Page 2 - INSTALLATION INSTRUCTIONS; This manual provides instructions for conversion:; from; CAUTION
INSTALLATION INSTRUCTIONS This manual provides instructions for conversion: from to Analog Temperature Controller (A), PN 28071-0012 (without high-limit and cool down function)................................ Analog Temperature Controller (A), PN 28071-0018 (with high-limit and cool down function).....
Page 4 - Electrical Connections; Proceed as follows to make electrical connections:
Installing the Digital Controller Step Procedure 1. Insert the Digital Temperature Controller into the same panel slot making sure the face of the controlleris upright with the display on top and the push buttons on the bottom. 2.. Identify the two rectangular holes on top and bottom of the control ...
Page 5 - Figure 2 - Analog to Digital Terminal; Figure 3 - Modulating Control Circuit; Table 1 - Terminal Cross Reference
4 } 8 7 6 5 4 L2 L1 9 10 11 12 13 14 15 16 Connect To Connect To [13] [14] [15] [16] [1] [2] Remove From Remove From [5] [6] [L2] [L1] [G] 500 Not used oncertain modelgas and electricovens. NO CONNECT FIGURE 2 - BACK SIDE OF TEMPERATURE CONTROLLER } 8 7 6 5 4 L2 L1 9 10 11 12 13 14 15 16 Connect To ...
Page 7 - NOTE; Table 2 - Wiring Configurations
6 PS200 Gas Oven, 208-240V, 50/60Hz, 1 Ph, 3W...............................................................Figure 5PS200 Gas Oven, 200V, 50/60Hz,1 Ph, 2W (Export Only)................................................Figure 5PS200 Gas Oven, 208V, 50/60Hz,1 Ph, 2W (Export Only)...........................
Page 9 - Programming; A copy is enclosed with the new temperature control.
Programming After the Digital Temperature Control has been properly installed and wired, it is ready to be programmed for either thestandard on/off cycling gas solenoid/electric heating system, or the modulating gas valve system. Then, as requested bythe customer, the controller can be set for set l...
Page 10 - no; Figure 14 - Service Instructions
D i g i t a l T e m p e r a t u r e C o n t r o l l e r P N 3 6 0 5 6 S e r v i c e i n s t r u c t i o n s Push the lock key and the service key together to reach SP LOK,then use the service key to step through the other functions listedb e l o w . Use the arrow keys to change the function settings...
Page 11 - Digital Temperature Controller
SERVICE KEY: Service use only SET PT: Lit when controller is displaying set point temperature. UP and DOWN arrow keys: Used to change the set point. Press UNLOCK & SET POINT keys simultaneously to unlock set point, UP & DOWN keys will now function for 60 seconds. If SET POINT will not change...
Page 12 - Diagnostic Error Messages; Display; rPLC; Table 3 - Diagnostic Error Messages; ©1997 Middleby Marshall Inc.
Diagnostic Error Messages The controller runs background tests during normal operation. If a problem with the background tests occurs, an errormessage is shown (flashing) in the Display. These are called Diagnostic Error Messages (Table 3). Display Corrective Action rPLC rSET OPEn r TC Oven temperat...