Page 3 - Installation Instructions
Installation Instructions OUZXMAG,0002081 –19–03AUG05–1/1 Contents of Bundle BZ13788 ZX1037465 –UN–13SEP05 A—Z73362 Plate (1x) D—AZ59199 Job computer (1x) G—AZ101120 Wiring harness J—PF80209 Bracket (1x) B—Z72204 Plate (1x) E—H204964 Decal (1x) (1x) K—AZ71569 Connector (1x) C—AZ57754 Holder (1x) F—N...
Page 6 - Parts to Order
Installation Instructions OUCC002,00021C9 –19–04AUG06–1/1 Parts to Order ZX1039591 B A C ZX1039591 –UN–12JUL06 A—BZ100165 NIR Sensor (1x) B—AZ101740 Wear Plate for C—Z101953 Wear Plate for Flat High arc Spout (1x) Spout (1x) To complete the bundle BZ100157 installation theparts or bundles above illu...
Page 7 - Maintain Stability; Care should also be observed while servicing the sensor.
Installation Instructions OUCC002,0002373 –19–06SEP06–1/1 Mount and Dismount Safely With theMoisture Sensor ZX1039921 –UN–06SEP06 Hold handrail with one hand and carry the moisturesensor with the other. OUCC002,0002374 –19–06SEP06–1/1 Maintain Stability ZX1039668 ZX1039668 –UN–29AUG06 Keep work surf...
Page 8 - Modify High Arc Spout; On both sides of the spout, release the side wear plate; IMPORTANT: Grind spout sides at locations where
Installation Instructions OUCC002,000233C –19–12OCT06–1/2 Modify High Arc Spout ZX1039636 –UN–12JUL06 ZX1039637 –UN–12JUL06 ZX1039638 –UN–12JUL06 ZX1039639 –UN–12JUL06 ZX1039640 –UN–12JUL06 A—Fixing ScrewsB—Fixing ScrewsC—Template Z103666D—Area to CutE—Drilling HolesF—Brackets Z103667 On machines wi...
Page 10 - Replace Spout Wear Plate
Installation Instructions OUCC002,00021CE –19–12OCT06–1/1 Replace Spout Wear Plate ZX1039595 A B ZX1039595 –UN–10APR06 ZX1039594 C ZX1039594 –UN–10APR06 A—Wear plate—AZ101740—High arc spoutB—Wear plate—Z101953—Flat spoutC—Part to remove Using original hardware, install wear plate AZ101740 (A)on high...
Page 14 - Place sensor into working position but do not latch; IMPORTANT: To allow a proper adapter glass
Installation Instructions OUCC002,00021CD –19–18NOV06–4/4 ZX1039600 F E F E A D C B ZX1039600 –UN–10APR06 A—Adapter glass C—Front point setting E—Flange screw F—Flange nut B—Wear plate D—Rear point setting 7. Place sensor into working position but do not latch it. Adjust sensor assembly position so ...
Page 15 - Install Feed Roll Potentiometer AZ63280; spring to its original setting.
Installation Instructions OUZXMAG,0001BEF –19–13NOV03–1/3 Install Feed Roll Potentiometer AZ63280 ZX1034539 –UN–16NOV03 A—Feed roll springB—Eye-boltC—Plate Z72204D—Holder AZ57754 Install Upper Plate Z72204 and Holder AZ57754 1. Remove right-hand feed roll spring (A) by loosening eye-bolt (B). 2. Ins...
Page 19 - Connect part of wiring harness AZ101120 with
Installation Instructions OUCC002,00021CA –19–18NOV06–2/8 X30 Connector AZ71569 Pin Connections Pin Number Wire Pin #1 .......................................... 584 Pin #2 .......................................... 586 Pin #3 .......................................... 585 Pin #4 ......................
Page 21 - the rear right-hand side of the cab as shown.
Installation Instructions OUCC002,00021CA –19–18NOV06–5/8 IMPORTANT: Route wiring harness AZ101120 (C) alongside machine wiring harnessand secure with tie bands. NOTE: Connector (A) shall be used for inoculant dosing device connection. Connector (B) shall be stored in a safe place ifNIR sensor is no...
Page 23 - Connecting Inoculant Dosing Device; Tx wire; of; GND wire
Installation Instructions OUZXMAG,00020A0 –19–13SEP05–1/1 Connecting Inoculant Dosing Device ZX1037996 –UN–13SEP05 A—Connector for inoculant dosing device To enable the dosing device system, the connector (A)MUST be connected to the relevant connector of inoculantdosing device control unit in the fo...
Page 25 - Attach GreenStar Decals
Installation Instructions OUZXMAG,00020A1 –19–14SEP05–1/1 Attach GreenStar Decals ZX1031229 –UN–02NOV02 ZX1031230 –UN–02NOV02 A—Decal H204964B—Decal N302284C—Display • Attach decal H204964 (A) to left hand side of theharvester as indicated. • Attach decal N302284 (B) as indicated in front of thedisp...
Page 26 - Load Software; Load Display Software
Installation Instructions OUZXMAG,0002083 –19–04AUG05–1/2 Load Software Load Display Software To load new software: 1. Install PC Card containing NEW software in card slot A of mapping processor. 2. Turn ignition key to RUN position. 3. Press “INFO” key to enter INFO mode. 4. Press key B in “INFO” t...
Page 28 - Check Yield Monitoring Functionality; Calibrate Mass-Flow Sensor
Installation Instructions OUZXMAG,0001BF6 –19–18NOV03–1/2 Check Yield Monitoring Functionality Calibrate Mass-Flow Sensor 1. Turn ignition key to RUN position. 2. Press “SETUP” key to enter SETUP mode. 3. Press key C in “SETUP” to select “GreenStar Display”. 4. Select your native language and units ...
Page 29 - Check Inoculant Dosing Functionality; NOTE: For a proper use of the liquid injection pump
Installation Instructions OUZXMAG,0001BF6 –19–18NOV03–2/2 6. Press key C to select “SPFH Network” and check communication between SPFH and Harvest Monitor. 7. Press RUN key. OUZXMAG,0002084 –19–04AUG05–1/1 Check Inoculant Dosing Functionality ZX1035268 –UN–26JUL04 1. Turn ignition key to start harve...