Page 2 - Dimensional drawing
2 Product Guide - LRM1070, LRM1080 LRM1070, LRM1080 The OccuSwitch is a movement detector with a build-in switch. It will switch off the lights in a room or area when it is vacated and thus save up to 30% of electrical energy. The OccuSwitch can switch any load up to 6A and control an office area of...
Page 3 - Functions advanced version; Applications
Product Guide - LRM1070, LRM1080 3 The OccuSwitch is designed for use in offices and similar applications, including toilets, storage rooms, etc. It is optimized for recessed ceiling mounting and for mounting heights between 2.5 and 3.5 meter.The surface box allows surface-mounting as well, with eit...
Page 4 - Mounting; Fixing
4 Product Guide - LRM1070, LRM1080 Mounting Fixing The OccuSwitch can be mounted in two ways; recessed in the ceiling or surface-mounted using the ceiling box.The ceiling box (LRH1070) has breakout ports for cable ducts and a breakout centrepiece. When selecting a location for the OccuSwitch, avoid ...
Page 5 - Electrical Installation
Product Guide - LRM1070, LRM1080 5 The OccuSwitch can be installed with either conventional wiring or Wieland connectors. For the second option, the Wieland cable (LCC1070) is required. The OccuSwitch comes with a detachable mains connector for easy installation. This connector is removed if the Wie...
Page 6 - Commissioning; Daylight control; Note; Turn the dial to raise or lower the required light level.; Absence mode
6 Product Guide - LRM1070, LRM1080 Commissioning Daylight control Daylight override The daylight override function prevents the lights from switching on when sufficient daylight is available. To enable this function it is necessary to set the required light level by turning the dial counterclockwise...
Page 7 - • Environmental conditions other than in a normal
Product Guide - LRM1070, LRM1080 7 Set required light level Make certain that the required light level is available and no daylight is entering the area.Calibrate by aiming the IRT9090 towards the OccuSwitch and pressing the “save” button.The lights will flash once to indicate the new level is store...
Page 8 - Specifications
8 Product Guide - LRM1070, LRM1080 Specifications Mains connection Voltage 230V AC +/10%; 50/60Hz Maximum load 6 A. (1380 VA) any load Connector screw terminal MRT3P7.62-3VE or GMVSTBW2.5/3-ST-7.62 Maximum wire range 1.5 to 2.5mm 2 Mains distribution system TN-S, 16A max, with Neutral grounded Power...
Page 9 - Data
Product Guide - LRM1070, LRM1080 9 Packing data Ordering Data Type Box dimensions (mm) Qty Material Weight (Kg) net gros LRM1070 Unit box 105 x 95 x 58 1 cardboard 0.12 0.15 LRM1070 Outer box 400 x 300 x 300 42 cardboard 5 5.6 LRM1080 Unit box 105 x 95 x 58 1 cardboard 0.12 0.15 LRM1080 Outer box 40...