Page 3 - TABLE OF CONTENTS
i TABLE OF CONTENTS I MPORTANT S AFETY I NSTRUCTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 G LOSSARY OF S YMBOLS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 G ENERAL D ESCRIPTION . . . . . . . ....
Page 5 - WARNING
1 IMPORTANT SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS This manual contains important instructions that should be closely followed during installation and maintenance of this UPStation GXT 6kVA Maintenance Bypass.This product is designed for commercial / industrial use only. This product is not int...
Page 6 - GLOSSARY OF SYMBOLS; Risk of electrical shock
2 GLOSSARY OF SYMBOLS Risk of electrical shock Indicates Warning or Caution followed by important instructions Requests the user to consult the manual Equipment grounding conductor On Off i
Page 7 - GENERAL DESCRIPTION
3 GENERAL DESCRIPTION Congratulations on your purchase of Liebert's UPStation GXT 6 kVA Maintenance Bypass. As with every Liebert product, we stand behind our quality. If you have any questions concerning this Maintenance Bypass, please feel free to contact your local sales representative, or call t...
Page 9 - MAJOR COMPONENTS
5 MAJOR COMPONENTS The following is a general description of each component and its functions. Please review this section carefully, as it will give you a better understanding as to how the UPStation GXT 6 kVA Maintenance Bypass operates. B YPASS S WITCH The Bypass Switch allows easy and rapid trans...
Page 10 - CABLE INSTALLATION; CAUTION; Power Cable and Protection Ratings
6 CABLE INSTALLATION W IRING P REPARATION For access to terminal blocks, see diagrams on page 4. P OWER C ABLE I NSTALLATION Refer to the chart below when selecting cables: ! CAUTION Please read this section thoroughly before attempting to install wiring to this unit.Be sure that the unit is not con...
Page 14 - CL
10 WALL-MOUNT DIAGRAM D IAGRAM FOR A TTACHING U NIT TO W ALL Use the following diagram, which shows the location and measurements of factory-cut mounting slots, when preparing to attach the GXT Maintenance Bypass to a wall. Liebert recommends using 1/4-20 mounting screws. Rubber pads are supplied fo...
Page 15 - HARDWIRE OUTPUT OPTION
11 HARDWIRE OUTPUT OPTION This product is intended to be installed by a qualified electrician only.1. COMPLETELY REMOVE ALL POWER FROM THE FRAME. If the Maintenance Bypass is connected to the UPS, disconnect external battery supply. 2. Remove the end cover plate to access the terminal block (see Acc...
Page 16 - OPERATING PROCEDURES; UPS
12 OPERATING PROCEDURES START-UP AND INITIALIZATION Follow these steps in order to start up the GXT 6kVA UPS while connected to the Maintenance Bypass. O N M AINTENANCE B YPASS 1. Set the Maintenance Bypass switch (SW1) to UPS position. 2. Close (position I ) UPS Input switch (SW2). 3. Close (positi...
Page 17 - SPECIFICATIONS
13 SPECIFICATIONS Typical Transfer Time(to or from maintenance bypass) < 6 milliseconds Input Voltage Nominal 208VAC or 240VAC Total Current 30A max. Operating Ambient Temperature 0° to +40° C Storage Ambient Temperature -20° to +60° C Dimensions, W x D x H, in (mm) 8.2 x 21.0 x 6.2 (209 x 534 x ...
Page 20 - OWER; UPStation GXT 6 kVA Maintenance Bypass; SER
The Company Behind the Products With over a million installations around the globe,Liebert is the world leader in computer protectionsystems. Since its founding in 1965, Liebert hasdeveloped a complete range of support andprotection systems for sensitive electronics: • Environmental systems—close-co...