Page 3 - TABLE OF CONTENTS; Parallel Connection (see; Figures 2 and 3
i TABLE OF CONTENTS 1.0 I NTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 2.0 U NPACKING AND I NSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 2.1 Unpacking and Preliminary...
Page 4 - ii; FIGURES
ii FIGURES Figure 1 Typical cabinet data, Form C contact and wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Figure 2 Typical parallel connections (without internal rotary disconnect). . . . . . . . . . . . . . . . . . . . . . . 6 Figure 3 Typical parallel connection...
Page 5 - Introduction 1; NTRODUCTION
Introduction 1 1.0 I NTRODUCTION The Liebert Interceptor II Series Transient Voltage Surge Suppressor (TVSS) is a high-quality, high energy surge current diversion system designed to protect sensitive equipment from damag- ing transient voltage surges. Proper installation is required for maximum sys...
Page 6 - Unpacking and Installation; NPACKING; Unpacking and Preliminary Inspection
2 Unpacking and Installation 2.0 U NPACKING AND I NSTALLATION 2.1 Unpacking and Preliminary Inspection 1. Inspect the shipping crate(s) for damage or signs of mishandling before unpacking the unit.2. Remove any securing bands and cardboard packing and inspect the unit for any obvious shipping damage...
Page 7 - Series
Unpacking and Installation 3 Figure 1 Typical cabinet data, Form C contact and wiring Table 1 Units with or without internal service disconnect switch **Model Series Application Connection Dimensions (Inches) Weight (lbs.) A B C D E F SI016SI025 All voltage configurations* Wire Lugs 16 12 9 16.75 10...
Page 8 - Electrical Connections; LECTRICAL; Voltage Ratings and Power Source Configurations; Standard for Safety, Transient; Parallel Connection; Table 2; Model Series
4 Electrical Connections 3.0 E LECTRICAL C ONNECTIONS All electrical connections should be installed only by a qualified (licensed) electrician. All wiring must comply with the National Electrical Code (NEC) and applicable local codes. 3.1 Voltage Ratings and Power Source Configurations Before makin...
Page 9 - Electrical Connections 5; Disconnect Switch; ponents for servicing.; Table 3; Source Configurations; Three Phase Delta 3W+G; For other voltages or source configurations, consult factory.
Electrical Connections 5 Disconnect Switch —TVSS units must be connected to the load side of the main service discon- nect, or load side of a protected circuit’s disconnecting means.Interceptor II “SI” Models with an “R” designator in the part number, are equipped with an inter- nal disconnect switc...
Page 10 - Electrical Connections; Figure 2; ra
6 Electrical Connections Figure 2 Typical parallel connections (without internal rotary disconnect) Figure 3 Typical parallel connections (with internal rotary disconnect) Phas es Neut ra l Gr ou nd Liebert Surge Protective Protected Panel To Loads Protected Wire should be less than 5 feet and strai...
Page 11 - Electrical Connections 7; safety hazard and is not recommended.; Grounding Electrode
Electrical Connections 7 3.2.1 System Grounding and Bonding The performance and safety of any TVSS system is dependent on proper grounding and bonding. Grounding is required primarily for safety. Correct implementation also enhances equipment per- formance. Incorrect grounding can reduce or impede t...
Page 12 - PERATION; Figure 4; summary of all surge modules within device.; Full Protection LEDs; —Green LEDs are illuminated only when all surge components are at; Reduced Protection; surge components such as open fuse links.; Sonic Alarm; matically reset itself after repair.; Table 4; Monitoring Features
8 Operation 4.0 O PERATION Figure 4 Operation controls and indicators Status LED Indicators —Green and red LEDs for each protected phase provide a visual status summary of all surge modules within device. Full Protection LEDs —Green LEDs are illuminated only when all surge components are at 100% per...
Page 13 - Operation 9; Form C Dry Contacts; result from utility switching, line regulation problems, etc.; Remote Monitor Panel
Operation 9 Form C Dry Contacts —Dual summary alarm Form C (1 N.O. and 1 N.C.) relay contacts are provided for remote indication of each failed surge current modules. The summary alarm contacts terminals are located on the PC board inside the unit. Contacts are rated for 5 amps at 240 VAC with a pow...
Page 14 - 0 Troubleshooting, Service & Maintenance; ROUBLESHOOTING; Troubleshooting; the factory, having available the following information:; Service; tion; Preventive Maintenance—Inspection and Cleaning; LOCK OUT ALL POWER SOURCES TO THE UNIT BEFORE
10 Troubleshooting, Service & Maintenance 5.0 T ROUBLESHOOTING , S ERVICE & M AINTENANCE 5.1 Troubleshooting If status failure indication occurs or Form C relay has changed states, a qualified electrician should first determine if the systems voltage and proper phasing exists.If the Intercep...
Page 15 - Limited Warranty 11; IMITED; Warranty Extends to First Purchaser for Use, Non-transferable:
Limited Warranty 11 6.0 L IMITED W ARRANTY This Warranty is given ONLY to purchasers who buy for commercial or industrial use in the ordi- nary course of each purchaser's business. General: Liebert’s products are in our opinion the finest available. We take pride in our products and are pleased that...
Page 16 - 2 Limited Warranty; Items Not Covered By Warranty:; EXTEND THE ORIGINAL WARRANTY PERIOD.
12 Limited Warranty Items Not Covered By Warranty: THIS WARRANTY DOES NOT COVER DAMAGE OR DEFECT CAUSED BY misuse, improper application, wrong or inadequate electrical current or connection, inadequate water or drain ser- vices, negligence, inappropriate on site operating conditions, corrosive atmos...
Page 17 - The Company Behind the Products; and protection systems for sensitive electronics:; Via Leonardo Da Vinci 8; Liebert Asia
Revised: April 2001 Interceptor Transient Voltage Surge Suppressor The Company Behind the Products With more than 1,000,000 installations around the globe, Liebert is the world leader in computer protection systems. Since its founding in 1965, Liebert has developed a complete range of support and pr...