Generac 18 kW NG - Manuals
Generac 18 kW NG – Manual in PDF format online.
Manuals:
Manual Generac 18 kW NG
Summary
ElEctrical formulas TO FIND KNOWN VALUES 1-PHASE 3-PHASE KILOWATTS (kW) Volts, Current, Power Factor E x I 1000 E x I x 1.73 x PF 1000 KVA Volts, Current E x I 1000 E x I x 1.73 1000 AMPERES kW, Volts, Power Factor kW x 1000 E kW x 1000 E x 1.73 x PF WATTS Volts, Amps, Power Factor Volts x Amps E x ...
Page 1 contents specifications .......................................................... 4 Generator ................................................................ 4 Engine ..................................................................... 5 Fuel Consumption ......................................
Page 4 Generator Unit 8 kW 10 kW 12 kW 14 kW 16 kW 17 kW 20 kW Rated Max. Continuous Power Capacity (Watts*) 7,000 NG 8,000 LP 9,000 NG 10,000 LP 12,000 NG 12,000 LP 13,000 NG 14,000 LP 16,000 NG 16,000 LP 16,000 NG 17,000 LP 18,000 NG 20,000 LP Rated Voltage 120/240 Rated Voltage at No-Load (NG) 22...
SpecificationS Page 5 Fuel Consumption Model # Natural Gas* LP Vapor** 1/2 Load Full Load 1/2 Load Full Load 7/8 kW 77 140 0.94/34 1.68/62 9/10 kW 102 156 1.25/46 1.93/70 12/12 kW 152 215 1.53/56 2.08/76 13/14 kW 156 220 1.56/58 2.30/84 16/16 kW 183 261 1.59/58 2.51/91 16/17 kW 183 261 1.61/59 2.57/...
Page 6 sPEcificatioNs mountinG dimenSionS AIR INTAKE AIR OUTLET FRONT OF UNIT HOLE LOCATIONS FOROPTIONAL MOUNTING TOA CONCRETE PAD MINIMUM DISTANCE AIR INTAKE FRONT VIEW LEFT SIDE VIEW RIGHT SIDE VIEW REAR VIEW "DO NOT LIFT BY ROOF" GROUNDING LUG Ø30.2 [Ø1.2] LIFTING HOLES 4 CORNERS CABLE AC...
sPEcificatioNs Page 8 major FeatureS Data Label (see sample) Oil Dipstick Exhaust Enclosure Composite Base Oil Filter Battery Compartment Fuel Regulator Fuel Inlet (back) Air Filter Circuit Breaker Control Panel Data Label (see sample) Oil Dipstick Exhaust Enclosure Composite Base Oil Filter Battery...
Part 1 GENEral iNformatioN air-cooled, automatic standby Generators Page 9 taBlE of coNtENts Part titlE PaGE 1.1 Generator identification 10 1.2 installation Basics 11 1.3 Non-Prepackaged interconnections 14 1.3 Preparation Before use 16 1.4 testing, cleaning and Drying 18 1.5 Engine-Generator Prote...
introduction This Diagnostic Repair Manual has been prepared especially for the purpose of familiarizing service per-sonnel with the testing, troubleshooting and repair of air-cooled, automatic standby generators. Every effort has been expended to ensure that information and instructions in the manu...
Page 11 GENERAL INFORMATION sEctioN 1.2 iNstallatioN Basics introduction Infor mation in this section is provided so that the ser vice technician will have a basic knowledge of installation requirements for home standby systems. Problems that arise are often related to poor or unau-thorized installa...
Part 1 Page 12 GENERAL INFORMATION sEctioN 1.2 iNstallatioN Basics Figure 1. Typical Installation
GENERAL INFORMATION sEctioN 1.2 iNstallatioN Basics poWer Source and load lineS The utility power supply lines, the standby (genera-tor) supply lines, and electrical load lines must all be connected to the proper terminal lugs in the transfer switch. The following rules apply: In 1-phase systems wit...
Page 14 Part 1 General information Section 1.3 non-PrePackaged interconnectionS Discussion:on the current model air-cooled generators Wire 194 was changed to 15B. Wire 15B is still utilized for posi-tive voltage for the transfer relay and Wire 23 is still the control ground for transferring the gene...
GENERAL INFORMATION sEctioN 1.3 NoN-PrEPacKaGED iNtErcoNNEctioNs Part 1 connect a 2008 and later load center SWitch to a pre-2008 air-cooled Generator. PROCEDURE: 1. Follow all instructions located in the Installation Manual that was supplied with the unit regarding mounting of the switch, junction ...
General The installer must ensure that the home standby gen-erator has been properly installed. The system must be inspected carefully following installation. All appli-cable codes, standards and regulations pertaining to such installations must be strictly complied with. In addition, regulations es...
GENERAL INFORMATION sEctioN 1.4 PrEParatioN BEforE usE in the selector knob and pull out to overcome spring pressure and then twist clockwise 90 degrees and allow the selector to return in once aligned with the LP (Liquid Propane) position. 6. Save this tool with the Owner's Manual.7. Install the ba...
FUEL SELECTION LEVER - “OUT” POSITION FOR LIQUID PROPANE (VAPOR) FUEL Figure 5. 12/14/16/17/20 kW, GT-990/GT-999 (Airbox Cover Removed) enGine oil recommendationS All oil should meet minimum American Petroleum Institute (API) Ser vice Class SJ, SL or better. Use no special additives. Select the oil'...
Page 19 GENERAL INFORMATION sEctioN 1.5 tEstiNG, clEaNiNG aND DrYiNG meterS Devices used to measure electrical proper ties are called meters. Meters are available that allow one to measure (a) AC voltage, (b) DC voltage, (c) AC frequency, and (d) resistance In ohms. The following apply: • To measure...
Part 1 meaSurinG current CLAMP-ON:To read the current flow, in AMPERES, a clamp-on ammeter may be used. This type of meter indicates current flow through a conductor by measuring the strength of the magnetic field around that conductor. The meter consists essentially of a current trans-former with a...
GENERAL INFORMATION sEctioN 1.5 tEstiNG, clEaNiNG aND DrYiNG Component testing may require a specific resis-tance value or a test for INFINITY or CONTINUITY. Infinity is an OPEN condition between two electrical points, which would read as no resistance on a VOM. Continuity is a closed condition betw...
Part 1 ViSual inSpection When it becomes necessary to test or troubleshoot a generator, it is a good practice to complete a thorough visual inspection. Remove the access covers and look closely for any obvious problems. Look for the following: • Burned or broken wires, broken wire connectors, damage...
GENERAL INFORMATION sEctioN 1.5 tEstiNG, clEaNiNG aND DrYiNG Part 1 HI-POT TESTER:A “Hi-Pot” tester is shown in Figure 7. The model shown is only one of many that are commercially available. The tester shown is equipped with a voltage selector switch that permits the power supply voltage to be selec...
Part 1 GENERAL INFORMATION sEctioN 1.5 tEstiNG, clEaNiNG aND DrYiNG TESTING ALL STATOR WINDINGS TO GROUND: 1. Disconnect Stator Output Leads 11 and 44 from the generator main line circuit breaker. 2. Disconnect Stator Output Leads 2 and 6 from the capacitor located on the end of the stator assembly....
GENERAL INFORMATION sEctioN 1.6 ENGiNE-GENErator ProtEctiVE DEVicEs General Standby electr ic power generators will often r un unattended for long periods of time. Such operating parameters as (a) battery voltage, (b) engine oil pres-sure, (c) engine temperature, (d) engine operating speed, and (e) ...
Part 1 oVercrank ShutdoWn This feature prevents the generator from damaging itself when it continually attempts to start and another problem, such as no fuel supply, prevents it from start-ing. The unit will crank and rest for a preset time limit. Then, it will stop cranking, and the LCD screen or t...
GENERAL INFORMATION sEctioN 1.7 oPEratiNG iNstructioNs Part 1 Page 27 control panel SET EXERCISE SYSTEM READY LOW BATTERY LOW OIL PRESSURE HIGH OIL TEMPERATURE OVERSPEED RPM SENSOR LOSS OVERCRANK ENTER ECS 8 kW UNITS 10-20 kW UNITS Figure 1. Generator Control Panel AUTO-OFF-MANUAL SWITCH:Use this sw...
Part 1 Page 28 GENERAL INFORMATION sEctioN 1.7 oPEratiNG iNstructioNs 10-20 kW – INSTALLATION ASSISTANT:Upon first power up of the generator, the display inter-face will begin an installation assistant. The assistant will prompt the user to set the minimum settings to operate. These settings are sim...
GENERAL INFORMATION sEctioN 1.8 automatic oPEratiNG ParamEtErs Part 1 Page 29 introduction When the generator is installed in conjunction with a transfer switch, either manual or automatic opera-tion is possible. Manual transfer and engine startup, as well as manual shutdown and re-transfer are cove...
Part 1 GENERAL INFORMATION sEctioN 1.8 automatic oPEratiNG ParamEtErs Page 30 load tranSFer The transfer of load when the generator is running is dependent upon the operating mode as follows: 1. Manual • Will not transfer to generator if utility is present.• Will transfer to generator if utility fai...
Page 31 air-cooled, automatic standby Generators Part 2 ac GENErators taBlE of coNtENts Part titlE PaGE# 2.1. Description and components 30 2.2 operational analysis 33 2.3 troubleshooting flow charts 35 2.4 Diagnostic tests 39 2.1 Description and Components .......................... 32 Introduction...
"C" "B" "C" ROTOR "B" "C" 9 "D" "B" "C" "D" BEARING CARRIER BRUSH HOLDERASSEMBLY ENGINE ADAPTOR "8KW" "8KW - 10KW" ENGINE ADAPTOR "10KW" 0.8 "D" "D" STATOR "12KW - 20KW" "12KW ...
AC GENERATORS sEctioN 2.1 DEscriPtioN & comPoNENts Part 2 Page 33 SLIP RINGS BEARING Figure 2. The 2-Pole Rotor Assembly 12-20 kW 8/10kW:Like the 12-20 kW rotor, the 8/10 kW 2-pole rotor must be operated at 3600 rpm to supply a 60 Hertz AC fre-quency. However, the 8/10kW rotor uses no slip rings...
BruSh holder and BruSheS (12-20 kW) The brush holder is retained to the rear bearing car-rier by means of two #10-32 x 9/16 Taptite screws. A positive (+) and a negative (-) brush are retained in the brush holder, with the positive (+) brush riding on the slip ring nearest the rotor bearing.Wire 4 c...
Page 35 AC GENERATORS sEctioN 2.2 oPEratioNal aNalYsis rotor reSidual maGnetiSm The generator revolving field (rotor) may be consid-ered to be a per manent magnet. Some “residual” magnetism is always present in the rotor. This residual magnetism is sufficient to induce a voltage into the stator AC p...
AC GENERATORS sEctioN 2.3 trouBlEsHootiNG floWcHarts Use the “Flow Charts” in conjunction with the detailed instr uctions in Section 2.4. Test numbers used in the flow charts correspond to the numbered tests in Section 2.4. The first step in using the flow charts is to correctly identify the problem...
AC GENERATORS sEctioN 2.3 trouBlEsHootiNG floWcHarts Part 2 Page 39 STOP TESTS FREQUENCY O.K., BUT VOLTAGE LOW TEST 14 - CHECK AC OUTPUT FREQUENCY TEST 15 - ADJUST ENGINE GOVERNOR TEST 16 - CHECK STEPPER MOTOR CONTROL TEST 2 - CHECK AC OUTPUT VOLTAGE TEST 17 - ADJUST VOLTAGE REGULATOR TEST 9 - CHECK...
AC GENERATORS sEctioN 2.4 DiaGNostic tEsts introduction This section is provided to familiarize the ser vice technician with acceptable procedures for the test-ing and evaluation of various problems that could be encountered on standby generators with air-cooled engine. Use this section of the manua...
* DaNGEr: usE EXtrEmE cautioN DuriNG tHis tEst. tHE GENErator Will BE ruNNiNG. HiGH aND DaNGErous VoltaGEs Will BE PrEsENt at tHE tEst tErmiNals. coNNEct mEtEr tEst clamPs to tHE HiGH VoltaGE tErmiNals WHilE tHE GENErator is sHut DoWN. staY clEar of PoWEr tErmiNals DuriNG tHE tEst. maKE surE mEtEr c...
AC GENERATORS sEctioN 2.4 DiaGNostic tEsts Connect the other meter test lead to Wire 4 (still dis- connected from previous tests). Measure and record static rotor amp draw. 13. Set the AUTO-OFF-MANUAL switch to the MANUAL position. Once the engine star ts, repeat Step 12. Measure and record running ...
teSt 6 – check Field BooSt (12-20 kW) DISCUSSION:See “Field Boost Circuit” in Section 2.2. Field boost current (from the circuit board) is available to the rotor only while the engine is cranking. Loss of field boost output to the rotor may or may not affect power winding AC output voltage. The foll...
AC GENERATORS sEctioN 2.4 DiaGNostic tEsts 5. Turn the Main Breaker to the "ON" or CLOSED position. 6. Set a VOM to measure resistance. 7. Connect one meter test lead to Wire 11 on the load side of the main breaker. Connect the other meter test lead to Wire 22 (power winding). Note the resis...
• An open circuit condition• A “short-to-ground” condition• A short circuit between windings note: the resistance of stator windings is very low. Some meters will not read such a low resistance, and will simply indicate continuity. recommended is a high quality, digital type meter capable of read-in...
AC GENERATORS sEctioN 2.4 DiaGNostic tEsts PROCEDURE: 1. Consult the owner’s manual of the meter being used for directions on measuring capacitance. Figure 7 shows a typical meter and how to check capacitance. 2. Connect the meter leads directly across the terminals of the capacitor. The rated µf (m...
2. Testing for a “grounded” condition: Any resistance reading indicated the winding is grounded. 3. Testing for a “shorted” condition: Any resistance reading indicated the winding is shorted. 4. If stator tests good and wire continuity tests good, refer back to flow chart. teSt 11 – reSiStance check...
AC GENERATORS sEctioN 2.4 DiaGNostic tEsts RESULTS: 1. Repair, replace or reconnect wires as necessary.2. Replace any damaged slip rings or brush holder.3. Clean and polish slip rings as required. teSt 13 – teSt rotor aSSemBly (12-20 kW) DISCUSSION:A rotor having completely open windings will cause ...
Part 2 GOVERNOR SHAFT PRIMARY ADJUST SCREW GOVERNOR CLAMP BOLT SECONDARY ADJUST SCREW Figure 10. Engine Governor Adjustment Single Cylinder Engines PROCEDURE (8 kW UNITS WITH DUAL GOVERNOR SPRINGS): 1. Loosen the governor clamp bolt (Figure 10).2. Hold the governor lever at its wide open throttle po...
STEPPER MOTOR PULL ARM THIS DIRECTION TO CLOSE THROTTLE Figure 11. Throttle Positions 9/10 kW Units STEPPER MOTOR STEPPER MOTOR ARM PULL ARM THIS DIRECTION TO CLOSE THROTTLE Figure 12. Throttle Positions 9/10 kW Units STEPPER MOTOR STEPPER MOTOR ARM PULL ARM THIS DIRECTION TO CLOSE THROTTLE Figure 1...
teSt 18 – check VoltaGe and Frequency under load DISCUSSION:It is possible for the generator AC output frequency and voltage to be good at no-load, but they may drop excessively when electrical loads are applied. This condition, in which voltage and frequency drop exces-sively when loads are applied...
Page 53 Figure 18. Energizing Cord Connection Figure 17. Construction of Energizing Cord GENERATOR CAPACITOR WIRES 2 & 6 TO DPE WINDING DEPRESS SWITCH FOR ONE SECOND PLUG ENERGIZING CORD INTO AC OUTLET CAPICITOR REMAINS CONNECTED TO GENERATOR Danger: The capacitor may need to be dis- charged b...
TRANSFER SWITCH sEctioN 3.1 DEscriPtioN & comPoNENts Part 3 Page 57 tranSFer mechaniSm The 2-pole transfer mechanism consists of a pair of moveable LOAD contacts, a pair of stationar y UTILITY contacts, and a pair of stationary STANDBY contacts. The load contacts can be connected to the utility ...
c. When de-energized, the relay’s normally open c o n t a c t s a r e o p e n a n d i t s n o r m a l l y - c l o s e d contacts are closed. d. The normally-closed relay contacts will deliver utility source power to the utility closing circuit of the transfer mechanism. e. The normally open relay co...
TRANSFER SWITCH sEctioN 3.1 DEscriPtioN & comPoNENts Part 3 Page 59 TERMINALS 0, 15B AND 23:These ter minals connect the transfer relay to the generator circuit board. See “Transfer Relay” in Section 3.1. FuSe holder The fuse holder holds three (3) fuses, designated as fuses F1, F2 and F3. Each ...
operational analySiS Figure 1 is a schematic for a typical “W/V-Type” transfer switch. Figure 1. Schematic Page 60 NEUTRAL CONNECTION SWITCH SW3 NO C1 COM SW2 VR1 NC NC COM C2 VR2 NO TR1 15B 23 1 7 4 7 9 3 6 9 F2 CIRCUIT 10 BLACK (MAIN 1) CONTROL TRANSFER RED (MAIN 2) NEUTRAL (WHITE) NEUTRAL (WHITE)...
TRANSFER SWITCH sEctioN 3.2 oPEratioNal aNalYsis Part 3 Page 61 Figure 2 is a wiring diagram for a typical “W/V-Type” transfer switch. Figure 2. Wiring Diagram 205 N2A N1A RED BLK 10 CIRCUIT LOAD CENTER 12 CIRCUIT LOAD CENTER 14 CIRCUIT LOAD CENTER CIRCUIT 8 8 CIRCUIT LOAD CENTER CIRCUIT 1 CIRCUIT 3...
NEUTRAL CONNECTION SWITCH SW3 NO C1 COM SW2 VR1 NC NC COM C2 VR2 NO TR1 15B 23 1 7 4 7 9 3 6 9 F2 CIRCUIT 10 BLACK (MAIN 1) CONTROL TRANSFER RED (MAIN 2) NEUTRAL (WHITE) NEUTRAL (WHITE) 23 0 F1 N2 N1 15B 23 BLACK RED N2 N1 15B 240VAC TO TO GENERATOR OUTPUT PANEL MAIN DISTRIBUTION T1 T2 T1 T2 E2 E2 E...
NEUTRAL CONNECTION SWITCH SW3 NO C1 COM SW2 VR1 NC NC COM C2 VR2 NO TR1 15B 23 1 7 4 7 9 3 6 9 F2 CIRCUIT 10 BLACK (MAIN 1) CONTROL TRANSFER RED (MAIN 2) NEUTRAL (WHITE) NEUTRAL (WHITE) 23 0 F1 N2 N1 15B 23 BLACK RED N2 N1 15B 240VAC TO TO GENERATOR OUTPUT PANEL MAIN DISTRIBUTION T1 T2 T1 T2 E2 E2 E...
tranSFer to StandBy 12 VDC is delivered to the transfer relay via Wire 15B and back to the circuit board via Wire 23. However, circuit board action holds the Wire 23 circuit open and the transfer relay remains de-energized. On generator startup, an “engine warm-up timer” on the generator circuit boa...
utility reStored, tranSFer SWitch de-enerGized After the preset time interval expires the circuit board will open the Wire 23 circuit to ground. The transfer relay de-energizes, it’s normally closed contacts close, and utility source voltage is delivered to the utility closing coil (C1), via Wires N...
utility reStored, retranSFer Back to utility As the utility coil pulls the transfer switch to an OVER CENTER position, the switch mechanically snaps to Utility. On closure of the main contacts to the utility power source side, Limit Switches SW2 and SW3 are mechanically actuated to “arm” the circuit...
tranSFer SWitch in utility When the transfer switch returns to the utility side, generator shutdown occurs after approximately one (1) minute. Page 69 TRANSFER SWITCH sEctioN 3.2 oPEratioNal aNalYsis Part 3 NEUTRAL CONNECTION SWITCH SW3 NO C1 COM SW2 VR1 NC NC COM C2 VR2 NO TR1 15B 23 1 7 4 7 9 3 6 ...
introduction to trouBleShootinG The first step in troubleshooting is to correctly identify the problem. Once that is done, the cause of the an be found by performing the tests in the appropriate flow chart.Test numbers assigned in the flow charts are identical to test numbers in Section 3.4, “Diagno...
TRANSFER SWITCH sEctioN 3.3 trouBlEsHootiNG floW cHarts Part 3 Page 71 Problem 8 – In Automatic Mode, Generator Starts When Loss of Utility Occurs, Generator Shuts Down When Utility Returns But There Is No Retransfer To Utility Power OR Generator Transfers to Standby During Excercise or in Manual Mo...
REPLACE CIRCUIT BOARD CORRECT UTILITY SOURCE VOLTAGE REPLACE GO TO PROBLEM 7 REPAIR OR REPLACE WIRING REPAIR OR REPLACE WIRE N1A/N2A BETWEEN N1/N2 LUGS AND FUSE HOLDER REPAIR N1/N2 OPEN WIRING BETWEEN TRANSFER SWITCH AND GENERATOR Problem 10 – Unit Starts and Transfer Occurs When Utility Power Is On...
General Te s t n u m b e r s i n t h i s s e c t i o n c o r r e s p o n d t o t h e numbered tests in Section 3.3, “Troubleshooting Flow Char ts”. When troubleshooting, first identify the problem. Then, perfor m the diagnostic tests in the sequence given in the flow char ts. teSt 26 – check VoltaGe...
TRANSFER SWITCH sEctioN 3.4 DiaGNostic tEsts Part 3 Page 75 e. Set the generator AUTO-OFF-MANUAL switch to AUTO. (1) The generator should crank and start. (2) W h e n t h e g e n e ra t o r s t a r t s, a n “ e n g i n e war m-up timer” should star t timing. After about 15 seconds, the transfer rela...
b. Actuate the operating lever down to move the load contacts against the standby contacts, i.e., load connected to the Standby source. 6. Repeat Step 5 several times. As the transfer switch operating lever is moved slight force should be needed until the lever reaches its center position. As the le...
TRANSFER SWITCH sEctioN 3.4 DiaGNostic tEsts Part 3 Page 77 13. Set VOM to measure DC voltage.14. Connect the (-) negative meter test lead to Wire 0 at the terminal strip in the generator. Connect the (+) positive meter test lead to Wire 23 at the terminal strip in the generator. 12 VDC should be me...
4. Using jumper wires, connect the positive (+) post of a 12 volt battery to relay Terminal “A” and the negative (-) battery post to Relay Terminal “B”. The relay should energize and the VOM should read CONTINUITY. 5. Now, connect the VOM test leads across Relay Terminals 1 and 7. a. Energize the re...
TRANSFER SWITCH sEctioN 3.4 DiaGNostic tEsts Part 3 Page 79 A B 7 9 4 6 1 3 TR1 SW1 205 C2 SW3 E1 SW2 C1 1 2 1 2 N1 N2 E1 E2 E2 T1 T2 B A G E F C D H Figure 4. Standby Control Circuit Test Points
(2) Press the right arrow key until “Debug” is flashing. (3) Press “Enter”. (4) Press the right arrow key until “Outputs” is flashing. (5) Press “Enter”. (6) Digital Output 8 is Wire 23 output from the board. Refer to Figure 5. (7) If Output 8 shows a “1” then the control board is grounding Wire 23....
Figure 7. Utility Control Circuit Test Points TRANSFER SWITCH sEctioN 3.4 DiaGNostic tEsts Part 3 Page 81 N1A N1A A B 7 9 4 6 1 3 TR1 SW1 B C2 SW3 SW2 C1 A N2A N2A F1 F2 F3 A A A B B B 1 2 1 2 N1 N2 E1 E2 T1 T2 126 A B I G C D E F H
PROCEDURE: 1. On the generator panel, set the AUTO-OFF-MANUAL switch to OFF. 2. Turn off the utility power supply to the transfer switch, using whatever means provided. 3. Remove fuses F1 and F2 from the fuse holder (see Figure 8). 4. Inspect and test fuses for blown condition. With a VOM set to mea...
240 VAC N1 N2 TEST POINTS Figure 9. Terminal Block Test Points teSt 37 – check utility SenSinG VoltaGe at the circuit Board DISCUSSION:If the generator star ts and transfer to STANDBY o c c u r s i n t h e a u t o m a t i c m o d e w h e n a c c e p t a bl e UTILITY source voltage is available at th...
sEctioN X.X XXXXXXXXXXXXXXXXXXXXXXXXXXX Page 85 TRANSFER SWITCH sEctioN 3.4 DiaGNostic tEsts Part 3 23 TB1 A N LC B LEGEND TRANSFER SWITCH GENERATOR LC-CIRCUIT BREAKER (LOADS) (16 CIRCUIT SHOWN FOR REFERENCE ONLY) SW1-AUTOMATIC TRANSFER SWITCH C2-GENERATOR COIL & RECTIFIER C1-UTILITY COIL & ...
Page 88 E2 WHITE GREEN 23 15B 0 N1 DET AIL DET AIL N2 BC 00 BC LINE E1 N2 N1 15B 23 N1 N2 23 194 UTILITY SUPPL Y FR OM SER VICE DISCONNECT E2 TO GR OUNDING ELECTR ODE NEUTRAL BLOCK (DISTRIB UTION P ANEL) GR OUND BC LINE BC 00 5 AMP FUSE T1 T2 CUST OMER LO AD R TS TRANSFER SWITCH T1 T2 E1 (C2 & V...
Page 93 TRANSFER SWITCH sEctioN 3.4 DiaGNostic tEsts Part 3 FUSE, 2A F3 GR OUND LUG LIMIT SWITCHES , A CTU AT OR RELA Y, TRANSFER UTILITY CIRCUIT BREAKER NB - NEUTRAL BLOCK LO AD SHED CONTR OLLER RELA Y, LO AD SHED LO AD SHED TRANSFER SWITCH CONT A CT OR XA1,XB1 TR UCB GND LS LSC LSS NB SOLENOID COI...
General This section will familiarize the reader with the various components that make up the DC control system.Major DC control system components that will be covered include the following: • A Terminal Strip / Interconnection Terminal• A Circuit Board.• An AUTO-OFF-MANUAL Switch.• A 7.5 Amp Fuse. ...
DIVIDER PANEL DIVIDER PANEL TO ENGINE TO ENGINE 6 7 9 8 3 5 4 1 2 10 1. CONTROL PANEL 2. 7.5 AMP FUSE3. STARTER CONTACTOR RELAY (10-20 KW) 4. 4 POSITION TERMINAL BLOCK5. TERMINAL BLOCK6. CIRCUIT BREAKER (8KW)7. 15 AMP GFCI DUPLEX OUTLET (17 & 20 KW) 8. CIRCUIT BREAKER (17 & 20 KW)9. CIRCUIT ...
DC CONTROL sEctioN 4.1 DEscriPtioN aND comPoNENts Part 4 PiN WirE circuit fuNctioN J1-1 85 High temperature shutdown: Shutdown occurs when Wire 85 is grounded by contact closure in HTO J1-2 86 Low oil pressure shutdown: Shutdown occurs when Wire 86 is grounded by loss of oil pressure to the LOP J1-3...
Page 100 J2 J3 (STEPPER MOTOR) REMOTE WIRELESS CONNECTION J1 J2 CONNECTOR (HARNESS END) 10 11 12 13 14 15 16 17 18 1 2 3 4 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 1 2 3 4 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 1 2 3 4 1 2 3 4 5 6 7 8 9 J1 CONNECTOR (HARNESS END) J2 CONNECTOR (PCB END) J1 ...
Page 101 sEctioN 4.1 DEscriPtioN aND comPoNENts PiN WirE circuit fuNctioN J1-1 85 High temperature shutdown: Shutdown occurs when Wire 85 is grounded by contact closure in HTO J1-2 86 Low oil pressure shutdown: Shutdown occurs when Wire 86 is grounded by loss of oil pressure to the LOP J1-3 13 12 VD...
Part 4 Page 102 DC CONTROL sEctioN 4.1 DEscriPtioN aND comPoNENts FEMALE SIDE MALE SIDE 2 1 1 2 C3 Figure 8. Choke Solenoid Connector Pin Number Identification menu SyStem naViGation To get to the MENU, use the "Esc" key from any page. It may need to be pressed many times before getting to t...
sEctioN 4.1 DEscriPtioN aND comPoNENts Page 103 MAIN MENU RUN LOG ALARM LOG HIST OR Y ST ATUS COMMAND ST AT E VERSIONS DISPLA Y GENERA TOR FREQ UENCY ENGINE HOURS ENGINE RPM BA TTER Y VO LT AG E DEB UG INPUTS OUTPUTS DISPLA YS ST AR TUP DELA Y EDIT CONTRAST LANGU AGE FREQ UENCY TIME/D ATE EXERCISE T...
CONTROLLER DISPLAY Ready to Run = 12 VDC ALWAYS PRESENT= AC VOLTAGE= GROUND FOR CONTROL PURPOSES= 12 VDC DURING CRANKING ONLY= 12 VDC DURING ENGINE RUN CONDITION= DC FIELD EXCITATION= 5 VDC TO LED 0 4 4 0 BA 6 11 22 6 2 2 REGULATOR 11 2604 22 VOLTAGE 4 0 0 13 13 18 SP2 IM2 16 13 SCR 0 0 86 85 HTO LO...
CONTROLLER DISPLAY Utility Loss Delay Pausing 10 sec CONTROLLER = 12 VDC ALWAYS PRESENT= AC VOLTAGE= GROUND FOR CONTROL PURPOSES= 12 VDC DURING CRANKING ONLY= 12 VDC DURING ENGINE RUN CONDITION= DC FIELD EXCITATION= 5 VDC TO LED 0 4 4 0 BA 6 11 22 6 2 2 REGULATOR 11 2604 22 VOLTAGE 4 0 0 13 13 18 SP...
CONTROLLER DISPLAY Utility Loss Delay Pausing 10 sec CONTROLLER = 12 VDC ALWAYS PRESENT= AC VOLTAGE= GROUND FOR CONTROL PURPOSES= 12 VDC DURING CRANKING ONLY= 12 VDC DURING ENGINE RUN CONDITION= DC FIELD EXCITATION= 5 VDC TO LED 0 4 4 0 BA 6 11 22 6 2 2 REGULATOR 11 2604 22 VOLTAGE 4 0 0 13 13 18 SP...
CONTROLLER DISPLAY Cranking Attempt #1 = 12 VDC ALWAYS PRESENT= AC VOLTAGE= GROUND FOR CONTROL PURPOSES= 12 VDC DURING CRANKING ONLY= 12 VDC DURING ENGINE RUN CONDITION= DC FIELD EXCITATION= 5 VDC TO LED 0 4 4 0 BA 6 11 22 6 2 2 REGULATOR 11 2604 22 VOLTAGE 4 0 0 13 13 18 SP2 IM2 16 13 SCR 0 0 86 85...
CONTROLLER DISPLAY Cranking Attempt #1 = 12 VDC ALWAYS PRESENT= AC VOLTAGE= GROUND FOR CONTROL PURPOSES= 12 VDC DURING CRANKING ONLY= 12 VDC DURING ENGINE RUN CONDITION= DC FIELD EXCITATION= 5 VDC TO LED 0 4 4 0 BA 6 11 22 6 2 2 REGULATOR 11 2604 22 VOLTAGE 4 0 0 13 13 18 SP2 IM2 16 13 SCR 0 0 86 85...
CONTROLLER DISPLAY Running - Utility Lost = 12 VDC ALWAYS PRESENT= AC VOLTAGE= GROUND FOR CONTROL PURPOSES= 12 VDC DURING CRANKING ONLY= 12 VDC DURING ENGINE RUN CONDITION= DC FIELD EXCITATION= 5 VDC TO LED 0 4 4 0 BA 6 11 22 6 2 2 REGULATOR 11 2604 22 VOLTAGE 4 0 0 13 13 18 SP2 IM2 16 13 SCR 0 0 86...
CONTROLLER DISPLAY Running - Utility Lost = 12 VDC ALWAYS PRESENT= AC VOLTAGE= GROUND FOR CONTROL PURPOSES= 12 VDC DURING CRANKING ONLY= 12 VDC DURING ENGINE RUN CONDITION= DC FIELD EXCITATION= 5 VDC TO LED 0 4 4 0 BA 6 11 22 6 2 2 REGULATOR 11 2604 22 VOLTAGE 4 0 0 13 13 18 SP2 IM2 16 13 SCR 0 0 86...
CONTROLLER DISPLAY Running - Utility Lost CONTROLLER = 12 VDC ALWAYS PRESENT= AC VOLTAGE= GROUND FOR CONTROL PURPOSES= 12 VDC DURING CRANKING ONLY= 12 VDC DURING ENGINE RUN CONDITION= DC FIELD EXCITATION= 5 VDC TO LED 0 4 4 0 BA 6 11 22 6 2 2 REGULATOR 11 2604 22 VOLTAGE 4 0 0 13 13 18 SP2 IM2 16 13...
CONTROLLER DISPLAY Running - Utility Lost CONTROLLER = 12 VDC ALWAYS PRESENT= AC VOLTAGE= GROUND FOR CONTROL PURPOSES= 12 VDC DURING CRANKING ONLY= 12 VDC DURING ENGINE RUN CONDITION= DC FIELD EXCITATION= 5 VDC TO LED 0 4 4 0 BA 6 11 22 6 2 2 REGULATOR 11 2604 22 VOLTAGE 4 0 0 13 13 18 SP2 IM2 16 13...
CONTROLLER DISPLAY Running / Cooling Down = 12 VDC ALWAYS PRESENT= AC VOLTAGE= GROUND FOR CONTROL PURPOSES= 12 VDC DURING CRANKING ONLY= 12 VDC DURING ENGINE RUN CONDITION= DC FIELD EXCITATION= 5 VDC TO LED 0 4 4 0 BA 6 11 22 6 2 2 REGULATOR 11 2604 22 VOLTAGE 4 0 0 13 13 18 SP2 IM2 16 13 SCR 0 0 86...
• The utility closing coil (C1) energizes and moves the main current carrying contacts to their NEUTRAL position. The main contacts move to an over center position past NEUTRAL and spring force closes them to their UTILITY side. LOAD terminals are now powered by the UTILITY source. • Movement of the...
CONTROLLER DISPLAY Ready to Run = 12 VDC ALWAYS PRESENT= AC VOLTAGE= GROUND FOR CONTROL PURPOSES= 12 VDC DURING CRANKING ONLY= 12 VDC DURING ENGINE RUN CONDITION= DC FIELD EXCITATION= 5 VDC TO LED 0 4 4 0 BA 6 11 22 6 2 2 REGULATOR 11 2604 22 VOLTAGE 4 0 0 13 13 18 SP2 IM2 16 13 SCR 0 0 86 85 HTO LO...
CONTROLLER DISPLAY Ready to Run = 12 VDC ALWAYS PRESENT= AC VOLTAGE= GROUND FOR CONTROL PURPOSES= 12 VDC DURING CRANKING ONLY= 12 VDC DURING ENGINE RUN CONDITION= DC FIELD EXCITATION= 5 VDC TO LED 0 4 4 0 BA 6 11 22 6 2 2 REGULATOR 11 2604 22 VOLTAGE 4 0 0 13 13 18 SP2 IM2 16 13 SCR 0 0 86 85 HTO LO...
VERIFY UTILITY SOURCE IS “OFF”* TEST 56 – CHECK POSITION OF AUTO-OFF-MANUAL SWITCH TEST 58 – TEST AUTO-OFF-MANUAL SWITCH TEST 59 – CHECK AUTO OPERATION OF CONTROLLER TEST 57 – TRY A MANUAL START ON OFF SWITCH IS “OFF” SWITCH IS IN “AUTO” ENGINE DOES NOT CRANK ENGINE CRANKS BAD BAD SET TO “AUTO” - RE...
Page 119 sEctioN 4.3 trouBlEsHootiNG floW cHarts BAD REPLACE CHOKE SOLENOID CLEAN, REGAP OR REPLACE REPLACE CIRCUIT BOARD REPLACE FUEL SOLENOID TEST 66 – CHECK FUEL SUPPLY AND PRESSURE REPLACE FUEL REGULATOR TEST 70 – CHECK FOR IGNITION SPARK TEST 69 – CHECK CHOKE SOLENOID TEST 74 – CHECK IGNITION M...
sEctioN 4.3 trouBlEsHootiNG floW cHarts Page 121 BAD NO SIGNAL REPAIR OR REPLACE BAD PROCEED TO PROBLEM 16 PROCEED TO PROBLEMS 10-13 CHECK INSTALLATION FOR PROPER AIRFLOW OR REPLACE DEFECTIVE SWITCH REPAIR LINKAGE IF BINDING. CHECK THROTTLE OPERATION.REFER TO ENGINE SERVICE MANUAL TEST 15 – CHECK AN...
Part 4 Page 122 DC CONTROL sEctioN 4.3 trouBlEsHootiNG floW cHarts FUSE BLOWS WHEN PLACED IN “AUTO” OR “MANUAL” Problem 20 – 7.5 Amp Fuse (F1) Blown TEST 80 – CHECK CRANKING AND RUNNING CIRCUITS Problem 21 – Generator Will Not Exercise TEST 79 – TEST EXERCISE FUNCTION GOOD BAD Problem 22 – No Low Sp...
Page 123 sEctioN 4.4 DiaGNostic tEsts introduction Perform these “Diagnostic Tests” in conjunction with the “Troubleshooting Flow Charts” of Section 4.3. The test procedures and methods presented in this section are not exhaustive. The manufacturer could not possibly know of, evaluate and advise the...
Page 124 INPUT 7 INPUT 8 DEBUG 1 2 3 INPUTS Figure 2. The Home Page, Debug and Input Screens 5. With the Inputs Screen displayed place the AUTO-OFF- MANUAL switch to the MANUAL Position. If the control- ler reads an input from the switch input 8 will change from “0” to “1”. 6. With the AUTO-OFF-MANU...
sEctioN 4.4 DiaGNostic tEsts Page 125 B. p e r f o r m a l o a d t e s t o n t h e B a t t e r y : (maintenance Free Battery) 1. Using a lead acid batter y load tester test the load capability of the battery. 2. Follow the load tester’s manufacturer’s instructions carefully. Figure 3. A Typical Batt...
Page 126 teSt 62 – check Wire 56 VoltaGe DISCUSSION:During an automatic start or when starting manually, a crank relay on the circuit board should energize. Each time the crank relay energizes, the circuit board should deliver 12 VDC to a star ter contactor relay (SCR), or star ter contactor (SC), a...
sEctioN 4.4 DiaGNostic tEsts Page 127 PROCEDURE: 1. Set a VOM to measure DC voltage.2. Remove Wire 13 from the Starter Contactor Relay located under the printed circuit board. 3. Connect the positive (+) meter test lead to the Wire 13 connector. Connect the negative (-) meter test lead to a clean fr...
Page 128 teSt 65 – teSt Starter motor CONDITIONS AFFECTING STARTER MOTOR PERFORMANCE: 1. A binding or seizing condition in the starter motor bearings.2. A shorted, open or grounded armature. a. Shor ted ar mature (wire insulation wor n and wires touching one another). Will be indicated by low or no ...
sEctioN 4.4 DiaGNostic tEsts Page 129 PINION Figure 13. Check Pinion Gear Operation (Single Cylinder) TOOLS FOR STARTER PERFORMANCE TEST:The following equipment may be used to complete a performance test of the starter motor: • A clamp-on ammeter.• A tachometer capable of reading up to 10,000 rpm.• ...
Page 130 STARTER CONTACTOR STARTER MOTOR TACHOMETER 12 VOLT BATTERY CLAMP ON AMP METER VISE Figure 17. Testing Starter Motor Performance teSt 66 – check Fuel Supply and preSSure DISCUSSION:The air-cooled generator was factor y tested and adjusted using natural gas as a fuel. If desired, LP (propane)...
sEctioN 4.4 DiaGNostic tEsts Page 131 PORT 3 PORT 1 PORT 2 Figure 20 (12-20 kW) Gas Pressure Test point note: Where a primary regulator is used to estab-lish fuel inlet pressure, adjustment of that regula-tor is usually the responsibility of the fuel supplier or the fuel supply system installer. 12-...
Page 132 i. Set a VOM to measure resistance. j. Connect one meter test lead to Wire 14 that was disconnected in Step 3. k. Connect the other meter test lead to Wire 14 at J2-3. See Figures on Pages 92-95. l. C O N T I N U I T Y s h o u l d b e m e a s u r e d . I f CONTINUITY is measured, repeat Ste...
sEctioN 4.4 DiaGNostic tEsts Page 133 CHOKE SOLENOID CHOKE PLATE Figure 22. Solenoid De-Energized, Choke Closed 12-20 kW Units CHOKE SOLENOID CHOKE PLATE Figure 23. Solenoid Energized, Choke Open 12-20 kW Units 3. Set a VOM to measure DC voltage. 4. Connect the positive (+) test lead to Wire 14 (Pin...
Page 134 2. Disconnect the C3 Connector. 3. Set a VOM to measure DC voltage. 4. Connect the positive (+) test lead to Wire 56 (Pin 1) of C3 Connector going to the control panel (Female Side) Connect the negative (-) test lead to Wire 0 (Pin 2). 5. Set the AUTO-OFF-MANUAL Switch to MANUAL. While cran...
sEctioN 4.4 DiaGNostic tEsts Page 135 Figure 27. Spark Tester Figure 28. Checking Ignition Spark To deter mine if an engine miss is ignition related, connect the spark tester in series with the spark plug wire and the spark plug (Figure 29). Then, crank and start the engine. A spark miss will be rea...
Page 136 Figure 29. Checking Engine Miss RESULTS: 1. If no spark or very weak spark occurs, go to Test 73.2. If sparking occurs but engine still won’t start, go to Test 71.3. When checking for engine miss, if sparking occurs at regular intervals but engine miss continues, go to Test 20. 4. When chec...
sEctioN 4.4 DiaGNostic tEsts Page 137 DISCUSSION:The Cylinder Leak Down Tester checks the sealing (compression) ability of the engine by measuring air leakage from the combustion chamber. Compression loss can present many different symptoms. This test is designed to detect the section of the engine ...
Page 138 WIRE 18 CONNECTION Figure 32. Wire 18 Connection 10-20 kW Units 2. Depending on engine type, do the following: a. O n V- t w i n u n i t s, r e m ove W i r e 5 6 f r o m t h e Starter Contactor Relay (SCR). Using a jumper lead, jump 12 VDC from Wire 15B at TB1 (Customer Connection) to the t...
sEctioN 4.4 DiaGNostic tEsts Page 139 PROCEDURE, ADJUSTING MAGNETO FLYWHEEL GAP:note: the air gap between the ignition magneto and the flywheel on single cylinder engines is not adjustable. proceed directly to Step 10 for single cylinder engines. For V-twin engines, proceed as follows. 1. See Figure...
Page 140 RESULTS:If sparking still does not occur after adjusting the a r m a t u r e a i r g a p, t e s t i n g t h e gr o u n d w i r e s a n d p e r fo r m i n g t h e b a s i c f l y w h e e l t e s t , r e p l a c e t h e ignition magneto(s). PROCEDURE, REPLACING MAGNETOS: 1. Follow all steps o...
sEctioN 4.4 DiaGNostic tEsts Page 141 teSt 75 – check oil preSSure SWitch and Wire 86 DISCUSSION:If the oil pressure switch contacts have failed in their closed position, the engine will probably crank and start. However, shutdown will then occur within about 5 (five) seconds. If the engine cranks a...
Page 142 a. Disconnect the J1 Connector from the printed circuit board. b. Connect one test lead to Wire 86 (disconnected from LOP). Connect the other test lead to Pin Location 4 (Wire 86) of the J1 Connector at the Circuit Board (for all models). CONTINUITY should be measured. If CONTINUITY is not ...
sEctioN 4.4 DiaGNostic tEsts Page 143 PROCEDURE: (INTAkE AND EXHAUST)Make sure that the piston is at Top Dead Center ( T D C ) o f i t ’s c o m p r e s s i o n s t r o ke ( b o t h va l ve s closed). The valve clearance should be 0.05-0.1mm (0.002-0.004 in.) cold.Check and adjust the valve to rocker...
Page 144 10. Connect one meter test lead to Wire 18 removed from the stud connector. Connect the other meter test lead to a clean frame ground. INFINITY should be measured. If CONTINUITY is measured, repair or replace Wire 18 between the stud connector and the J1 Connector. RESULTS:Refer to flow cha...
d. If coil resistance was measured in CS and FS, and FS2 Wire 14 is shorted to ground between J2 connector and CS, FS, or FS2, repair or replace the shorted wire. 8. Disconnect Wire 14 from the Fuel Solenoid (FS) and Choke Solenoid (CS). a. Connect one meter test lead to the FS terminal from which W...
Part 5 oPEratioNal tEsts air-cooled, automatic standby Generators Page 147 taBlE of coNtENts Part titlE 5.1. system functional tests 5.1 System Functional Tests ................................ 148 Introduction ....................................................148 Manual Transfer Switch Operation ...
introduction Following home standby electric system installation and periodically thereafter, the system should be tested Functional tests of the system include the following: • Manual transfer switch operation.• System voltage tests.• Generator Tests Under Load.• Testing automatic operation. Before...
OPERATIONAL TESTS AND ADJUSTMENTS sEctioN 5.1 sYstEm fuNctioNal tEsts Part 5 Page 149 DANGER + tHE traNsfEr sWitcH is NoW ElEctri- callY “Hot”, coNtact WitH “Hot” Parts Will rEsult iN EXtrEmElY HaZarDous aND PossiBlY fatal ElEctrical sHocK. ProcEED WitH cautioN. 5. Use an accurate AC voltmeter to ch...
11. Let the generator run at full rated load for 20-30 minutes. Listen for unusual noises, vibration or other indications of abnormal operation. Check for oil leaks, evidence of overheating, etc. 12. When testing under load is complete, turn off electrical loads. 13. Set the generator main circuit b...
Part 6 DisassEmBlY air-cooled, automatic standby Generators Page 151 taBlE of coNtENts Part titlE 6.1. major Disassembly 6.1 Major Disassembly ........................................ 152 Front Engine Access ......................................152 Major Disassembly ...................................
Front enGine acceSS SAFETY: 1. Set the AUTO-OFF-MANUAL switch to OFF.2. Remove the 7.5 amp main fuse. See Figure 1.3. Remove the N1 and N2 fuse from the transfer switch. Figure 1. Remove 7.5 Amp Fuse 4. Turn off fuel supply to the generator and remove the flex- line from the fuel regulator. 5. Remov...
Page 156 Part 6 DISASSEMBLY sEctioN 6.1 maJor DisassEmBlY 14. Remove Blower Housing: Using a 4mm allen wrench remove one button head cap screw from top of blower housing. Using a 10mm socket remove one 10mm bolt from the top of the blower housing. See Figure 19. Using a 10mm socket remove four 10mm ...
12. Remove Engine: Using proper lifting equipment remove the engine. See Figure 44. Figure 44. torque requirementS (unleSS otherWiSe SpeciFied) STATOR BOLTS ................................................ 6 ft-lbs ( +1 / -0 ) ROTOR BOLT .................................................................
2 6 44 2233 11 STATOR ENGINE COMPARTMENT CONTROL PANEL 1 5 2 3 4 7 6 8 11 9 10 12 13 14 15 16 17 18 J1 J2 MAIN CONTROLLER SP1 IM1 HTO 85 LOP 86 0 0 1 234 8586 1318 CHOKE SOLENOID RED 1 2 BLK FRAME GND 0 ENGINE GND 0 18 10 10 10 10 N1 N2 1 2 N1 N2 6 6 PANEL GND 0 0 0 0 0 0 GROUND + BATTERY TRANS SIG ...
Part 7 ELECTRICAL DATA scHEmatic, 8 KW HomE staNDBY Page 166 OUTPUT GENERATOR 240 VAC NEUTRAL INPUT UTILITY 240 VAC TRANSFER + BATTERY GROUND 56 0 15B 23 23 0 0 0 0 56 56 FS 16 13 SC 0 0 86 85 HTO LOP 18 BATTERY WARMER OPTIONAL N1 00 22 33 11 44 CB 15B 14 0 13 0 12V BATTERY SC 0 CS IM SP EXCITATION ...
Page 168 2 6 44 2233 11 STATOR ENGINE COMPARTMENT CONTROL PANEL 1 5 2 3 4 7 6 8 11 9 10 12 13 14 15 16 17 18 J3 J1 J2 MAIN CONTROLLER SP1 IM1 SP2 IM2 HTO 85 LOP 86 0 0 1 234 8586 1318 CHOKE SOLENOID RED 1 2 BLK ACTUATOR GOVERNOR SC SM FRAME GND 0 ENGINE GND 0 18 13 14 90 0 0 56 A 0 B SCR 16 13 16 10...
Page 170 Part 7 ELECTRICAL DATA scHEmatic, 10 KW HomE staNDBY 820 817818819 ACTUATOR J3 GOVERNOR 14 0 14 FS 90 13 18 SP2 IM2 OUTPUT GENERATOR 240 VAC NEUTRAL INPUT UTILITY 240 VAC TRANSFER + BATTERY GROUND 56 0 15B 23 23 0 0 FS 16 13 SCR 0 0 86 85 HTO LOP 18 BATTERY WARMER OPTIONAL N1 00 22 33 11 44...
Page 172 ENGINE COMPARTMENT CONTROL PANEL 1 5 2 3 4 7 6 8 11 9 10 12 13 14 15 16 17 18 J3 J1 J2 MAIN CONTROLLER SP1 IM1 SP2 IM2 HTO 85 LOP 86 0 0 1 234 8586 1318 CHOKE SOLENOID RED 1 2 BLK ACTUATOR GOVERNOR SC SM FRAME GND 0 ENGINE GND 0 18 13 0 14 4 90 0 0 56 A 0 B SCR 16 13 16 N1 N2 1 2 N1 N2 0 6 ...
Page 174 Part 7 ELECTRICAL DATA scHEmatic, 14 KW HomE staNDBY 0 4 4 0 BA 6 11 22 6 2 2 REGULATOR 11 2604 22 VOLTAGE 4 0 0 13 13 18 SP2 IM2 16 13 SCR 0 0 86 85 HTO LOP 18 0 13 12V BATTERY SCR SM IM1 SP1 44 11 POWER WINDING 33 22 WINDING POWER STATOR 4 0 56 0 SC 820 817818819 819 818 817 820 L2 L1 LED...
Page 176 CLOSEST TO BEARING BA 0 4 6 22 11 44 2233 11 STATOR 2 0 6 VOLTAGE REGULATOR 4 11 22 2 2 6 2211 ENGINE COMPARTMENT CONTROL PANEL 1 5 2 3 4 7 6 8 11 9 10 12 13 14 15 16 17 18 J3 J1 J2 MAIN CONTROLLER SP1 IM1 SP2 IM2 4 HTO 85 LOP 86 0 0 1 234 8586 1318 CHOKE SOLENOID RED 1 2 BLK ACTUATOR GOVER...
Page 178 Part 7 ELECTRICAL DATA scHEmatic, 17 KW HomE staNDBY 0 4 4 0 BA 6 11 22 6 2 2 REGULATOR 11 2604 22 VOLTAGE 4 0 0 13 13 18 SP2 IM2 16 13 SCR 0 0 86 85 HTO LOP 18 0 13 0 12V BATTERY SCR SM IM1 SP1 44 11 POWER WINDING 33 22 WINDING POWER STATOR 18 13 86 85 4 0 0 SC 13 0 0 00 00 11C L3 820 8178...
Page 180 CLOSEST TO BEARING BA 0 4 6 22 11 44 2233 11 STATOR 2 0 6 VOLTAGE REGULATOR 4 11 22 2 2 6 2211 ENGINE COMPARTMENT CONTROL PANEL 1 5 2 3 4 7 6 8 11 9 10 12 13 14 15 16 17 18 J3 J1 J2 MAIN CONTROLLER SP1 IM1 SP2 IM2 4 HTO 85 LOP 86 0 0 1 234 8586 1318 CHOKE SOLENOID RED 1 2 BLK ACTUATOR GOVER...
Page 182 Part 7 ELECTRICAL DATA scHEmatic, 20 KW HomE staNDBY 0 0 00 00 11C L3 0 4 4 0 BA 6 11 22 6 2 2 REGULATOR 11 2604 22 VOLTAGE 820 817818819 819 818 817 820 L2 L1 LED BOARD 4 3 2 1 4 4 0 0 ACTUATOR J3 GOVERNOR 14 14 90 13 13 13 18 SP2 IM2 OUTPUT GENERATOR 240 VAC NEUTRAL INPUT UTILITY 240 VAC ...
Part 7 Page 184 ELECTRICAL DATA WiriNG DiaGram, HomE staNDBY traNsfEr sWitcH, 9/10/12/16 circuit 205 N2A N1A RED BLK 10 CIRCUIT LOAD CENTER 12 CIRCUIT LOAD CENTER 14 CIRCUIT LOAD CENTER CIRCUIT 8 8 CIRCUIT LOAD CENTER CIRCUIT 1 CIRCUIT 3 CIRCUIT 10 CIRCUIT 12 CIRCUIT 14 CIRCUIT 16 CIRCUIT 5 CIRCUIT ...
Page 186 Part 7 ELECTRICAL DATA scHEmatic, HomE staNDBY traNsfEr sWitcH, 9/10/12/16 circuit NEUTRAL CONNECTION SWITCH SW3 NO C1 COM SW2 VR1 NC NC COM C2 VR2 NO TR1 15B 23 1 7 4 7 9 3 6 9 F2 CIRCUIT 10 BLACK (MAIN 1) CONTROL TRANSFER RED (MAIN 2) NEUTRAL (WHITE) NEUTRAL (WHITE) 23 0 F1 N2 N1 15B 23 B...
Generac Manuals
-
Generac 005793-3
User Manual
-
Generac 5943-3
User Manual
-
Generac XG8000E-5747-0
User Manual
-
Generac 005800-0
User Manual
-
Generac 5939-4
User Manual
-
Generac GP5500-5939-5
User Manual
-
Generac 5797-0
User Manual
-
Generac 005939-2
User Manual
-
Generac 005747-0
User Manual
-
Generac XG4000-5778-1
User Manual
-
Generac 005939-6
User Manual
-
Generac GP6500-5940-0
User Manual
-
Generac GP7500E-5943-2
User Manual
-
Generac XG7000E-5798-2
User Manual
-
Generac 006673-0
User Manual
-
Generac 5939-6
User Manual
-
Generac 005939-0
User Manual
-
Generac 005939-0
Manual
-
Generac 5941-1
User Manual
-
Generac 006230-0
User Manual