Page 2 - Contents; PREPARATION
ENGLISH-2 Contents PREPARATION Safety precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3Product specifications . . . . . . . . . . ...
Page 3 - ATION; Safety precautions; WARNING; GENERAL INFORMATION
ENGLISH-3 01 PREPAR ATION Safety precautions All materials supplied to this manual are indispensable for the safety of equipment .Users shall establish appropriate safety and health practices and determine the applicability of regulatory limitation based on following descriptions prior to use . WARN...
Page 4 - INSTALLING THE UNIT
ENGLISH-4 Safety precautions INSTALLING THE UNIT IMPORTANT: When installing the unit, always remember to connect first the refrigerant tubes, then the electrical lines . Always disassemble the electric lines before the refrigerant tubes . f f Upon receipt, inspect the product to verify that it has n...
Page 5 - Preparation of fire extinguisher
ENGLISH-5 01 PREPAR ATION f f Servicing shall be performed following the controlled procedure to minimize the risk of flammable refrigerant or gases . f f Do not install where there is a risk of combustible gas leakage . f f Do not place heat sources . f f Be cautious not to generate a spark as foll...
Page 6 - Leakage detection methods
ENGLISH-6 Safety precautions Leakage detection methods f f The leakage detector shall be calibrated in a refrigerant-free area . f f Make sure that the detector is not a potential source of ignition . f f The leakage detector shall be set to the LFL (lower flammability limit) . f f The use of deterg...
Page 7 - Installation location requirements
ENGLISH-7 01 PREPAR ATION Installation location requirements f f The unit shall be installed in an open space that is always ventilated . f f The local gas regulations shall be observed . f f For installation inside a building (this applies either to indoor or outdoor units installed inside) a minim...
Page 8 - Product specifications; Product compatibility
ENGLISH-8 Product specifications Product compatibility Line-up Heat pump units Chassis Model Name Split AE040RXED** AE060RXED** AE090RXED** - Mono AE050RXYD** AE080RXYD** AE120RXYD** AE160RXYD** Indoor units Tank Integrated Hydro Units Model Name Split AE200RNWSEG AE260RNWSEG AE200RNWSEG AE260RNWSEG...
Page 9 - Accessories
ENGLISH-9 01 PREPAR ATION Accessories Installation Manual (2) Zone sensor (1x10m, WH) (2) Temperature Sensor for Mixing Valve (1x15m, BLU) (1) Sensor holder of zone sensor and mixing valve (3) Sensor clip of zone sensor and mixing valve (3) Cable-tie for zone sensor and mixing valve (6) Aluminum tap...
Page 10 - Specifications
ENGLISH-10 Product specifications Specifications Model Name AE200RNWSEG AE260RNWSEG AE260RNWSGG AE200RNWMEG AE260RNWMEG AE260RNWMGG Type Split Mono Power source V/Hz 1Φ, 220-240V~, 50Hz 1Φ, 220-240V~, 50Hz 1Φ, 220-240V~, 50Hz 3Φ, 380-415V~, 50Hz 1Φ, 220-240V~, 50Hz 1Φ, 220-240V~, 50Hz 1Φ, 220-240V~,...
Page 11 - Typical application examples; Application 1: Space heating + water heating
ENGLISH-11 01 PREPAR ATION Typical application examples • The application examples given below are for illustration purposes only .• When the SAMSUNG Air-to-Water Heat Pump system is used in series with another heat source (e .g . gas boiler), ensure that the return water temperature not exceed 65 °...
Page 13 - Main components
ENGLISH-13 01 PREPAR ATION Main components ❋ ❋ Split ① ② ③ ④ ⑤ ⑥ ⑦⑨⑩ ⑪ ㉑ ⑮ ㉓ ㉕ ㉖ ⑧ ⑲ ⑱ ⑳ ⑰ ⑯ ⑭㉒ ㉔ ㉗ ㉘ ㉙ ㉚ ㉛㉜㉝ ⑬ ⑫ No. Part name Note ① Refrigerant pipe ø15 .88 (5/8"), Flare nut ② Refrigerant pipe ø6 .35 (1/4"), Flare nut ③ Hot water outlet ø22, Straight pipe ④ Secondary return ø22, Straight...
Page 17 - Functional diagram
ENGLISH-17 01 PREPAR ATION Functional diagram ❋ ❋ Split 3 G3 KIT 3-Way V/V Backup heater(2kW) PWM Pump HX_PHE Expansion Vessel(8L) Flow sensor Pressure Relief v/v Air Vent Manometer Water in Water out Temperature & pressure relief valve Drain(Tundish) T_tank T_w3 T_w2 T_w1 Heating T_eva out T_ev...
Page 18 - Dimensional drawing
ENGLISH-18 Dimensional drawing ①② ③ ④ ⑤⑥⑦ 595 700 85 85 85 85 70 70 1844 42 No Split Size type ① Refrigertant (Gas) Ø15 .88 Flare nut ② Refrigertant (Liquid) Ø6 .35 Flare nut ③ Hot water outlet Ø22, T1 .0 Straight pipe ④ Secondary return (260L option) Ø22, T1 .0 Straight pipe ⑤ Cold water inlet Ø22,...
Page 19 - Installing the unit; Installation of the indoor unit
ENGLISH-19 02 INSTALLATION Installing the unit Installation of the indoor unit The indoor unit should be installed indoors and meet the following conditions . f f Installation site should be sheltered from frost . f f In area with suitable space for servicing . f f A place with adequate ventilation ...
Page 20 - Moving the Indoor unit; Moving the Indoor unit with a fork lift
ENGLISH-20 Installing the unit Moving the Indoor unit f f Select the moving route in advance . f f Be sure that moving route is safe from weight of the indoor unit . Moving the Indoor unit with a fork lift f f Insert the fork into the wooden pallet at the bottom of the indoor unit carefully . Be car...
Page 21 - Base construction and installation of the Tank hydro unit; Drain Work
ENGLISH-21 02 INSTALLATION Base construction and installation of the Tank hydro unit Manufacturer is not responsible for the damage occurred by not following the installation standards .1 . Considering the vibration and weight of the Tank hydro unit, strength of the base ground must be strong enough...
Page 22 - Pipe work; Refrigerant pipe work
ENGLISH-22 Pipe work Refrigerant pipe work For all guide lines, specifications regarding refrigerant pipe work between the indoor unit and the outdoor unit, please follow the outdoor unit installation manual . Gas pipe (O .D .) Liquid pipe (O .D .) Indoor unit 15 .88 mm (5/8 inch) 6 .35 mm (1/4 inch...
Page 23 - Water pipe work
ENGLISH-23 02 INSTALLATION Water pipe work The hydro unit is equipped with components listed on the table below .The hot and cold water supply connections are clearly marked on the unit with labels . And service valves are provided .Whole water plumbing system including Hydro unit shall be installed...
Page 24 - Flushing and air-purging
ENGLISH-24 Pipe work Flushing and air-purging When filling water, the following start-up procedure should be followed . 1 . All system components and pipes must be tested for the presence of leaks .2 . Make-up water assembly or Flushing unit is recommended for installation and service .3 . Before co...
Page 26 - PWM characteristic curve
ENGLISH-26 Pipe work PWM characteristic curve PWM input signal(%) Max . Speed The additional pump should be the same type of product as the above graph .RecommendationGRUNDFOS UPMM 25-95 (Heating Type) Case 2) AC pump The maximum number of additional pump installation is one AC pumps (Input power 10...
Page 27 - Setting the pre-pressure of the expansion vessel; Calculating the pre-pressure of the expansion vessel
ENGLISH-27 02 INSTALLATION Setting the pre-pressure of the expansion vessel When it is required to change the default pre-pressure of the expansion vessel(1 bar), keep in mind the following guidelines: f f Use only dry nitrogen to set the expansion vessel pre-pressure . f f Inappropriate setting of ...
Page 28 - Charging water; Pressure relief valve; Piping insulation
ENGLISH-28 Pipe work Charging water Liquid Pipe Gas Pipe Cap Water Inlet Air-vent valve Water Outlet DHW Inlet Recirculation Inlet (Only 260 Liter Model) DHW Outlet After installation is completed the following procedures shall be used to charge water into the hydro unit . f f Connect water lines to...
Page 29 - Wiring work; Layout of PCB
ENGLISH-29 02 INSTALLATION Wiring work • Field-supplied electrical components such as power switch, circuit breakers, wires, terminal blocks, etc must be properly chosen with compliance with national legislation or regulation . • Switch off the power supply before making any connections .• All field...
Page 36 - Selecting solderless ring terminal
ENGLISH-36 Wiring work Selecting solderless ring terminal f f Select a solderless ring terminal of a connecting power cable based on a nominal dimensions for cable . f f Cover a solderless ring terminal and a connector part of the power cable and then connect it . Nominal dimensions for cable (mm 2 ...
Page 37 - Torque requirements
ENGLISH-37 02 INSTALLATION Torque requirements CONTROL-KIT PBA M3 M3 M3.5 M3.5 M4 Screw size Tightening torque (N·m) Part Terminal code Remarks M3 0 .5~0 .75 Control Kit PBA 2P Terminal Block PV/Peak power control SIGNAL Dry contact input R-32 ALARM Dry contact output WATER PUMP PWM signal output M3...
Page 39 - Types of allowable current; Minimum cross-sectional area of conductors; Grounding work; Grounding the power cable; Note 1) Grounding work 3
ENGLISH-39 02 INSTALLATION Types of allowable current Conductors of supply cord shall have a nominal cross-sectional area not less than that shown in the table below . Minimum cross-sectional area of conductors Rated current of appliance (A) Nominal cross-sectional area (mm2) ≤0 .2 Tinsel cord a) ≤0...
Page 40 - Checking correct grounding; Connection of the power supply and communication cable
ENGLISH-40 Wiring work Checking correct grounding If the power distribution circuit does not have a grounding or the grounding does not comply with specifications, an grounding electrode must be installed . The corresponding accessories are not supplied with the Air to Water Heat pump .1 . Select an...
Page 43 - Connecting the power terminal; Connection of the backup heater power supply
ENGLISH-43 02 INSTALLATION Connecting the power terminal f f Connect the cables to the terminal board using the solderless ring terminal . f f Use certified and reliable cables . f f Connect the cables with the torque chart as below . f f If the terminal is loose, fire may occur caused by arc . If t...
Page 44 - Connection of the thermostat; Connection of the 2-way valve
ENGLISH-44 Wiring work 1 phase 3 phase Booster heater (DHW, assembly in factory) 1 Phase ELCB 1 Phase ELCB 3 Phase ELCB DHW Tank Connection of the thermostat Description No. of wires Max. current Thickness Supply Scope Room Thermostat 4 22mA > 0 .75 mm 2 , H05RN-F or H07RH-F Field supply (220-240...
Page 47 - Connection of the 3-way valve
ENGLISH-47 02 INSTALLATION Connection of the 3-way valve Description No. of wires Mini. / Max. current Thickness Supply Scope Diverting type 3way valve 4 10mA / 50mA > 0 .75 mm 2 , H05RN-F or H07RN-F Field supply (220-240V~, Input) B17 : 3WAY (L1) B18 : 3WAY (L2) B16 : Live (L) B15 : Neutral (N) ...
Page 48 - Connection of the back-up boiler; Connecting for external contact functions; Connecting external sensors for zone control
ENGLISH-48 Wiring work Connection of the back-up boiler Description No. of wires Mini. / Max. current Thickness Supply Scope Back-up Boiler 2+ground 10mA / 50mA 0 .75mm 2 H05RN-F or H07RN-F Field supply (220-240V~, Input) L N L N When it set back up boiler on the hydro unit (relay off ) Boiler B4 : ...
Page 49 - Connecting for smart grid ready control
ENGLISH-49 02 INSTALLATION Connecting for smart grid ready control 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 Connection terminal for SG READY Signal 1 Connection terminal for SG READY Signal 2 SG READY Signal 2 SG READY Signal 1 SG READY Signal 1 SG READY Signal 2 Product operation Short Op...
Page 50 - Self-test mode of wired remote controller; Use of self-test mode
ENGLISH-50 Self-test mode of wired remote controller Use of self-test mode 0 Please enter your PASSWORD Service mode Service mode Reset All Service Mode Power Master Reset ODU K3 Reset Field Setting Value Self-Test Mode Indoor Unit Option 1 . If you want to use the various additional functions for y...
Page 51 - THERS; Troubleshooting; Thermistor
ENGLISH-51 03 O THERS Troubleshooting If the unit has some problem to work properly, the LED on hydro unit will flash and some error codes will be displayed on the controller .The following table described the explanation of error codes on the LCD display . Thermistor f f Check its resistance . 10ko...
Page 52 - Communication
ENGLISH-52 Troubleshooting Communication Display Explanation Communication error between remote controller and the Hydro unit Tracking error between remote controller and the Hydro unit Memory(EEPROM) Read/Write Error(Wired remote controller data error) E601, E604 E654 MEMORY(EEPROM) Read/Write Erro...
Page 53 - Water pump & Flow Sensor; Water flow range
ENGLISH-53 03 INSTALLATION Water pump & Flow Sensor Display Explanation Low flow rate error• in case of low flow rate in 30 sec during water pump signals is ON(Starting)• in case of low flow rate in 15 sec during water pump signals is ON(After starting)Normal flow rate error• in case of normal f...
Page 54 - DHW tank; Piping diagram
ENGLISH-54 DHW tank Piping diagram • The product must be installed without any water leakage .• Please verify that the DHW tank and other components are properly installed and reinstall them if necessary . - Use certified components and the correct tools . - Keep adequate space for the installing . ...
Page 55 - System configuration
ENGLISH-55 03 INSTALLATION No. Note No. Note ① Service valve ⑦ T-Joint ② 3 way diverting valve ⑧ Expansion relief Valve ③ Drain Valve ⑨ T-Joint ④ T-Joint ⑩ Pressure reducing valve with integrated check valve and strainer ⑤ Tundish Tank Temp Temperature sensor for DHW tank ⑥ Expansion vessel ❋ ❋ The ...
Page 56 - Switch box layout
ENGLISH-56 DHW tank Switch box layout DHW Tank Temp . CNS042(YEL) • When you set the hot water supply temperature to 55°C or less, do not use the booster heater . - The heatpump and the booster heater operate until the initial set temperature is reached . After that, only the booster heater may oper...
Page 57 - Electrical connections; Procedure; Connections to be made in the electrical box of DHW tank
ENGLISH-57 03 INSTALLATION Electrical connections Procedure • Switch off the power supply before making any connections .• Use a thermal grease in thermistor pocket after installing electric connections . WARNING Connections to be made in the electrical box of DHW tank 1 . Connect the booster heater...
Page 59 - Mixing Valve; Installation of mixing valve
ENGLISH-59 03 INSTALLATION Mixing Valve Installation of mixing valve Under Floor Radiator TW4 Balancing Vessel (Mixing tank) When two different zones are used with different temperature, adjust the temperature of discharge water to high temperature water and control the amount of bypass to provide l...
Page 60 - -zone control using Thermostat
ENGLISH-60 Mixing Valve ❋ ❋ The mixing valve is controlled based on the FCU WL value . ❋ ❋ As the #4044 value increases and the #4045 value decreases, the control speed increases . (Temperature hunting may occur if the control speed increases depending on the load .) ❋ ❋ The additional pump and mixi...
Page 61 - -Zone Control Using Remote Controller
ENGLISH-61 03 INSTALLATION 2-Zone Control Using Remote Controller 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 Tw2_z2 M Tw2_z1 Zone2 19/20 17/18 B14/B15 B10/B11 B2/B3/B5 Radiator Zone1 Under Floor Balancing Vessel Mixing Senser(Default, 15 m) CNS045(BLU) You can operate the 2-zone control usin...
Page 62 - Temperature sensor work; Example of sensor installation
ENGLISH-62 Temperature sensor work Example of sensor installation Weld the sensor holder on the selected location of the pipe and then insulate it . When the pipe is a copper pipe When the pipe is not a copper pipe Pipe Sensor holder Pipe Sensor Sensor clip Sensor Aluminum tape Sensor Rubber tape Se...
Page 63 - Setting the EHS converter
ENGLISH-63 03 INSTALLATION Setting the EHS converter Mode Selection switch Micro SD card Left position: Field Setting Value (FSV) mode Right position: Operating Data Backup mode Left position Right position f f Micro SD card is a separate purchase, using 8 ~ 32GB It's possible .
Page 64 - Reading and writing FSV; How to upload or download field settings (example)
ENGLISH-64 Temperature sensor work Reading and writing FSV How to upload or download field settings (example) 1 . Insert an SD card into the Sub PBA SD Card slot on the Hydro unit . Micro SD card 2 . Select Field Setting Value in Service mode .3 . Press Up/Down button to select FSV Upload or Downloa...
Page 65 - How to download to a microSD card
ENGLISH-65 03 INSTALLATION How to download to a microSD card 1 . Download the wired remote controller image, change the file name to “IMAGE .BIN,” and then download to microSD Card .2 . Download the wired remote controller program, change the file name to “MICOM .BIN,” and then download to microSD C...
Page 66 - When the microSD Card is removed during download
ENGLISH-66 Temperature sensor work When the microSD Card is removed during download 1 . When you remove the microSD Card during download, the “INSERT MICROSD CARD AND SYSTEM RESET” screen appears and the download is stopped . 2 . When you insert the microSD Card and press the and buttons for system ...
Page 67 - Concrete curing function; Entering procedure
ENGLISH-67 03 INSTALLATION Concrete curing function When pipes of floor heating are installed, operation for reinforcing concrete curing is applied . (Period of operation: 23 days) Entering procedure 1 . After turning off the DIP switch K3 of indoor unit (Default ON), power off and on the indoor uni...
Page 68 - Micom; DIP switch
ENGLISH-68 Concrete curing function NOTE • Definition of Dip switch function Dip S/W S/W #1 S/W #2 S/W #3 S/W #4 ON (default) • None • None • None • Turn off when an E101 error occurs OFF • Emergency heating • Emergency hot water supply • Concrete curing • E101 error does not turn off reference item...
Page 69 - Installation option setting; The procedure of option setting
ENGLISH-69 03 INSTALLATION Installation option setting f f Set the indoor unit installation option with remote controller option . The procedure of option setting High Temp Button High Fan Button Mode change Low Temp Button Low Fan Button Entering mode for option setting Option setting mode Entering...
Page 70 - Changing a particular option
ENGLISH-70 Installation option setting Changing a particular option You can change each digit of set option . Option SEG1 SEG2 SEG3 SEG4 SEG5 SEG6 Explanation PAGE MODE The option mode you want to change The tens’ digit of an option SEG you will change The unit digit of an option SEG you will change...
Page 71 - Optional : Extending the power cable
ENGLISH-71 03 INSTALLATION Optional : Extending the power cable 1 . Prepare the following tools . Tools Spec Shape Crimping pliers MH-14 Connection sleeve (mm) 20xØ6 .5 (HxOD) Insulation tape Width 19 mm Contraction tube (mm) 70xØ8 .0 (LxOD) 2 . As shown in the figure, peel off the shields from the ...