Page 3 - Surge Suppression Systems; LIEBERT SURGE PROTECTIVE DEVICE; Items Not Covered By Warranty:
Surge Suppression Systems Installation, Operation and Maintenance Manual 1 Liebert TVSS Units SL-22085 Rev 2, 11/2006 LIEBERT SURGE PROTECTIVE DEVICE INSTALLATION, OPERATION AND MAINTENANCE MANUAL TABLE OF CONTENTS UNPACKING AND INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ...
Page 4 - INSTALLATION INSTRUCTIONS; Limited Warranty
Installation, Operation and Maintenance Manual 2 Liebert TVSS Units SL-22085 Rev 2, 11/2006 Surge Suppression Systems INSTALLATION INSTRUCTIONS The Liebert Surge Protective Devices (SPDs) are high quality, high energy surge current diversion systems designed to protect sensitive equipment from damag...
Page 5 - ELECTRICAL CONNECTIONS
All electrical connections should be installed by a qualifi ed (licensed) electrician only. All wiring must comply with the National Electrical Code (NEC) and applicable local codes. VERIFY THAT ALL POWER CIRCUITS ARE DE-ENERGIZED AND LOCKED OUT BEFORE MAKING ELECTRICAL CONNECTIONS. Voltage Ratings a...
Page 6 - Source Confi gurations; VOLTAGE RATINGS AND POWER SOURCE CONFIGURATIONS; LIEBERT PRODUCTS COVERED:
Source Confi gurations Installation, Operation and Maintenance Manual 4 Liebert TVSS Units SL-22085 Rev 2, 11/2006 Surge Suppression Systems VOLTAGE RATINGS AND POWER SOURCE CONFIGURATIONS Nominal Operating Voltage L-N L-G L-L 100 100 N/A 110 110 N/A 120 120 N/A 230 230 N/A 277 277 N/A Maximum Contin...
Page 7 - Typical Parallel Connections (with Internal Rotary Disconnect)
Surge Suppression Systems Installation, Operation and Maintenance Manual 5 Liebert TVSS Units SL-22085 Rev 2, 11/2006 Typical Parallel Connections (without Internal Rotary Disconnect) Typical Parallel Connections (with Internal Rotary Disconnect) To Protected Loads Liebert Surge Protective Device Pr...
Page 8 - Example Installations
System Grounding and Bonding The performance and safety of any SPD system is dependent on proper grounding and bonding. Grounding is required for safety. Correct implementation also enhances equipment performance. Incorrect grounding can reduce or impede the SPD’s operation. All electrical circuits ...
Page 9 - Troubleshooting / Servicing / Maintenance; Troubleshooting; PanelGuard Series — Type LPGE
Surge Suppression Systems Installation, Operation and Maintenance Manual 7 Liebert TVSS Units SL-22085 Rev 2, 11/2006 Troubleshooting / Servicing / Maintenance Troubleshooting If status failure indication occurs or Form C relay has changed states, a qualifi ed electrician shall fi rst determine if the...
Page 10 - Typical Parallel Installations; PowerSure Low Exposure Series - Type LPL; Status; Unit is equipped with Summary
Type LPM Type ACV & AII Type LPL Installation Instructions PowerSure Medium Exposure Series AccuVar Series PowerSure Low Exposure Series 1. Insure that all power is removed before beginning installation. A qualifi ed licensed electrician shall install all electrical connections. 2. The SPD is pro...
Page 11 - and a Neutral connection is not available, please contact factory.; Surge Voltage Ratings.; TVSS; Allowable Range; PowerSure Medium Exposure Series — Type LPM 100-2; PowerSure Medium Exposure Series — Type LPM 160
Surge Suppression Systems Installation, Operation and Maintenance Manual 9 Liebert TVSS Units SL-22085 Rev 2, 11/2006 7. An external circuit breaker is not necessary for over-current protection for most units (LPL Units require a 30A or less circuit breaker). However, it is recommended that the SPD ...
Page 12 - Liebert Active Tracking Filter Series — Type F; load amps or overcurrent protection (Circuit Breaker) rating.; Type LM Series; LM Series
Installation, Operation and Maintenance Manual 10 Liebert TVSS Units SL-22085 Rev 2, 11/2006 Surge Suppression Systems Liebert Active Tracking Filter Series — Type F Surge Protective Device (SPD) Installation Instructions 1. Ampacity: The fi lter’s maximum continuous current (Ampere) rating must be g...
Page 13 - Typical Series Connections for Delta (3 Wire + Ground) System; TERMINAL WIRE SIZE RANGE; Single lug with single connection for Input and Output.; Type SS Series
Surge Suppression Systems Installation, Operation and Maintenance Manual 11 Liebert TVSS Units SL-22085 Rev 2, 11/2006 Typical Series Connections for Delta (3 Wire + Ground) System N G Phase (s) Neutral Neutral Phase (s) INPUT OUTPUT Transient Ground Safety Ground Liebert Active Tracking Filter Syst...
Page 14 - Liebert PanelGuard Series - Type LPGE; Installation Instructions; connections; Active Tracking Filter Series - Type F; Typical Cabinet Data (30 to 400Amps)
Installation, Operation and Maintenance Manual 12 Liebert TVSS Units SL-22085 Rev 2, 11/2006 Surge Suppression Systems Liebert PanelGuard Series - Type LPGE Surge Protective Device (SPD) Installation Instructions 1. Insure that all power is removed before beginning installation. A qualifi ed licensed...
Page 15 - conductors comply with all of the following:; Liebert AccuGuide Series — Type ACG; AccuVar Series; Hybrid Advantage Series — Type H; Audible Alarm — AccuVar Series
Surge Suppression Systems Installation, Operation and Maintenance Manual 13 Liebert TVSS Units SL-22085 Rev 2, 11/2006 Installation Instructions All electrical connections shall be installed by a qualifi ed (licensed) electrician. All wiring must comply with the National Electrical Code (NEC) and app...
Page 16 - All Units - No Disconnect; Dimensional Information; Interceptor II, Type SI
Installation, Operation and Maintenance Manual 14 Liebert TVSS Units SL-22085 Rev 2, 11/2006 Surge Suppression Systems Connection The AccuGuide assembly is provided in standard lengths of 5, 8, 10, 12, 15, and 20 feet. Each end of the assembly will include an additional fi ve feet of #10, 8, 6, or 4 ...
Page 31 - Emerson Network Power.; The global leader in enabling Business-Critical Continuity; Emerson Network Power.com; Surge Protection; Liebert Corporation; Technical Support
Interceptor II, SAD Hybrid Advantage, Type SS, LM, AccuVar, PowerSure LPM/LPL Series, ATF Series, PanelGuard Extension, AccuGuide Products Installation, Operation and Maintenance Manual Surge Protection For Business-Critical Continuity ™ Emerson Network Power. The global leader in enabling Business-...