 1.2.3. (1) Cooling control when the outdoor unit heat exchanger is...
1 (1) (2) (3) (1) (2) (3) Control time 4-2-3. Refrigerant Oil Recovery Control between Systems Simplified flow of system refrigerant oil recovery control Refrigerant oil recovery control between systems shall be performed as the flow mentioned below. Cooling cycle 4-3-1. Defrost Methods Maximum 3 mi...
1 (1) 30 seconds after the oil level changes from 2 to 1, the recovery valves turn ON.However, if the oil level becomes 2, this control is stopped. * If the low oil level continues, that outdoor unit (oil-receiving outdoor unit) receives a supply of oil from operating outdoor units where the oil lev...
1 (1) (2) (3) (4) Control during normal operation (A) Cooling operation (B) Mixed cooling/heating operation The main purpose of this valve is to detect the flow of refrigerant (refrigerant volume) on the indoor-unit side whenthe outdoor unit heat exchanger is functioning as an evaporator. When the v...
1 Front Heatexchanger 1 72 96 7-1. Types of Electronic Thermostatic Expansion Valves [CHDX07263, CHDX09663] Capacity Electroniccontrol valve Electroniccontrol valve 1Electroniccontrol valve 2 Electroniccontrol valve 4 Heat exchanger 1 valve Heat exchanger 2 valve For SC circuit Heat exchanger 1 valv...
1 ) 7-4. SC Circuit Electronic Control Valve [MOV4] (1) SC Control (Cooling Mode only During cooling operation, the liquid refrigerant which condenses at the outdoor unit heat exchanger flows intothe receiver tank, and SC (sub-cool = supercooling) approaches 0°F. When SC is small and the length of t...
1 8-1. Fan mode * 8-3. Fixed Initial Fan Mode For the first 30 seconds after operation starts, the mode is fixed at the initial mode which was calculated from therelationship between the outdoor air temperature and the outdoor unit horsepower. If the outdoor unit horsepower changes dramatically, say...
1 20 20 – 20 20 – – 10-1. Normal Control (1) Cooling operation Position of electronic control valve Stopped Fan Thermostat OFF Thermostat ON Cooling Outdoor unit operating Outdoor unit stopped Performs SH control in the range of 55 – 480pulses. * The SH target value is controlled so that the E3 - E1...
1 Electronic thermostatic expansion valve Gas tube valve ON ON ON 20 pulses20 pulses 20 pulses A gas tube valve kit may be connected to the Type D indoor unit. When the gas tube valve kit is connected, operations of gas tube valve kit and indoor unit electronic thermostatic expansion valve are as sh...
1 (1) (2) This control is carried out regularly in cooling mode only. During stopped, fan or thermostat OFF condition, indoor unit expansion valve is opened regularly for 1 to 2 min-utes regularly (at an interval of once every 2 hours.) During the thermostat ON, the indoor unit electronic thermostat...
1 <Alarm Information> (1) Discharge temperature protection alarm This device sets an upper limit discharge temperature of 222°F for all compressors. When the discharge tem-perature reaches 222°F, that compressor is stopped and restarted. If the same high discharge condition occurs4 times, then...
1 Occurs when an open CT circuit is detected in the invertercompressor. 96 Occurs during ordinary operation when overcurrent (27 A) is detected. (1) Fan motor (2) Inverter compressor (4) CT circuit detection trouble List of Alarms (3) Constant-speed compressor List of overcurrent and lock currents A...
1 (1) (2) High-pressure sensor failure This system contains 2 types of pressure sensors: a high-pressure sensor and a low-pressure sensor. Alarms are emitted when the high-pressure sensor becomes an electrical open-circuit or a short-circuit condi-tions, and a broken wiring, short-circuit or poor co...
1 <Caution> (A) Reduce the number of outdoor units set at outdoor unit No.1 by the number of failed outdoor units. (B) At the S010 switch on the PCB of the failed outdoor unit, turn ON the switch for the compressor to dis able, and turn ON the “backup” switch. <Field Application Functions&g...
1 17-2. Anti-slime countermeasures ... EEPROM setting 0C (set only on the main unit) This setting controls the operation of the drain pump. 17-3. Delayed Start for Each System: Outdoor EEPROM 3E (set only on outdoor unit No. 1) The operation start time can be delayed according to the set system addr...
1 18-1. Snowfall Sensor Functions: Outdoor EEPROM 04 * If the snowfall sensor is used, then depending on the circumstances it is necessary to make the correct setting at all outdoor units in the system. * If “control is not performed” is set, control by the above signal is ignored. This setting is u...
1 When judgment mode is not engaged, the LED indicates the normal display (OFF), or else indicates alarms orother information. [1] Judgment mode is canceled automatically when 4 hours have passed after it was started. [2] Forced cancel Short-circuit the CHECK pin while the judgment mode display is a...
2 2 - 1 W-2WAY ECO-i SYSTEM Outdoor Unit Repair Procedures Contents 2. OUTDOOR UNIT REPAIR PROCEDURES 1. Removing Panels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 -2 2. Removing Electrical Component Box and Duct . . . . . . . . . ...
2 2 - 3 W-2WAY ECO-i SYSTEM Outdoor Unit Repair Procedures 2. Removing Electrical Component Box and Duct (1) Remove the electrical component box cover (remove 6 screws). (Fig. 3) • When closing the cover after the repair work, set the upper fringe of the cover should cometo align inside the electric...
2 2 - 5 W-2WAY ECO-i SYSTEM Outdoor Unit Repair Procedures 3. Discharging Compressor Oil Discharged oil can be used for checking the condition of the system. Based on the appearance and color of thedischarged oil, a judgment can be made on whether the system is operating normally or not. 3-1. Discha...
2 2 - 6 4. Backup Operation W-2WAY ECO-i SYSTEM Outdoor Unit Repair Procedures This system includes an emergency automatic backup function that allows the A/C to operate during the periodafter trouble occurs until repairs are made. However, during repair and at other times, use manual backup opera-t...
2 2 - 8 4. Backup Operation W-2WAY ECO-i SYSTEM Outdoor Unit Repair Procedures 4-2-2. Backup operation by setting the failed compressor not to operate Backup operation settings for each compressor INV compressor AC1 compressor Setting for backup operation OK Failed DIP switch S010: Turn BACK UP and ...
2 2 - 9 W-2WAY ECO-i SYSTEM Outdoor Unit Repair Procedures 5. Recovering Refrigerant The following equipment and tools are required: Jumper wire with clips, adjustable wrench, set of manifold gauge valves specially designed for refrigerant R410Aonly, vacuum pump, refrigerant recovery unit, pre-purge...
2 2 - 11 W-2WAY ECO-i SYSTEM Outdoor Unit Repair Procedures 5. Recovering Refrigerant (2) If the remote controller (RCS-TM80BG) is not available for maintenance of the outdoor unit Determine the outdoor unit where the unit No. setting (S007) (3P DIP switch) (Blue) on the outdoor unit control PCB is ...
2 2 - 12 5. Recovering Refrigerant W-2WAY ECO-i SYSTEM Outdoor Unit Repair Procedures 5-2-3. Refrigerant recovery procedures (2): Indoor unit with no ball valve equipped Refrigerant in all indoor units and the refrigerant tubing circuit must be pumped into the outdoor unit. The maximumrefrigerant st...
2 2 - 13 W-2WAY ECO-i SYSTEM Outdoor Unit Repair Procedures 5. Recovering Refrigerant 5-3. Recovery of Refrigerant from Entire System (1) Turn off power to the entire outdoor system. (2) Short-circuit the AP (Air Purge) pins (CN102) on the outdoor control PCB of all outdoor units, then supply power ...
2 2 - 14 6. Checking for Leakage After Repair W-2WAY ECO-i SYSTEM Outdoor Unit Repair Procedures 6-1. Pressure Check for Leakage of Outdoor Unit After completing repair of the outdoor unit, carry out the following leakage check. (1) Check that all service valves for gas tubes, liquid tube, and balan...
2 2 - 16 8. Charging Compressor Oil W-2WAY ECO-i SYSTEM Outdoor Unit Repair Procedures 8-1. If Refrigerant Has Already Been Charged to Outdoor Unit Be sure to use an exclusive oil-charging tank for charging compressor oil. Prior to charging, carry out vacuum drying inside the tank and take care that...
2 2 - 17 W-2WAY ECO-i SYSTEM Outdoor Unit Repair Procedures 8. Charging Compressor Oil (2) Charging compressor oil into oil-charging tank Connect a piece of pipe to the lower valve and then insert the other end deeply into the bottom of the oil con-tainer. Make sure you avoid letting any air be suck...
2 2 - 18 8. Charging Compressor Oil W-2WAY ECO-i SYSTEM Outdoor Unit Repair Procedures Next follow the instructions in “5-2-1. Cooling operation (for all units)” at the outdoor unit where oil will be charged,and start cooling operation at all units. When the operating conditions have stabilized, per...
2 2 - 19 W-2WAY ECO-i SYSTEM Outdoor Unit Repair Procedures 8. Charging Compressor Oil 8-3. Charging Additional Compressor Oil (after replacing compressor) The rated amount of oil is pre-charged in the compressors as given below: When replacing a faulty compressor, be sure to first measure the amoun...
2 2 - 20 9. Pumping Out Refrigerant from Outdoor Unit W-2WAY ECO-i SYSTEM Outdoor Unit Repair Procedures Required equipment and tools: This work is performed in order to collect the refrigerant from an outdoor unit where repairs (other than compressorreplacement) will be performed into other outdoor...
2 2 - 21 W-2WAY ECO-i SYSTEM Outdoor Unit Repair Procedures 9. Pumping Out Refrigerant from Outdoor Unit (8) Short-circuit the vacuum application pin on the outdoor unit control PCB of the unit to be repaired. Then turn ON the outdoor unit power. When the vacuum application pin is short-circuited an...
2 2 - 22 9. Pumping Out Refrigerant from Outdoor Unit W-2WAY ECO-i SYSTEM Outdoor Unit Repair Procedures (9) Close the gas tube and balance tube on the outdoor unit to be repaired. Then slowly close the liquid tube ser- vice valve. * When the low pressure at the outdoor unit to be repaired reaches 7...
2 2 - 23 W-2WAY ECO-i SYSTEM Outdoor Unit Repair Procedures 10. Compressor 10-1. Compressor Trouble Diagnosis and Check Methods Generally, compressor failures can be classified into the following categories. (1) Mechanical trouble (A) Locking (intrusion of foreign objects, galling, etc.) (B) Pressur...
2 2 - 24 10. Compressor W-2WAY ECO-i SYSTEM Outdoor Unit Repair Procedures 10-2. Replacing the Compressor(s) 10-2-1. Replacing only the failed compressor (1) If backup operation is required, follow the instructions in “4. Backup Operation” and engage backup operation. (2) Follow the instructions in ...
2 2 - 25 W-2WAY ECO-i SYSTEM Outdoor Unit Repair Procedures 10. Compressor 10-2-2. Replacing all compressors in a failed unit (1) Follow the instructions in “3. Discharging Compressor Oil” and drain the oil from the oil separator in the failed unit. Measure the amount of drained oil. (2) If backup o...
2 2 - 26 10. Compressor W-2WAY ECO-i SYSTEM Outdoor Unit Repair Procedures 10-2-3. Replacing all compressors in a system (1) Follow the instructions in “3. Discharging Compressor Oil” and drain the oil from the oil separators in all out- door units. Measure the amount of drained oil. (2) Follow the ...
2 2 - 27 W-2WAY ECO-i SYSTEM Outdoor Unit Repair Procedures 10. Compressor 10-2-4. Dry core cleaning If burning or other failures occur repeatedly at compressors within the same system, in many cases the cause is acid, sludge, carbon, or other substances that remain in the refrigeration cycle as the...
2 2 - 28 10. Compressor W-2WAY ECO-i SYSTEM Outdoor Unit Repair Procedures (16) After evacuating all nitrogen gas from the tubing, apply vacuum to all outdoor units where dry cores were removed until the pressure is –14.7 psig (5 Torr) or less. (17) INSTALLATION: Refer to the “Information for the Pe...
2 2 - 29 W-2WAY ECO-i SYSTEM Outdoor Unit Repair Procedures 10. Compressor Removal (1) Connect a manifold gauge to the high- and low-pressure outlet ports at the outdoor unit where the compressor will be replaced. Connect the manifold gauge to a nitrogen cylinder and perform nitrogen gas replacement...
2 2 - 30 10. Compressor W-2WAY ECO-i SYSTEM Outdoor Unit Repair Procedures (1) (2) (3) (4) (5) (6) (7) (8) (9) (10) (11) (12) (13) CAUTION CAUTION Fig. 23 Crankcaseheater Cushioning rubber(Inner 1 leg) Cushioning rubber(Temporary fastening bolts - 2 inner legs) Front view Fig. 24 Installation Remove...
2 2 - 31 W-2WAY ECO-i SYSTEM Outdoor Unit Repair Procedures 10. Compressor Removal (1) (2) Follow the instructions in “1. Removing Panels” and “2. Removing Electrical Component Box and Duct” and remove the corresponding parts from the outdoor unit where the compressor will be replaced. (3) (4) (5) (...
2 2 - 32 10. Compressor W-2WAY ECO-i SYSTEM Outdoor Unit Repair Procedures (1) (2) * (3) (4) (5) Temporary mount 2 cushion rubbers with bolts at the position as shown in the figure 27. Set up the leg of the new compressor onto the 2 cushion rubbers. Fig. 26 O-ring Fixing nutat the main unit side Fig...
2 2 - 33 W-2WAY ECO-i SYSTEM Outdoor Unit Repair Procedures 10. Compressor (6) (7) (8) (9) (10) (12) (13) Follow the instructions in “7. Evacuating System” and apply vacuum to the outdoor unit where the compres- sor was replaced. CAUTION CAUTION Fig. 28 Cushioningrubber guide Brazinglocations (3) Fr...
2 2 - 35 W-2WAY ECO-i SYSTEM Outdoor Unit Repair Procedures 11. High and Low Pressure Sensors (1) (2) (3) (1) CAUTION Fig. 29 High pressuresensor The outdoor unit connection ports for the high and low pressure sensors employ Schrader-type push-to-release valves. Therefore it is not necessary to reco...
2 2 - 36 12. Replacing 4-way Valve W-2WAY ECO-i SYSTEM Outdoor Unit Repair Procedures (1) (2) (3) Connect the manifold gauge to the high and low-pressure outlet ports at the outdoor unit where the 4-way valve will be replaced. Connect the manifold gauge to a nitrogen cylinder and perform nitrogen ga...
2 2 - 37 W-2WAY ECO-i SYSTEM Outdoor Unit Repair Procedures 12. Replacing 4-way Valve (1) (2) (3) (4) CAUTION Brazed parts(4 locations) Fig. 31 12-2. When the replacement is not available from the right side of the unit Follow the instructions of “10. Compressor” and remove the constant-speed compre...
3 3 - 1 W-2WAY ECO-i SYSTEM Outdoor Unit Maintenance Remote Controller Contents 3. OUTDOOR UNIT MAINTENANCE REMOTE CONTROLLER 1. Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 -2 2. Functions . . . . . . . . . . ...
3 3 - 2 1. Overview W-2WAY ECO-i SYSTEM Outdoor Unit Maintenance Remote Controller OUTDOOR UNIT MAINTENANCE REMOTE CONTROLLER (RCS-TM80BG) for W-2WAY ECO-i N About the outdoor unit maintenance remote controller The outdoor unit utilizes nonvolatile memory (EEPROM) on its PCB. This allows EEPROM data...
3 3 - 3 W-2WAY ECO-i SYSTEM Outdoor Unit Maintenance Remote Controller 2. Functions N Functions on the ordinary display (1) Functions: Button operations can be used to perform the following functions. • Start/stop of all indoor units • Switching between cooling and heating • Test run of all indoor u...
3 3 - 4 3. Ordinary Display Controls and Functions W-2WAY ECO-i SYSTEM Outdoor Unit Maintenance Remote Controller N Functions on the ordinary display • Connect the special service checker wiring to the outdoor unit PCB. The connection is shown in the figure below. L If the communications line in the...
3 3 - 5 W-2WAY ECO-i SYSTEM Outdoor Unit Maintenance Remote Controller 3. Ordinary Display Controls and Functions Fig. 1 L All units start/stop (Fig. 1) <Operation> The (ON/OFF operation) button can be used to start and stop all the indoor units. • The LED illuminates if any indoor units is op...
3 3 - 6 3. Ordinary Display Controls and Functions W-2WAY ECO-i SYSTEM Outdoor Unit Maintenance Remote Controller N Display (functions) • Use the temperature setting and buttons to change the item code. Item code Item Remarks Outdoor unit alarm Alarm code display No. of connected indoor units Qu...
3 3 - 8 3. Ordinary Display Controls and Functions W-2WAY ECO-i SYSTEM Outdoor Unit Maintenance Remote Controller N Concerning the 7-segment, 4-digit display remote controller timer display The unit Nos. of connected units are indicated by four 7-segment digits ( ) and a colon. 1 2 7 12 17 3 13 18 8...
3 3 - 9 W-2WAY ECO-i SYSTEM Outdoor Unit Maintenance Remote Controller 4. Monitoring Operations Display the indoor unit and outdoor unit sensor temperatures. <Operating procedure> Press and hold the (CHECK) button and buttons simultaneously for 4 seconds or longer to engage temperature monit...
3 3 - 11 W-2WAY ECO-i SYSTEM Outdoor Unit Maintenance Remote Controller 5. Outdoor Unit Alarm History Monitor • Displays outdoor unit alarms only. • Check the indoor unit alarm histories separately using the indoor unit remote controllers or other control device. <Operating procedure> Press ...
3 3 - 12 6. Mode Settings W-2WAY ECO-i SYSTEM Outdoor Unit Maintenance Remote Controller N Setting mode 1 <Operating procedure> Press and hold the (CHECK) button and (VENTILATION) button simultaneously for 4 seconds or longer. Press the temperature setting and buttons to change the item co...
3 3 - 13 W-2WAY ECO-i SYSTEM Outdoor Unit Maintenance Remote Controller 6. Mode Settings N Setting mode 2 <Operating procedure> Press and hold the (CHECK) button, button, and button simultaneously for 4 seconds or longer. Press the temperature setting and buttons to change the item code. T...
4 4 - 1 W-2WAY ECO-i SYSTEM Remote Controller Functions Contents 4. REMOTE CONTROLLER FUNCTIONS 1. Simple Settings Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 -2 2. Detailed Settings Function . . . . . . . . . . . . . . . . . . . . . . ....
4 4 - 2 1. Simple Settings Function W-2WAY ECO-i SYSTEM Remote Controller Functions This allows the filter lifetime, operating mode priority change, central control address, and other settings to be made for an individual or group-control indoor unit to which the remote controller used for simple se...
4 4 - 3 W-2WAY ECO-i SYSTEM Remote Controller Functions 1. Simple Settings Function List of Simple Setting Items Item code Item Setting data No. Description Filter sign ON time (fitlter life time) 0000 Not displayed 0001 150 hours 0002 2,500 hours 0003 5,000 hours 0004 10,000 hours 0005 Use the filter...
4 4 - 4 2. Detailed Settings Function W-2WAY ECO-i SYSTEM Remote Controller Functions This allows the system address, indoor unit address, and other settings to be made for the individual or group-control indoor unit to which the remote controller used for detailed settings is connected. When detail...
4 4 - 5 W-2WAY ECO-i SYSTEM Remote Controller Functions 2. Detailed Settings Function List of Detailed Setting Items Item code Item Setting data No. Description No. Description No. Description 0000 Semi-Concealed (A) 0001 4-Way Air Discharge (Mini) Semi-Concealed (X, XM) 0005 0006 Concealed-Duct Hig...
4 4 - 9 W-2WAY ECO-i SYSTEM Remote Controller Functions 2. Detailed Settings Function Simple setting items Item code Item Description 01 Filter sign ON time setting (filter lifetime) Changes the indoor unit filter lifetime when a high-performance filter or other optional product is installed. 02 Degree...
4 4 - 10 2. Detailed Settings Function W-2WAY ECO-i SYSTEM Remote Controller Functions Item code Item Description 03 Central control address Set when using a central control device. Used when setting the central control address manually from the remote controller. 04 Operating mode priority change N...
4 4 - 15 W-2WAY ECO-i SYSTEM Remote Controller Functions 3. Remote Controller Servicing Functions The remote controller includes a number of servicing functions. Use these as needed for test runs and inspections. List of Servicing Functions Functions Description Button operation Reset operation Unit...
4 4 - 16 3. Remote Controller Servicing Functions W-2WAY ECO-i SYSTEM Remote Controller Functions Test Run Function Operates the unit with the thermostat forced ON. <Procedure> Press and hold the button for 4 seconds or longer. “Test” appears on the remote controller LCD display (Fig. 3). ...
4 4 - 17 W-2WAY ECO-i SYSTEM Remote Controller Functions 3. Remote Controller Servicing Functions N Sensor Temperature Display Function (displayed regardless of whether unit is operating or stopped) The procedure below displays the sensor temperatures from the remote controller, indoor unit, and out...
5 5 - 1 W-2WAY ECO-i SYSTEM Trouble Diagnosis Contents 5. TROUBLE DIAGNOSIS 1. Contents of Remote Controller Switch Alarm Display . . . . . . . . . . . . . . . . . . . . . . . . . 5 -2 2. Outdoor Unit Control Panel LED Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5...
5 5 - 2 1. Contents of Remote Controller Switch Alarm Display W-2WAY ECO-i SYSTEM Trouble Diagnosis ON: Blinking: OFF: Possible cause of malfunction Wired remote control display Wireless remote controller receiver display Operation Timer Standb y for heating Serial communication errors Mis-setting R...
5 5 - 4 2. Outdoor Unit Control Panel LED Display W-2WAY ECO-i SYSTEM Trouble Diagnosis ( : ON : Blinking : OFF) LED (RED) Display meaning 1 2 After the power is turned ON (and automatic address setting is not in progress), no communication with the indoor units in that system is possible. (Both ON)...
5 5 - 5 W-2WAY ECO-i SYSTEM Trouble Diagnosis 3. Remote Controller Servicing Functions Sensor temperature display function (displayed both when unit is running and stopped) Use the following check procedure to display the sensor temperatures from the remote controller, indoor unit, and outdoor unit ...
5 5 - 6 3. Remote Controller Servicing Functions W-2WAY ECO-i SYSTEM Trouble Diagnosis Sensor Temperature Relationship Table Location where sensor is installed Sensor address Sensor type Sensor address Sensor type Indoor unit Remote controller temperature Discharge temperature sensor Indoor unit int...
5 5 - 7 W-2WAY ECO-i SYSTEM Trouble Diagnosis 4. W-2WAY ECO-i Alarm Codes With type 96, the INV compressor is compressor 1, and the constant-speed compressor is compressor 2. With type 72, the INV compressor is compressor 1. Alarm code Alarm meaning Page E06 Outdoor unit failed to receive serial com...
5 5 - 27 W-2WAY ECO-i SYSTEM Trouble Diagnosis 5. Blinking Inspection Display on the Remote Controller Blinking inspection display (2) (compressor magnet SW seizing detection) Alarm code (Blinking inspection display) Alarm meaning Compressor magnet SW seizing detectedStatus: Although an outdoor unit...
5 5 - 28 6. Inspection of Parts W-2WAY ECO-i SYSTEM Trouble Diagnosis (1) High-pressure switch (63PH1, 63PH2) • 63PH1: Disconnect the CN042 connector (3P, WHT) from the outdoor unit control panel. Measure the resis- tance between socket pins 1 and 3. The resistance is OK if the result is 0 Ω . • 63P...
5 5 - 29 W-2WAY ECO-i SYSTEM Trouble Diagnosis 7. Test Pin When the test pin on the outdoor unit control PCB is short-circuited, each part can be operated individually. • After turning OFF the main unit power, short circuit the test pin (CN022, WHT), then turn the power back ON. Output is performed ...
5 5 - 30 8. Thermister Characteristics Curve W-2WAY ECO-i SYSTEM Trouble Diagnosis 8-1. Room temp.sensor 8-2. Indoor heat exch. coil sensor (E1, E3) 40 35 30 25 20 15 10 5 0 -20 -15 -10 -5 0 5 10 15 20 8 7 6 5 4 3 2 1 0 20 30 40 50 60 Indoor Heat Exchanger temperature sensor[E1, E3] 10 15 20 25 30 3...
5 5 - 31 W-2WAY ECO-i SYSTEM Trouble Diagnosis 8. Thermister Characteristics Curve 8-4. Compressor discharge gas temp. sensor 8-3. Outdoor temp. sensor, Compressor suction gas temp. sensor Outdoor heat exch. coil sensor (C1, C2) 40 35 30 25 20 15 10 5 0 -20 -15 -10 -5 0 5 10 15 20 Outdoor temperatur...
Sanyo Manuals
-
Sanyo DP50E44
User Manual
-
Sanyo AVM-3260G
User Manual
-
Sanyo DS25230
User Manual
-
Sanyo VPC-TH1
User Manual
-
Sanyo VPC-TH1
Manual
-
Sanyo VPC-HD1010
User Manual
-
Sanyo VPC-HD1010
Manual
-
Sanyo VPC-GH2
User Manual
-
Sanyo VPC-GH2
Manual
-
Sanyo VPC-FH1
User Manual
-
Sanyo VPC-FH1
Manual
-
Sanyo VPC-CS1
User Manual
-
Sanyo VPC-CS1
Manual
-
Sanyo VPC-HD2000
User Manual
-
Sanyo VPC-HD2000
Manual
-
Sanyo DP42545
Manual
-
Sanyo CLT-2419
Manual
-
Sanyo VCC-XZ200P
Manual
-
Sanyo DVD-L70
Manual
-
Sanyo DS13310, DS19310
Manual