Page 3 - Table of Contents
2 Table of Contents Congratulations ........................................................................................................................................................................................................................ 3 General Instructions ...........................
Page 5 - Here are some suggestions to help you use your; Refrigeration system; NOTICE; CAUTION; Your safety and the safety of others are very important.; WARNING
3 Congratulations Thank you for your decision to purchase Friedrich. Your new Friedrich has been carefully engineered and manufactured to give you many years of dependable, efficient operation, maintaining a comfortable temperature and humidity level. Many extra features have been built into your un...
Page 6 - MODEL NUMBER; Typical Unit Components and Dimensions
4 General Specifications Installation Checklist q Inspect all components and accessories for damage before and after installation. q Remove the cardboard wall sleeve support and grill weatherboard. q Check for proper wall sleeve installation in accordance with the wall sleeve installation instructio...
Page 7 - PTAC Installation Recommendations; Figure 1; VIEW: OUTSIDE BUILDING ELEVATION
5 PTAC Installation Recommendations PTAC units should be installed no closer than 12" apart when two units are side by side. If three or more PTAC units are to operate next to one another allow a minimum of 36" between units. Also, a vertical clearance of 60" should be maintained between...
Page 8 - Wall Sleeve Installation Instructions (PDXWS); See Page 9; Figure 3; Typical Wall Sleeve Installation; Falling Object Hazard; All 230/208V units are manufactured with a
6 Wall Sleeve Installation Instructions (PDXWS) NOTE: Insure that the unit is only installed in a wall structurally adequate to support the unit including the sleeve, chassis and accessories. If the sleeve projects more than 8" into the room, a subbase or other means of support MUST be used. Ple...
Page 9 - Alternate Wall Installations; Figure 4; Panel Wall; Figure 6; Curtain Wall; Figure 5; Frame and Brick Veneer; Figure 7; Block and Brick Veneer
7 NOTE: Follow all wall system manufacturer installation instructions. For sunrooms and modular buildings, adhere to their installation instructions for supporting and sealing sleeve to their frames. All wall and window/wall installations must provide for proper drainage. In applications where the d...
Page 10 - Figure 9; Dimensions; Figure 8; Wall Sleeve Attachment
8 Figure 9 Dimensions FRP007 NOTE: The Wall Sleeve must behorizontally level (side-to-side)and pitched 1/4 bubble to theoutside when installed in anopening.The mounting hole locationshould be approximately 2-4”from the top and bottom of thesleeve. MOUNTING HOLES PLASTIC ANCHORS WOOD SCREW ALTERNATEF...
Page 11 - Lintel Installation; One-Piece Deep Wall Sleeve
9 FRP010 NOTE: Construct wall opening to comply with all applicable building codes. MAIN STUDS JACK STUDS LINTEL MOUNTINGSCREW HOLES NO HOLES IN BOTTOM OF WALLSLEEVE UNLESS DRAIN KIT IS USED MAIN STUDS JACK STUDS 5. Drill two 3/16" holes through each side of the sleeve approximately 4" from ...
Page 12 - QUANTITY; COVER PLATES; PXDR10 Drain Kit Installation; Internal Drain
10 FRP011 DRAIN TUBE SIDE VIEW FRONT VIEW WALL SLEEVE OPTIONAL AREA PREFERRED AREA-NO FOAM INSULATION IF THE DRAIN MUST BELOCATED IN THE OPTIONALAREA, THE FOAM INSULATIONMUST BE CUT AWAY ANDREMOVED TO ALLOW ACCESSTO THE DRAIN. NUT MOUNTINGPLATE GASKET SCREW 3" Figure 11 Drain Kit Location and In...
Page 13 - DETAIL B; External Drain (for new; Cover Plate Installation; Drain Kit Installation
11 FRP012 FOAMGASKET OVERFLOW SLOTS DETAIL B DETAIL A COVERPLATE FOAMGASKET SCREWS ½” O.D. TUBE MOUNTINGPLATE NUT External Drain (for new construction or unit replacement) When using an external drain system, the condensate is removed through either of two drain holes on the back of the wall sleeve....
Page 14 - Standard Grille; Description
12 PXGA Standard Grille Installation Instructions 1. Remove the center support and weatherboard if still installed in the sleeve. 2. Insert six plastic grommets into the grille openings from the outside of the grille as shown in Figure 13. 3. Insert two #8 x ⅜" sheet metal screws (provided) in t...
Page 15 - A. Electrical Rating Tables; All 230/208 volt units are equipped with power cords.; 50V Receptacles and Fuse Types; AMPS; Typical LCDI Devices; Electrical Shock Hazard
13 W ARNING 15/20A LCDI Device 30A LCDI Device TEST BEFORE EACH USE 1. PRESS RESET BUTT ON 2. PLUG LCDI INT O POWER RECEPT ACLE 3. PRESS TEST BUTT ON, RESET BUTT ON SHOULD POP UP 4. PRESS TEST BUTT ON, FOR USE DO NOT USE IF ABOVE TEST F AILS WHEN GREEN LIGHT IS ON IT IS WORKING PROPERL Y RESET TEST ...
Page 16 - Power Cord Installation
14 TABLE 2 Model Heater kW Power Cord Kit Voltage Amperage Receptacle PDE07K 0.0 PXPC23000 230/208 15 NEMA 6-15r PDE/PDH07K 2.0 PXPC23015 230/208 15 NEMA 6-15r 3.0 STD 230/208 20 NEMA 6-20r PDE09K 0.0 PXPC23000 230/208 15 NEMA 6-15r PDE/PDH09K 2.0 PXPC23015 230/208 15 NEMA 6-15r 3.0 STD 230/208 20 N...
Page 18 - Chassis Install Preparation; Suffocation Hazards
16 Chassis Install Preparation Check to be sure the wall sleeve, extension (if used), grille, and drain kit are installed properly before chassis installation. 1. Remove the weatherboard and center support from the sleeve (if still in place). Be sure an outdoor grille is attached. NOTE: Use a wall s...
Page 19 - Unit Damage Hazard
17 FRP020 SHIPPINGTAPE Figure 20 Shipping Tape Location FRP021 REMOVE SHIPPINGSCREW IF PRESENT Figure 21 Shipping Screw Location Figure 22 Removing Front Panel CAUTION Unit Damage Hazard Failure to follow this caution may result in equipment damageor improper operation. Failure to remove shipping ta...
Page 20 - Securing Unit; Excessive Weight Hazard; Chassis Installation
18 1. Lift unit level and slide unit into wall sleeve until from seal rests firmly against front of wall sleeve. 2. Locate the four supplied chassis mounting screws. Insert the screws through the chassis mounting flange holes that are aligned with the speed nuts in the wall sleeve. Tighten all four ...
Page 21 - How To Connect; Junction Box Location; Wire Clamp
19 How To Connect IMPORTANT: Please read following electrical safety data carefully. 1. Remove front panel. See Figure 22. 2. Remove junction box. • Remove junction box cover by removing three screws from front. Remove junction box by taking out top, rear and side screws. See Figure 24. WARNING Elec...
Page 22 - Friedrich PTAC Digital Control and Unit Features
20 Friedrich PTAC Digital Control and Unit Features The new Friedrich digital PTAC has state of the art features to improve guest comfort, indoor air quality and conserve energy. Through the use of specifically designed control software for the PTAC industry Friedrich has accomplished what other Man...
Page 24 - System Configuration; Fresh Air Vent Control; CLOSE; Adjusting Air; Air Vent Control Location; Backside of Front Panel
22 System Configuration Fresh Air Vent Control The vent control lever is located on the left side of the unit, behind the front panel. NOTE: The vent door shipping hardware must be removed before using the vent control lever. See page 17, Figure 21, (Remove Shipping Screw from Vent Door if present)....
Page 25 - Digital Control User Input Configuration; DIP SWITCH; Dip Switches; Emergency Heat Override – Switch 1; Dip Switch Setting
23 The adjustable control dip switches are located at the lower left hand portion of the digital Smart Center. The inputs are only visible and accessible with the front cover removed from the PTAC. Digital Control User Input Configuration Switch Description Function Factory Setting Option 1 Emergenc...
Page 26 - Digital Control Operation
24 FRP030 High Med Low Fan Cool Heat Fan Speed Mode Temperature Power °F vs. °C Display The unit is factory configured to display all temperatures in degrees Fahrenheit (° F). To switch to degrees Celsius press the ‘Fan Only’ and ‘Low Fan’ buttons simultaneously for three seconds. The display will s...
Page 28 - Desk Control Terminals; Energy Management
26 Desk Control Terminals The Friedrich PD model PTAC has built-in provisions for connection to an external switch to control power to the unit. The switch can be a central desk control system or even a normally open door switch.For desk control operation connect one side of the switch to the D1 ter...
Page 29 - Routine Maintenance; Decorative Front
27 q Inspect and ensure that all components and accessories have been installed properly and that they have not been damaged during the installation process. q Check the condensate water drain(s) to ensure they are adequate for the removal of condensate water, and that they meet the approval of the ...
Page 30 - Basic Troubleshooting
28 Basic Troubleshooting COMPLAINT CAUSE SOLUTION Unit does not operate. ● Unit turned off. ● Turn unit on ● Thermostat is satisfied. ● Raise/Lower temperature setting. ● LCDI power cord is unplugged. ● Plug into a properly grounded 3 prong recep- tacle. See "Electrical Rating Tables" on pag...
Page 32 - Accessories
30 New Construction Accessories PDXWS PDXWSEXT WALL SLEEVE Galvanized zinc coated steel is prepared in an 11-step process, then powder coated with a polyester finish and cured in an oven for exceptional durability. The wall sleeve is insulated for sound absorption and thermal ef- ficiency, 16" H...
Page 33 - New Construction Accessories; CONDUIT KIT WITH JUNCTION BOX; REPLACEMENT FILTER PACK
31 New Construction Accessories PXCJA CONDUIT KIT WITH JUNCTION BOX Hard wire conduit kit with junction box for 208/230V and 265V units (subbase not required). Kit includes a means of quick disconnect for easy removal of the chassis. *Required for 265V installations. PXFTA REPLACEMENT FILTER PACK Th...
Page 34 - SECOND THROUGH FIFTH YEAR; FIRST YEAR; Authorized FRIEDRICH Service Agency
32 Friedrich Air Conditioning Company 10001 Reunion Place, Suite 500 San Antonio, TX 78216 210.357.4400 www.friedrich.com ROOM AIR CONDITIONERS LIMITED WARRANTY ANY PART: If any part supplied by FRIEDRICH fails because of a defect in workmanship or material within twelve months from date of original...