The following WARNING applies to all battery cabinets suppliedwith UPS systems: INTERNAL BATTERY STRAPPING MUST BE VERIFIED BY MANU-FACTURER PRIOR TO MOVING A BATTERY CABINET. Battery cabinets contain non-spillable batteries. Keep units upright. Do not stack. Do not tilt. Failure to heed this warnin...
i Table of Contents 1.0 Safety Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 2.0 Installation Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42.1 Types of...
iii List of Figures Figure 1 Multi-Module UPS, 65 & 80 kVA (left) and bottom-entry 100-225 kVA (right) . . . . . . . . . . . . 5 Figure 2 UPS Multi-Module Unit Block Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 Figure 3 Preferred Grounding Confi...
1 I MPORTANT S AFETY I NSTRUCTIONS Save These Instructions. This manual contains important instructions that should be followed during installation of your Series 600T UPS and batteries. ! WARNING EXERCISE EXTREME CARE WHEN HANDLING UPS CABINETS TO AVOID EQUIPMENT DAMAGE OR INJURY TO PERSONNEL. THE ...
2 If you require assistance for any reason, call the toll-free Liebert Global Services number; 1-800- 543-2378. For LGS to assist you expediently, please have the following information available: ! WARNING LOCATE CENTER OF GRAVITY SYMBOLS AND DETERMINE UNIT WEIGHT BEFORE HANDLING CABINET. Part Numbe...
Safety Precautions 3 1.0 S AFETY P RECAUTIONS Read this manual thoroughly, paying special attention to the sections that apply to you, before working with the UPS. Retain this manual for use by installing personnel. Under typical operation and with all UPS doors closed, only normal safety precaution...
4 Installation Considerations 2.0 I NSTALLATION C ONSIDERATIONS Install your Series 600T UPS in accordance with the submittal drawing package and the following procedures. A Liebert authorized representative must perform the initial system check-out and start-up to ensure proper system operation. Eq...
Installation Considerations 5 Figure 1 Multi-Module UPS, 65 & 80 kVA (left) and bottom-entry 100-225 kVA (right) ! WARNING LOCATE CENTER OF GRAVITY SYMBOLS AND DETERMINE UNIT WEIGHT BEFORE HANDLING CABINET.
6 Installation Considerations Figure 2 UPS Multi-Module Unit Block Diagram 2.1 Types of System Control Cabinets 1. SCCT is a stand-alone cabinet containing system control logic for up to six UPS modules, static bypass switch, manually operated disconnects for the static bypass switch, and two motor-...
Unloading and Handling 7 3.0 U NLOADING AND H ANDLING The UPS module is shipped in one cabinet to allow easy handling at the site. Because the weight distribution in the cabinet is uneven, use extreme care during handling and transport. Your instal- lation may also include Battery Cabinets and a Sys...
8 Inspections 4.0 I NSPECTIONS 4.1 External Inspections 1. While the UPS system is still on the truck, inspect the equipment and shipping container(s) for any signs of damage or mishandling. Do not attempt to install the system if damage is apparent. If any damage is noted, file a damage claim with ...
Equipment Location 9 5.0 E QUIPMENT L OCATION 1. Handle cabinet(s) in accordance with the safety precautions in Section 1.0 . Use a suitable material handling device to move cabinet to its final location. Exercise extreme care because of the uneven weight distribution. Carefully lower the cabinet to...
10 Battery Installation 6.0 B ATTERY I NSTALLATION 6.1 Battery Safety Precautions Servicing of batteries should be performed or supervised by personnel knowledgeable of batteries and the required precautions. Keep unauthorized personnel away from batteries. When replacing batteries, use the same num...
Battery Installation 11 Battery Safety Precautions in French Per CSA Requirements Instructions Importantes Concernant La Sécurité Conserver Ces Instructions ! ADVERTISSEMENT DES PIECES SOUS ALIMENTATION SERONT LAISSEES SANS PROTECTION DURANT CES PROCEDURES D’ENTRETIEN. UN PERSONNEL QUALIFIE EST REQU...
Battery Installation 13 6.2 Matching Battery Cabinets Two sizes of optional battery cabinets are available. Refer to Figure 18 to Figure 22. The battery cabinet cells range from 90 to 150 Ampere-hours. The same model battery cabinet may be paral- leled in multiple cabinet strings for additional capa...
14 Configuring Your Neutral and Ground Connections 7.0 C ONFIGURING Y OUR N EUTRAL AND G ROUND C ONNECTIONS Improper grounding is the largest single cause of UPS installation and start-up problems. This is not an easy subject, since grounding techniques vary significantly from site to site, dependin...
Configuring Your Neutral and Ground Connections 15 7.1 Preferred Grounding Configuration, 480 or 600 VAC Input and Output, IsolatedPower Distribution Units, Wye-Connected Service Figure 3 Preferred Grounding Configuration, 480 or 600 VAC Input and Output The most-common configuration of Series 600T ...
16 Configuring Your Neutral and Ground Connections 7.2 Grounding Configuration, 480 or 600 VAC Input and Output, Delta Source Figure 4 Grounding Configuration with Ungrounded Delta Source Input As previously mentioned, Series 600T UPS systems require a bypass input neutral for sensing and monitoring...
Configuring Your Neutral and Ground Connections 17 7.3 Preferred Grounding Configuration with Power-Tie Switchgear Figure 5 Preferred Grounding Configuration, Power-Tie Systems Multi-Module Systems can be used with Power-Tie switchgear to provide dual critical load busses. The Power-Tie switchgear p...
18 Configuring Your Neutral and Ground Connections 7.4 Grounding Configurations, Battery Systems Figure 6 Battery Cabinet Grounding Configuration Large, open-rack battery systems are normally either locally grounded or left ungrounded, depend- ing on local code requirements. Battery cabinet systems,...
Wiring Considerations 19 8.0 W IRING C ONSIDERATIONS Refer to Appendix A - Site Planning Data and installation drawings (Figure 8 through Figure 55). Determine AC currents for your system (kVA, voltage, and options). Also refer to equipment nameplate for the model number, rating, and voltage. Refer ...
20 Wiring Considerations 8.1 Power Wiring 1. Power wiring must be run in individual, separate conduits or cable trays. Refer to the Outline and Terminal Details drawings ( Figure 8 to Figure 22 and Figure 28 to Figure 32 ) for locations of the various power connections within the UPS and SCC. In par...
Wiring Considerations 21 8.2 Control Wiring Control wiring must be stranded and tinned and run in individual separate steel conduits. Control wiring must be separated from power wiring. In addition, each control wiring cable group should be run in a separate conduit to minimize control signal interf...
22 Wiring Considerations 8.3 Battery Wiring Power wiring to the Battery Cabinet connects positive, negative, and ground power cables from the Battery Cabinet to the associated UPS. Connection of the UPS to the Battery Cabinet serves to both charge and discharge the batteries (when needed). The batte...
Wiring Considerations 23 Figure 7 Typical Multi-Module Configurations I R CB2 Output SBB I R I R CB2 CB2 #2 UPS CB1 #1 UPS CB1 #3 UPS CB1 RIB RIB BIB RIB SCCI SCCI / SCCC (can accomodate up to 6 UPS modules) Battery MBD Battery MBD Battery MBD MIB To Critical Load SBB SBS MBB System Controls I R #2 ...
24 Wiring Connections 9.0 W IRING C ONNECTIONS Refer to the drawings in this manual and any other drawings provided by Liebert for this installa- tion. Make all of the following connections: 1. AC power cables from input power source circuit breaker (RIB) to UPS Module Input. Observe phase rotation....
26 Wiring Inspection 10.0 W IRING I NSPECTION 1. Verify all power connections are tight. 2. Verify all control wire terminations are tight. 3. Verify all power wires and connections have proper spacing between exposed surfaces, phase-to- phase and phase-to-ground. 4. Verify that all control wires ar...
76 Appendix A - Site Planning Data 12.0 A PPENDIX A - S ITE P LANNING D ATA 65-225 kVA Multi-Module Systems 12.1 Notes 1. Nominal rectifier AC input current (considered continuous) is based on full rated output load. Maximum current includes nominal input current and maximum battery recharge current...
Appendix A - Site Planning Data 77 30% maximum input harmonic current and 0.85 lagging input power factor at full load without optional input filter. 14. Dimensions and weights do not include the System Control Cabinet required for Multi-Module Systems. Table 4 Series 600T Multi-Module Systems, 65-2...
The Company Behind the Products With over a million installations around the globe,Liebert is the world leader in computer protectionsystems. Since its founding in 1965, Liebert hasdeveloped a complete range of support andprotection systems for sensitive electronics: • Environmental systems—close-co...
Liebert Manuals
-
Liebert UD600
Manual
-
Liebert 277
Manual
-
Liebert PS400-60S
Manual
-
Liebert F277Y800-03
Manual
-
Liebert Series 600
Manual
-
Liebert XDC
Manual
-
Liebert Type SS
Manual
-
Liebert 2U
Manual
-
Liebert NX UPS System
Manual
-
Liebert 1500
Manual
-
Liebert UD2000
Manual
-
Liebert NET1080T
Manual
-
Liebert 3000
Manual
-
Liebert UD1400
Manual
-
Liebert GXT96VLRT2UL
Manual
-
Liebert SERIES 600T
Manual
-
Liebert 700-2200 VA
Manual
-
Liebert UD600R
Manual
-
Liebert HiSwitch2
Manual
-
Liebert 100
Manual