Page 2 - application & engineering data; ENGINE SPECIFICATIONS: 80 kW; Standby Generators

2 of 9 70 • 80 • 100 • 130 • 150 kW application & engineering data GENERATOR SPECIFICATIONS Type Synchronous Rotor Insulation Class H Stator Insulation Class H Telephone Interference Factor (TIF) <50 Alternator Output Leads 1-Phase 4 wire Alternator Output Leads 3-Phase 6 wire (70, 80 & 1...

Page 3 - operating data; SURGE CAPACITY IN AMPS; ENGINE FUEL CONSUMPTION

3 of 9 70 • 80 • 100 • 130 • 150 kW operating data GENERATOR OUTPUT VOLTAGE/kW - 60Hz kW LPG Amp LPG kW Nat. Gas Amp Nat. Gas CB Size (Both) QT070 120/240 V, 1Ø, 1.0 pf 67 292 64 267 300 120/208 V, 3Ø, 0.8 pf 70 243 67 232 300 120/240 V, 3Ø, 0.8 pf 70 211 67 201 250 277/480 V, 3Ø, 0.8 pf 70 105 67 1...

Page 5 - available accessories; Product

5 of 9 70 • 80 • 100 • 130 • 150 kW available accessories Standby Generators Model # Product Description 005632-0 - 70, 80 & 150 kW005633-0 - 100 & 130 kW Cold Weather Kit If the temperature regularly falls below 32 °F (0 °C), install a cold weather kit to maintain optimal battery temperatur...