Page 2 - Table of Contents
2 3 920-159-01 (10-03) 920-159-01 (10-03) Table of Contents Installation Recommendations ......................................................................................................................................................... 3I. General Specifications Model Number Identification Gu...
Page 4 - Chassis Specifications; Section I. General Specifications
4 5 920-159-01 (10-03) 920-159-01 (10-03) V ert-I-Pak ® Chassis Specifications MODEL: V(E,H)A24 Voltage (V) 230/208 Refrigerant R-22 Chassis Width 23.125 Chassis Depth 23.125 Chassis Height ** 47.25 Supply Duct Collar *** 10" Drain Connection 3/4" FPT Min. Circuit Amps See Nameplate CFM Indo...
Page 5 - Figure 4; Top View; ) Utility Closet Dimensions; Figure 3; Typical Utility Closet; Chassis Shown in Closet, on Optional Platform
4 5 920-159-01 (10-03) 920-159-01 (10-03) electrical entrance control box Figure 4 Top View Exterior Wall Flexible Ductwork Rigid Ductwork VPAWP1-8/1-14 Wall Plenum Plenum VPDP1 drain pan beneath unit is required on all VEA/VHA24 units. Drain pan must be installed prior to chassis installation Chass...
Page 6 - ) Wall Plenum and Architectural Louver Installation; Figure 5; Wall Plenum & Outdoor Louver Installation
6 7 920-159-01 (10-03) 920-159-01 (10-03) 2) Wall Plenum and Architectural Louver Installation A. Install the wall plenum (VPAWP1-8/1-14) components in accordance with the installation instructions provided with each accessory. B. Ensure that the divider is adjusted properly for the depth of the wal...
Page 7 - ) Electrical Information; Electrical Data; SAMPLE; Sample Nameplate (see your chassis nameplate)
6 7 920-159-01 (10-03) 920-159-01 (10-03) 3) Electrical Information Electrical Data * Single circuit from main box. Based on copper wire, single insulated conductor at 60°C.NOTE: Use copper conductors ONLY. Wire sizes are per NEC. Check local codes for overseas applications. SAMPLE VHA/VEA24K25 VHA/...
Page 8 - Electrical Requirements; Figure 6; CAUTION; Drain Connection; Figure 7
8 9 920-159-01 (10-03) 920-159-01 (10-03) 3) Electrical Information (continued) IMPORTANT: ALL 208/230V CHASSIS MUST BE HARD WIRED WITH PROPERLY SIZED BREAKER. SEE NAMEPLATE FOR SPECIFIC CHASSIS ELECTRICAL REQUIREMENTS. SEE PAGE 9 - FIGURE 8 FOR UNIT WIRING AND WALL THERMOSTAT WIRING. SEE PAGE 7 FOR...
Page 9 - Electrical & Thermostat Wiring Diagrams; Figure 8
8 9 920-159-01 (10-03) 920-159-01 (10-03) 3) Electrical Data (continued) L1 L2 QUICK DISCONNECT HERM BLUE YELLOW GREEN WHITE RED CAPACITOR BROWN GREEN BROWN COMP WIRE HARNESS COMPRESSOR RED BLUE BLACK RED FAN c BLACK BLUE WHITE TRANSFORMER WHITE BLACK BLACK COIL, SOLENOID WIRE NUT (RED) SEE NOTE #4 ...
Page 10 - ) Indoor Return Air Grille Installation; Return Air Grille Options; Figure 9
10 11 920-159-01 (10-03) 920-159-01 (10-03) All Vert-I-Pak chassis are shipped with a 20" x 14" filter installed. If an accessory filter holder is to be used, you MUST remove the factory shipped filter from the chassis. Do NOT use two filters 4) Indoor Return Air Grille Installation There ar...
Page 12 - ) Final Installation Checklist; III. Chassis Operation; ) Remote Thermostat Control; With the chassis in place, you are now ready to begin chassis; RT2 Digital Thermostat
12 13 920-159-01 (10-03) 920-159-01 (10-03) 8) Final Installation Checklist o Correct line voltage? o Chassis deck level? o Plenum divider baffle installed? o Wall plenum caulked? Level? Flashing? o HACR type breaker/fuse? o Single circuit only? o Ductwork connected? o Chassis weather seal in place?...
Page 13 - 3) Condensate Disposal System; To Remove the Chassis from the Closet:; 5) Routine Maintenance; Performing Routine Maintenance
12 13 920-159-01 (10-03) 920-159-01 (10-03) 12) Fresh Air Door The Fresh Air Door is an "intake" system. The fresh air door is opened via a slide on the front of the chassis located just above the indoor coil. Move the slide left to open and right to close the fresh air door. The system is c...
Page 14 - FRIEDRICH AIR CONDITIONING CO.; A SERIES SINGLE PACKAGE VERTICAL AIR CONDITIONERS
14 15 920-159-01 (10-03) 920-159-01 (10-03) FRIEDRICH AIR CONDITIONING CO. Post Office Box 1540 · San Antonio, Texas 78295-1540 (210) 357-4400 · FAX (210) 357-4480 VERT- I-PAK ® A SERIES SINGLE PACKAGE VERTICAL AIR CONDITIONERS LIMITED WARRANTY SAVE THIS CERTIFICATE. It gives you specific rights, yo...
Page 15 - MODEL DESCRIPTION PHOTO
14 15 920-159-01 (10-03) 920-159-01 (10-03) RETURN AIR GRILLE Interior return air grille that hinges to allow a Þ eld supplied (16" x 20") Þ lter to slip inside. Must be used when an access door / panel already exists in closet. DIMENSIONS: 18 7 / 16 " high x 22 3 / 8 " wide. ACCES...
Page 16 - Use Factory Certified Parts.
920-159-01 (10-03) Use Factory Certified Parts. FRIEDRICH AIR CONDITIONING CO. Post Office Box 1540 · San Antonio, Texas 78295-15404200 N. Pan Am Expressway · San Antonio, Texas 78218-5212(210) 357-4400 · Fax (210) 357-4480www.friedrich.com Printed in the U.S.A.