Page 2 - PECIFICATIONS
2 SS-PCB50 P RODUCT S PECIFICATIONS S PECIFICATIONS PCB090-5 PCB120-5 PCB180-5 Total Cooling - BTU/h (kW) 88,400 (25.9) 118,600 (34.8) 172,000 (50.4) Sensible Cooling - BTU/h¹ (kW) 67,100 (19.7) 89,200 (26.1) 131,000 (38.4) EER² 8.9 9.7 8.5 Indoor Blower (Qty.) 2 2 2 Type Belt Belt Belt Size - D x W...
Page 3 - UNIT SIZE; IMENSIONS
SS-PCB50 3 P RODUCT S PECIFICATIONS UNIT SIZE A - HEIGHT B - SUPPLY AIR C - RETURN AIR 090 36” (914 mm) 12½” (318 mm) 179/16” (446 mm) 120,180 52” (1321 mm) 20¼” (514 mm) 2513/16” (656 mm) D IMENSIONS All dimensions in inches and millimeters. Drawings are not to scale. Note: The Horizontal Conversio...
Page 4 - LECTRICAL; LECTRIC; Unit Size; HKCB
4 SS-PCB50 P RODUCT S PECIFICATIONS E LECTRICAL C ONNECTIONS Main power entrance location (with electric heat installed)Control wiring entrance locationMain power entrance location (without electric heat installed) Note: Single-point wiring is available at location #1 when heat kit is installed. See...
Page 5 - AN
SS-PCB50 5 P RODUCT S PECIFICATIONS CFM EXTERNAL STATIC PRESSURE (INCHES W.C.) SEE NOTE (3) 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 2600 669 0.44 816 0.59 916 0.75 1004 0.92 1084 1.09 1157 1.28 1226 1.47 1291 1.67 2800 734 0.53 847 0.69 944 0.8...
Page 9 - OOLING; NITS
SS-PCB50 9 P RODUCT S PECIFICATIONS INDOOR AIR CONDENSER AIR TEMPERATURE 23.9°C 29.4°C 35.0°C 40.6°C 46.1°C L/S WB Total Cap. SensCap. Kw Total Cap. SensCap. Kw Total Cap. SensCap. Kw Total Cap. SensCap. Kw Total Cap. SensCap. Kw 2246 22.2 64.17 29.53 16.42 60.17 28.00 18.63 56.17 26.48 20.83 52.17 ...
Page 10 - NGLISH
10 SS-PCB50 P RODUCT S PECIFICATIONS INDOOR AIR CONDENSER AIR TEMPERATURE 75°F 85°F 95°F 105°F 115°F SCFM WB Total Kbtuh Sens Kbtuh Kw Total Kbtuh Sens Kbtuh Kw Total Kbtuh Sens Kbtuh Kw Total Kbtuh Sens Kbtuh Kw Total Kbtuh Sens Kbtuh Kw 4760 72 219.0 100.8 16.42 205.3 95.6 18.63 191.7 90.4 20.83 1...
Page 11 - PPLICATION
SS-PCB50 11 P RODUCT S PECIFICATIONS F ACTORY S UPPLIED A CCESSORIES T HERMOSTAT (CHT90-120) Two-stage cool and two-stage heat thermostat with subbase, Manual changeover, Fan ON or AUTO. Note: A variety of thermostat con fi gurations can be used on this equipment based on the application needs. For ...
Page 12 - UALITY
12 SS-PCB50 P RODUCT S PECIFICATIONS Q UALITY M AKES THE D IFFERENCE ! All of our systems are designed and manufactured with the same high-quality standards, regardless of size or ef fi ciency. We have designed these units to signi fi cantly reduce the most frequent causes of product failure. They a...