Page 2 - MICROPROCESSOR CONTROL; OUTLINE OF MICROPROCESSOR CONTROL; OUTPUT to outdoor unit; Remote controller
OC274-26 10 MICROPROCESSOR CONTROL ● Compressor and outdoor fan : ON-OFF 1. OUTLINE OF MICROPROCESSOR CONTROL ● OFF-ON switching. ● COOL/DRY-FAN selector switching. ● Thermostat setting. ● TIMER mode selector-switching and Timer setting. ● HIGH-LOW fan speed switching. ● AUTO Vane selector (AIR DISC...
Page 3 - Remote controller operation buttons; FILTER button; FAN SPEED button
OC278-5 Remote controller operation buttons TIMER OFF TIMER CHECK SET TEMP. DRY COOL FAN CLOCK AUTO AUTO START STOP MODE TIMER ON/OFF CLOCK/TIMER FAN SPEED AIR DISCHARGE FILTER CHECK TEST RUN AIR SWEEP SET TEMP. TIMER SET F FANSPEED REMOTE CONTROLLER FILTER button This resets the filter service indi...
Page 4 - Caution; Remote controller display
OC278-6 TIMER OFF TIMER CHECK SET TEMP. DRY COOL FAN CLOCK AUTO AUTO START STOP MODE TIMER ON/OFF CLOCK/TIMER FAN SPEED AIR DISCHARGE FILTER CHECK TEST RUN AIR SWEEP SET TEMP. TIMER SET F FANSPEED REMOTE CONTROLLER Operation lamp This lamp lights during operation,goes off when the unit stops andflas...
Page 5 - REFRIGERANT SYSTEM DIAGRAM; Outdoor unit
OC247A-15 9 REFRIGERANT SYSTEM DIAGRAM Outdoor unit Refrigerant pipe(Option) 5/8 (with heat insulator) Outdoorheatexchanger Refrigerant pipe(Option) 3/8 (with heat insulator) Flexible tube Flared connection Ball valve Fusibleplug HighPressureSwitch Outdoor coilthermistorTH3 Ball valve Flow of refrig...
Page 6 - start until this period has ended.; INDOOR UNIT CONTROL; Press MODE button to set operation mode to Cool.; NOTE : Set temperature changes by 2 ̊F in the range 65~87 ̊F, each
OC274-27 Minimum 3 minutes 1 ON Thermostat Indoor fan Auto vane Compressor ON LOW or HIGH Initially 10 ° (Changeable by remote controller setting) LOW or HIGH ON OFF OFF CLOSE CLOSE OFF Operation starts byO N / O F F b u t t o nON. Operation stops byO N / O F F b u t t o nOFF. The room temperature d...
Page 8 - Changes by pressing the AIR DISCHARGE button.
OC274-29 (3) Auto vane control Auto vane position is set to 10 degrees airflow at the start-up of COOL operation. It can then be changed by the remotecontroller. (a) Vane position set mode & swing mode.( ! ) Every time AIR DISCHARGE button is pressed, setting will be change. ( @ ) Airflow direct...
Page 9 - (4) Detecting abnormalities in the outdoor unit; RANGE A
OC274-30 (4) Detecting abnormalities in the outdoor unit After the compressor has been continuously operated for 3 minutes, if the difference between the indoor coil temperatureand room temperature is out of RANGE C for 1 minute, the indoor fan speed will turn to low. Five minutes later, if the diff...
Page 10 - TROUBLESHOOTING; TROUBLE IN TEST RUN
OC274-38 11 TROUBLESHOOTING 1. TROUBLE IN TEST RUN The display “CENTRALLYCONTROLLED” on remotecontroller does not disap-pear. 1) Wrong address setting of remote con- troller/indoor controller board. 2) Timer adapter is connected to the remote controller. 3) Signal transmission error between indoor u...
Page 13 - Protection function is working.; OTHER TROUBLES AND CAUSES; “CENTRALLY CONTROLLED” is displayed.
OC274-42 vanes do not work. Vane motor does not work.Limit switch does not work.Connector is poorly connected.Vane motor is poorly assembled.Indoor controller board is damaged. Unit stops after 5 to20 seconds operation Protection function is working. Air discharge displayis OFF and air dis-charge bu...
Page 14 - HOW TO CHECK THE PARTS; Opening and closing temperature of protector.
OC274-43 5. HOW TO CHECK THE PARTS Room temperaturethermistor (RT1)Pipe temperaturethermistor (RT2) Fan motor (MF) Disconnect the connector, then measure the resistance using a tester.(Surrounding temperature 50°F to 86°F) Measure the resistance between the terminals using a tester.(Surrounding temp...
Page 15 - CEILING CASSETTE
OC246-37 4. How to check the parts PL12AK/PL18AK/PL24AK/PL30AK/PL36AK/PL42AK Parts name Check points Disconnect the connector then measure the resistance using a tester. (Surrounding temperature 50 - F~86 - F) Measure the resistance between the terminals using a tester. (Surrounding temperature 68 -...
Page 16 - How to check the parts; Thermistor R; PC MODELS: CEILING SUSPENDED INDOOR UNITS
OC278-39 5. How to check the parts Parts name Check points Disconnect the connector then measure the resistance using a tester.(Ambient temperature 50 ° F to 86 ° F) Measure the resistance between the terminals using a tester.(Ambient temperature 77 ° F) Vane motor (MV) (Refer to the thermistor) Roo...
Page 17 - OUTDOOR MICROPROCESSOR CONTROL; Protection function
OC247A-16 10 MICROPROCESSOR CONTROL OUTDOOR MICROPROCESSOR CONTROL 1. Protection function (1) As soon as a reversed phase, an open phase, or a P. C. board trouble is sensed, the operation stops and the check code is displayed by LED on the outdoor controller board. (2) When a protection function suc...
Page 18 - Function of switches on the outdoor controller board
OC247A-17 6. Fixed fan-output While the compressor is operating and the fan output step is indicated by LED, pushing SW2 fixes the fan output of that time.The fixed fan-output can be released when either of the following conditions is satisfied. 1 SW2 is pushed again. 2 SW3 setting is changed. 3 The...
Page 20 - mode the indication changes to output state indication.
OC247A-19 1-1 Outdoor coil temperature To obtain data on the outdoor coil temperature,add the number of bits of lighting LEDs, andsee the graph to find the temperature. 1-2 Fan output step To obtain data on the fan output step, add the number of bits of lighting LEDs, and see the graph below to find...
Page 22 - WRONG WIRING ON SITE; -1 Between remote controller and indoor unit; OUTDOOR UNIT
OC247A-21 4. WRONG WIRING ON SITE 4-1 Between remote controller and indoor unit If wire is disconnected between the remote controller and the indoor unit, the POWER ON display does not appear despiteturning the power switch ON. The beep sound is not heard, either. 4-2 Phenomena due to wrong wiring b...