Page 5 - THE RECIPIENTS OF THIS MANUAL
1592010870 XWEB3000_5000 EVO STP GB r1.0 2014.06.16.doc XW EB3000/5000 EVO 5/20 1. PRODUCT DISPOSAL (WEEE) With reference to Directive 2002/96/EC of the European Parliament and of the Council of 27 January 2003 and to the relative national legislation, please note that: There lies the obligation n...
Page 6 - PACKAGE; power cord
1592010870 XWEB3000_5000 EVO STP GB r1.0 2014.06.16.doc XW EB3000/5000 EVO 6/20 3. PACKAGE Before opening the package make sure that the packaging is intact and that there is no sign of impact or tampering. Before starting any operation, it is necessary to check that the XWEB-EVO box contains: 1 X...
Page 7 - INSTALLATION
1592010870 XWEB3000_5000 EVO STP GB r1.0 2014.06.16.doc XW EB3000/5000 EVO 7/20 4. INSTALLATION For installation, the XWEB-EVO system must not be opened in any way. If the box is opened, the warranty will lapse. XWEB-EVO can be installed in various ways based on the type of user interface access tha...
Page 9 - LED
1592010870 XWEB3000_5000 EVO STP GB r1.0 2014.06.16.doc XW EB3000/5000 EVO 9/20 LED LED Colour Description Pwr Green On when the system is powered HDD Blue On when the disc executes physical writing operations Rec Blue On when the system is recording data Ser1/Ser2 Blue On when the system is reading...
Page 10 - Product Literature’ section.; CONTROLLER INSTALLATION PROCEDURE; the network
1592010870 XWEB3000_5000 EVO STP GB r1.0 2014.06.16.doc XW EB3000/5000 EVO 10/20 5. INSTALLATION Refer to the INSTALLATION MANUAL for a description of the XWEB-EVO interfaces and electrical connections. A paper copy of it is included in the XWEB-EVO package and an electronic copy is provided by the ...
Page 11 - CONTROLLER CONFIGURATION; unique serial address; Enter “Menu
1592010870 XWEB3000_5000 EVO STP GB r1.0 2014.06.16.doc XW EB3000/5000 EVO 11/20 Keep the serial cable away from power cables and from any possible source of electromagnetic disturbance Do not connect the serial cable shielding to the earth connection of the electrical system Do not connect th...
Page 12 - GENERAL RULES, AND MINIMUM REQUIREMENTS; than local connectivity, we therefore recommend it,
1592010870 XWEB3000_5000 EVO STP GB r1.0 2014.06.16.doc XW EB3000/5000 EVO 12/20 6. LOCAL CONNECTIVITY The most common and frequently used user interface access is local access through a screen, mouse and keyboard, directly connected to XWEB-EVO. The system can also operate without having these peri...
Page 13 - CONNECTIVITY WITH CROSS CABLE; a pre-requisite to setting the connection
1592010870 XWEB3000_5000 EVO STP GB r1.0 2014.06.16.doc XW EB3000/5000 EVO 13/20 7.2 CONNECTIVITY WITH CROSS CABLE Local access from the PC is the fastest way to manage setup. It is possible to connect a PC to XW EB-EVO through the network interface supplied with an ‘RJ45 Ethernet connector’. The co...
Page 14 - SETTING UP THE REMOTE ACCESS CONNECTION
1592010870 XWEB3000_5000 EVO STP GB r1.0 2014.06.16.doc XW EB3000/5000 EVO 14/20 7.3 MODEM CONNECTIVITY ( “OR POINT-TO-POINT CONNECTION”) A modem connection makes it possible to set up a connection between PC and XW EB-EVO through the phone line. This type of connection is usually required when ther...
Page 15 - dixell; ’ as the user name
1592010870 XWEB3000_5000 EVO STP GB r1.0 2014.06.16.doc XW EB3000/5000 EVO 15/20 Enter the telephone number of the line that XWEB-EVO is connected to. If there is a switchboard and the number that needs to be dialled for the external line is 0, enter: 0,04379833. Enter ‘ dixell ’ as the user name an...
Page 16 - INTRANET (“OR LAN CONNECTION”) AND VPN CONNECTIVITY
1592010870 XWEB3000_5000 EVO STP GB r1.0 2014.06.16.doc XW EB3000/5000 EVO 16/20 7.4 INTRANET (“OR LAN CONNECTION”) AND VPN CONNECTIVITY This type of connection allows you to access XWEB-EVO from any PC connected to the local network. This type of connection must also be used to configure XWEB-EVO f...
Page 17 - INTERNET CONNECTIVITY ON PUBLIC IP; you will need a; (Internet Service Provider). Tell your ISP that you wish to; OPERATION; EVO package. Or, consult the “Product Literature“ section of
1592010870 XWEB3000_5000 EVO STP GB r1.0 2014.06.16.doc XW EB3000/5000 EVO 17/20 7.5 INTERNET CONNECTIVITY ON PUBLIC IP This type of connection allows you to access XWEB directly from any PC with an internet connection without having to install any additional software on your PC. Caution: the Intern...
Page 18 - SYSTEM DATA
1592010870 XWEB3000_5000 EVO STP GB r1.0 2014.06.16.doc XW EB3000/5000 EVO 18/20 9. SYSTEM DATA Fill in the table below, make a xerox copy and keep it near the XW EB. HostName ___________________________ [example: myXWEB001 ] IP Address ___________________________ [example: 192.168.0.123 ] Gateway _...