L300P/SJ300 Low Current Trip Function for Pumping Applications Sometimes it is desirable to have the inverter trip when running at constant speed and the motor current falls below a certain threshold level. In the case of a pump, this would be indicative of absence of fluid in the pump, and hence no...

Page 3 - TIMING CHART; Page 3

TIMING CHART Time Output Frequency [FA1] (N.O.) C041 o [OL] (N.C) o [OL] (N.C) n [OL] AND [FA1] n [OL] AND [FA1] o n Motor Current Hitachi America, Ltd. © 2004 Hitachi America, Ltd. Page 3

Page 4 - Page 4

TIMING CHART (continued) p q [FA1] (N.O.) C041 Output Frequency Motor Current p q TRIP [OL] (N.C) q [OL] (N.C) p [OL] AND [FA1] p [OL] AND [FA1] q Hitachi America, Ltd. © 2004 Hitachi America, Ltd. Page 4