Page 2 - Electrical specifications; WIRE CONNECTION; Connecting wires and the ground wire
Electrical specifications MODEL MSZ-GE06NA MSZ-GE09NAMSY-GE09NA MSZ-GE12NAMSY-GE12NA MSZ-GE15NAMSY-GE15NA MSZ-GE18NAMSY-GE18NA INDOOR UNIT Power supply (V, PHASE, Hz) 208/230, 1, 60 Min. Circuit Ampacity (A) 1.0 Fan motor (F.L.A.) (A) 0.76 OUTDOOR UNIT Power supply (V, PHASE, Hz) 208/230, 1, 60 Max. ...
Page 3 - ACCESSORIES; Drain piping for outdoor unit
1-4. INSTALLATION DIAGRAM ACCESSORIES Check the following parts before installation.<Indoor unit> (1) Installation plate 1 (2) Attachment screws for the installa-tion plate 4 × 25 mm 5 (3) Remote controller holder 1 (4) Screws for the remote controller holder3.5 × 16 mm (Black) 2 (5) Battery (...
Page 4 - • Make ground wire a little longer than; INDOOR UNIT INSTALLATION; lower than the indoor side.
• Connect wires to the appropriate terminals• For future servicing, leave some slack in the connecting wires. • Make ground wire a little longer than others. (More than 1-9/16 in. [40 mm]) 2-1. ATTACHING THE INSTALLATION PLATE • Find a stud in the wall to attach installation plate (1) horizontally b...
Page 5 - Rear or bottom piping; the unit to left and right.
2-4-2. DRAIN PIPING • If the extension drain hose has to pass through a room, be sure to wrap it with insu- lation (field-supplied). • The drain hose should point downward for easy drain. (Fig. 1)• If the drain hose provided with the indoor unit is too short, connect it with a field- supplied drain ho...
Page 6 - OUTDOOR UNIT INSTALLATION
3-1. CONNECTING WIRES FOR OUTDOOR UNIT 1) Remove the service panel.2) Remove the conduit cover.3) Attach the conduit connectors to the conduit plate with lock nuts then secure it against unit with screws. 4) Connect the ground wires of indoor/outdoor unit connecting wire (A) and power supply cord (K...
Page 7 - WARNING
3-3. PIPE CONNECTION • Fasten flare nut with a torque wrench as specified in the table (refer to 3-2.).• When fastened too tight, flare nut may eventually break and cause refrigerant leakage.• Be sure to wrap insulation around the piping. Direct contact with the bare piping may result in burns or frost...
Page 8 - RELOCATION AND MAINTENANCE; ASSEMBLY; Removal procedure; Installation procedure; assembly completely to the unit.; If the above method cannot be used
5-3. PUMPING DOWN When relocating or disposing of the air conditioner, pump down the system following the procedure below so that refrigerant is not released into the atmosphere.1) Connect the gauge manifold valve to the service port of the stop valve on the gas pipe side of the outdoor unit. 2) Ful...