Page 2 - APPLICATION & ENGINEERING DATA; COMMERCIAL 30 kW

APPLICATION & ENGINEERING DATA Rating definitions - Standby: Applicable for supplying emergency power for the duration of the utility power outage. No overload capability is available for this rating. (All ratings in accordance with BS5514, ISO3046 and DIN6271). (All ratings in accordance with B...

Page 3 - OPERATING DATA

COMMERCIAL 30 kW KW RATING 30 LP / 29 NG ENGINE SIZE 1.6 Liter 4 cyl. inline GENERATOR OUTPUT VOLTAGE/KW - 60Hz KW AMP CB Size 120/208V, three phase, 0.8 pf 30 LP / 29 NG 104.2 LP / 100.7 NG 125 120/240V, three phase, 0.8 pf 30 LP / 29 NG 90.3 LP / 87.3 NG 100 277/480V, three phase, 0.8 pf 30 LP / 2...

Page 4 - INTERCONNECTIONS; GENERAC

COMMERCIAL 30 kW © 2007 Generac Power Systems, Inc. All rights reserved. All specifications are subject to change without notice. Bulletin 0174550SBY / Printed in USA 05.07 INTERCONNECTIONS INSTALLATION LAYOUT 30 240 1 ø 150 #1 to 300 mcm 30 208 3 ø 125 #2 to 1/0 30 240 3 ø 100 #4 to 1/0 30 480 3 ø ...