Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 2.0 Seller warrants the products it manufactures to be free from defects in material and workmanship for a period of eigh-teen (18) months from the date of shipment from Seller’s manufacturing plant or twelve (12) months from dat...
Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 2.0 READ CAREFULLY BEFORE OPERATING YOUR COMPRESSOR. The following instructions have been prepared to assist in operation of Vilter Vission 20/20 micro-controllers. The entire manual should be reviewed before attempting to operat...
TOC - 1 Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 2.0 Table of Contents Section Title Section Number Standard Vilter Warranty Statement ...................................................................................................... iImportant Message.................
TOC - 5 Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 2.0 Table of Contents / List of Tables and Figures Table/Figure Page Number Table 3-1. Digital I/O .............................................................................................................................
TOC - 7 Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 2.0 END OF TOC List of Tables and Figures Table/Figure Page Number Figure 20-1. Data Backup Screen - Save/Load ......................................................................................... 20-1Figure 20-2. Dat...
TOC - 8 Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 2.0 How to Use This Manual NOTE Manual revision should match software version. This manual contains instructions for the Vission 20/20 Operation & Service Manual. It has been divided into 28 sections. Section 1: Opera...
1 – 1 Figure 1-1. Operational Flow Charts (1 of 2) Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 2.0 Section 1 • Operational Flow Charts Volume and Capacity slides are less than 5% Oil Separator Temp >Oil Sep Start Trip Setpt Filter Diff Press < Start Filter Diff Trip ...
2 – 1 Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 2.0 Section 2 • Installation Recommendations Proper Wiring Sizing • Always size wire gauges as speci fi ed by the National Electrical Code (NEC) for electronic control devices. • For improved noise immunity, install one siz...
2 – 2 Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 2.0 Section 2 • Installation Recommendations Grounding • Continuous grounds must be run from the util- ity ground to the Vission 20/20, see Figure 2-3. Grounding. • Grounds must be copper or aluminum wire.• Never use condui...
2 – 3 Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 2.0 Section 2 • Installation Recommendations Figure 2-5. Correct Transformer Wiring Method Wiring Methods • Each Vission 20/20 panel should have its own indi- vidual control transformer, see Figure 2-5 and Figure 2-6. Figur...
2 – 4 Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 2.0 Section 2 • Installation Recommendations Best Practices • Do: • Keep AC wires away from circuit boards.• Always run conduit into the bottom or sides of an enclosure.• If the conduit must be placed in the top of an enclo...
3 – 1 Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 2.0 Section 3 • Hardware Architecture Overview The Vission 20/20 control panel utilizes X-86 PC technol-ogy with a Linux operating system. For hardware archi-tecture, see Figure 3-1. The Vission 20/20 has the following attr...
3 – 2 Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 2.0 Section 3 • Hardware Architecture Digital Input/Output (I/O) Refer to Table 3-1. Compressor Start Output:• When the Vission 20/20 signals the compressor to start, this output is energized. When the Vission 20/20 signals...
3 – 3 Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 2.0 Section 3 • Hardware Architecture Table 3-1. Digital I/O (1 of 2) Board I/O # Description Type 1 1 Compressor Start OUTPUT 1 2 Oil Pump Start OUTPUT 1 3 Capacity Increase OUTPUT 1 4 Capacity Decrease OUTPUT 1 5 Volume I...
3 – 4 Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 2.0 Section 3 • Hardware Architecture Remote Enabled Output:• This output is energized when the Vission 20/20 panel is enabled for remote control. If the compres-sor parameter does not satisfy start conditions or is placed ...
3 – 8 Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 2.0 Section 3 • Hardware Architecture Digital Output Boards The digital output board convert signals generated by the Vission 20/20 program into 120Vac signals that can be energize or signal other devices. All the signals a...
3 – 9 Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 2.0 Section 3 • Hardware Architecture Digital Input Boards The digital input board convert 120Vdc signals from ex-ternal devices to signals for the Vission 20/20 program. All the signals are digital in that the only two sta...
3 – 10 Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 2.0 Section 3 • Hardware Architecture Digital In-Out Boards The digital input - output board convert signals gener-ated by the Vission 20/20 program into 120Vac signals as well as detect external 120Vac inputs to signal th...
3 – 11 Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 2.0 Section 3 • Hardware Architecture Analog Input Boards The analog input board convert varying DC signals into a signal that can interpreted by the Vission 20/20 pro-gram. The signals are considered analog because the in...
3 – 12 Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 2.0 Section 3 • Hardware Architecture Analog Input Jumper Tables The following tables are used to con fi gure each channel of the analog input board signal type and range desired by the operator, see Table 3-4. CHANNEL 1 S...
3 – 14 Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 2.0 Section 3 • Hardware Architecture Analog Output Boards The Analog Output board convert signals from the Vission 20/20 program into a current ranging from 4mA to 20mA, see Figure 3-7. Voltage LEDs:• Marked in the diagra...
4 – 1 Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 2.0 Section 4 • Main Screen Figure 4-1. Main Screen Overview The Main Screen is the fi rst screen encountered when powering up the Vission 20/20 Panel, see Figure 4-1. This screen is designed as the starting point for all s...
4 – 2 Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 2.0 Section 4 • Main Screen Figure 4-2. Top Status Bar Top Status Bar The standard view of the status bar shows three pieces of information. From left to right , the bar shows the con-trol method, the current run mode, and ...
4 – 3 Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 2.0 Section 4 • Main Screen Figure 4-3. Parameter Bar Parameter Bar The main purpose of the Parameter Bar is to display the common operational parameters that the operator would be most concerned with. It also gives the ope...
4 – 4 Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 2.0 Section 4 • Main Screen Parameter Bar (Continued) Unit Start Button:• When pressed, a start dialog box will appear that will give the operator a number of run options; Auto, Manual, Remote, or Auto Sequencing, see Figur...
4 – 5 Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 2.0 Section 4 • Main Screen Bottom Status Bar The bottom status bar gives the operator easy access to some basic functions and information. The functions are available via the four button, see Figure 4-5. Maintenance Button...
4 – 6 Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 2.0 Section 4 • Main Screen Splash Screen The splash screen is the dynamic portion of the screen that will change as the operator navigates through the Vission 20/20 panel screen, see Figure 4-6. The main screen shows a gra...
5 – 1 Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 2.0 Section 5 • Menu Screen Overview The menu screen is the launching point to every other section of the Vission 20/20 panel software. Every screen navigated to from this screen will return to the menu screen upon exiting,...
5 – 2 Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 2.0 Section 5 • Menu Screen Instrument Calibration:• Navigates to the instrument calibration screen where the operator can calibrate all of the system sensors. Slide Calibration:• Navigates to the slide calibration screen w...
6 – 1 Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 2.0 Section 6 • Compressor Control Figure 6-1. Compressor Control Screen - Suction Pressure Control Overview The compressor control screen is where an operator can set the majority of the compressor settings. These setting ...
6 – 2 Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 2.0 Section 6 • Compressor Control Figure 6-2. Compressor Control Screen - Process Temperature Control the interval time given a near continuous movement of the capacity slide. Adjusting these setpoints can be use-ful in sl...
6 – 4 Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 2.0 Section 6 • Compressor Control Figure 6-4. Compressor Control Screen - Discharge Pressure Control
6 – 7 Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 2.0 Section 6 • Compressor Control Figure 6-8. Compressor Control Screen - Rapid Cycling VFD Control Rapid Cycling VFD Control The VFD page is where the operator can tune the motor VFD for desired rapid cycling VFD operatio...
6 – 8 Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 2.0 Section 6 • Compressor Control Oil Restriction Offset:• This is the differential offset around Oil Restriction Setpoint. For example, if Oil Restriction Setpoint is set to 1800 RPM and Oil Restriction Offset is set to 5...
6 – 9 Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 2.0 Section 6 • Compressor Control see Figure 6-9. If Pulldown is enabled, this feature will only function when the compressor is running in local Auto, Auto Sequencing mode and the Control mode is Suction Pressure 1. The P...
6 – 11 Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 2.0 Section 6 • Compressor Control Figure 6-10. Compressor Control Screen - Misc. 1 (Control Mode) Control Mode This drop down box gives the operator the ability to change the type of control mode such as suction pres-sure...
6 – 12 Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 2.0 Section 6 • Compressor Control Figure 6-11. Compressor Control Screen - Misc. 2 (Economizer & Hot Gas Bypass Control) Capacity Slide Triggered Outputs The Vission 20/20 offers two digital outputs that can be trigge...
6 – 14 Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 2.0 Section 6 • Compressor Control Figure 6-12. Compressor Control Screen - Oil Control & Liquid Injection Control of liquid being injected into the compressor the pre-viously mentioned setpoints have a slightly differ...
6 – 15 Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 2.0 Section 6 • Compressor Control Liquid Inj. Setpoint 1:• Setpoint at which the liquid solenoid will activate if in solenoid control or if the setting for the control vari-able for the PID is in liquid motorized value co...
7 – 1 Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 2.0 Section 7 • Alarms and Trips Overview The Alarms and Trips screen allows the operator to view and adjust settings for compressor safety and alarm set-tings. For Alarms and Trips Screen Pages refer to Figures 7-1, 7-2, 7...
7 – 3 Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 2.0 Section 7 • Alarms and Trips safety. After a time delay, (setting of the Oil Separator Temperature Safety Changeover timer), the Low Oil Separator Start Temperature is bypassed and Low Oil Separator Run Temperature alar...
7 – 4 Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 2.0 Section 7 • Alarms and Trips After a time delay, (setting of the High Superheat Temperature Safety Changeover timer), this safety is deactivated and the High Superheat Run Temperature alarm and safety setpoints become a...
7 – 5 Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 2.0 Section 7 • Alarms and Trips normal setpoint values after the Oil Pressure Bypass timer has expired. This time limit is set on the Timer menu screen. Run oil pressure is de fi ned as manifold pressure minus suction pres...
7 – 6 Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 2.0 Section 7 • Alarms and Trips Oil Pressure Safety Bypass timer times out. Low Oil Injection Temp Trip • This message will appear when the Oil Injection tem- perature falls below the Low Oil Injection Temperature trip set...
8 – 1 Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 2.0 Section 8 • Timers Overview The timers screen allows the operator to view and adjust timer settings associated with compressor operation. There are different types of timers that the operator should be aware of listed b...
8 – 3 Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 2.0 Section 8 • Timers for a time period that exceeds the setpoint of the Accumulative Anti-Recycle Timer, then when the compressor shuts down, it will be allowed to restart immediately. Compressor Interlock Bypass:• Once t...
9 – 2 Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 2.0 Section 9 • Compressor Scheduling Time:• This setpoint allows selection of Hours, Minutes and AM/PM values for an event. When time set for an event is achieved, control mode will get changed as selected for that event. ...
10 – 2 Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 2.0 Section 10 • Compressor Sequencing setpoint offset then sequencing decisions are made according to Unload Rate 1 timer. Unload Rate 2 Offset (outer):• De fi nes the outer Pressure/Temp setpoint offset to monitor compre...
10 – 3 Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 2.0 Section 10 • Compressor Sequencing Figure 10-3. Compressor Sequencing Screen - Page 3 Compressor Sequencing Table Compressor sequencing table menu allows operator to view and adjust settings those are used for compress...
10 – 4 Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 2.0 Section 10 • Compressor Sequencing Step:• This parameter would decide stepwise increment or decrement value in percentage of the compressor capacity. In the case when last step makes total ca-pacity greater than maximu...
10 – 5 Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 2.0 Section 10 • Compressor Sequencing Con fi guration Overview NOTE Slave Compressors should be con fi gured fi rst, then con fi gure the Master Compressor. The Con fi guration screen allows the operator to; • Enable / di...
10 – 6 Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 2.0 Section 10 • Compressor Sequencing At this point the slave compressor will begin multicast-ing its status information over the network at a rate of every 15 seconds. (After the Master Compressor is con- fi gured, the s...
10 – 7 Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 2.0 Section 10 • Compressor Sequencing COMPRESSOR SETUP FOR MASTER COMPRESSOR SEQUENCING NOTE The master compressor will ALWAYS be priority#1 compressor – and act as the trim compressor. So this must be taken into account ...
11 – 1 Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 2.0 Section 11 • Condenser Control Overview This screen allows the operator to view and adjust con-denser setpoint settings associated with condenser op-eration. This screen will only be active if the Condenser Control opt...
11 – 2 Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 2.0 Section 11 • Condenser Control Manual:• Mode for controlling condenser control operation manually. Operator controls the operation by manual stepping using an on/off toggle button at each step. Condenser Press:• This i...
11 – 3 Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 2.0 Section 11 • Condenser Control Low Speed Fan:• Allows steps to have option for time delay in case of fan spin down. Any of Out #1 to Out #4 can be se-lected as Low Speed Fan through combo box. E.g.: Let’s say Out #2 is...
12 – 1 Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 2.0 Section 12 • Service Options Overview The Service Option screen allows the operator the ability to force individual digital or analog outputs ON. This fea-ture is used for diagnostic purposes during initial setup and/o...
12 – 5 Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 2.0 Section 12 • Service Options Analog Outputs The Analog Output (AO) selections allow the operator to enter a desired value of the output then turn on the out-put, see Figure 12-5. The operator will have to measure the o...
13 – 1 Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 2.0 Section 13 • Instruments Calibration Overview The Instrument Calibration screen allows the operator to de fi ne how the Vission 20/20 will interpret the signal from any devices attached to the panel’s analog inputs. Th...
13 – 2 Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 2.0 Section 13 • Instruments Calibration Custom Device:• This option allows the operator to choose the mini- mum and maximum value of the instrument being used. Offset:• Once the two point calibration is completed, it is n...
13 – 4 Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 2.0 Section 13 • Instruments Calibration Remote Capacity The remote capacity input allows a system controller such as the PLC to control the capacity position during direct I/O control. Control Input:• This dropdown box is...
13 – 5 Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 2.0 Section 13 • Instruments Calibration Figure 13-5. Instruments Calibration Screen - Analog Inputs (Page 5) Offset:• Once the two-point calibration is completed, it is not uncommon for there to be a small error. By enter...
14 – 1 Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 2.0 Section 14 • Slide Calibration Overview The Slide Calibration screen is used in calibrating the slide actuators and to establish Vission 20/20 control parameters. It is important that the operator uses cau-tion while o...
14 – 2 Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 2.0 Section 14 • Slide Calibration mechanical stops for normal slide travel. These soft-ware limits purpose is to prevent the slide from actu-ally hitting the mechanical stops which could result in a number of undesirable ...
14 – 3 Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 2.0 Section 14 • Slide Calibration Calibrate Slide Valve Actuators Assuming that the actuator motors have not been cali-brated, the transmitter output of the actuator motor will fl uctuate wildly until they are calibrated....
14 – 5 Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 2.0 Section 14 • Slide Calibration Figure 14-4. Photo-chopper Press down on Photo-chopper to release tension from mo-tor mount. 8. Use the “+” button on the Vission 20/20 to drive the capacity slide to its maximum mechanic...
14 – 6 Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 2.0 Section 14 • Slide Calibration Command Shaft Rotation The following table describes the rotation direction required by the actuator. Every optical actuator has the ability to be wired to rotate in either direction. Ene...
14 – 7 Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 2.0 Section 14 • Slide Calibration Slide Valve Troubleshooting Guide The Analog output card of the Vission 20/20 produces a 4–20mA signal to any attached devices. However, it is not uncommon that small differences in the b...
14 – 9 Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 2.0 Section 14 • Slide Calibration Slide Valve Actuator Troubleshooting Guide Blink Code Vilter actuators communicate problems discovered by the internal diagnostics to the technician by LED blink codes. Only one blink cod...
15 – 1 Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 1.9 Section 15 • Trend Chart Overview This screen allows the operator to view and adjust set-tings for the trend chart, see Figure 15-1. Trend Chart Screen. Trending feature can be started & stopped from this screen. U...
15 – 2 Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 1.9 zoom level operator can view 3 minutes of trend data and Zoom In button will be inactive. At minimum zoom level operator can view full 120 hours of trend data and Zoom Out button will be inactive. Back/Forward:• These ...
15 – 3 Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 1.9 Figure 15-2. Trend Setup Screen Section 15 • Trend Chart Setup The operator can modify trending options through the Trend Setup screen, see Figure 15-2. Trend Setup Screen.Trend Setup screen can be accessed by pressing...
16 – 1 Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 2.0 Section 16 • Event List Overview This screen is designed to display compressor events in chronological order. The information available on the screen is valuable for understanding the operation of the compressor and tr...
17 – 1 Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 2.0 Section 17 • Input / Output Overview This screen displays “Live Data” of all the analog points and digital points being monitored. There are four pages of Input / Outputs (I/O) available for viewing, see Figures 17-1, ...
18 – 1 Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 1.9 Section 18 • Auxiliary Input / Output Overview The Auxiliary Input/Output (I/O) section of the Vission 20/20 gives the operator fl exibility to add peripheral instruments and/or devices such as motors, valves and solen...
18 – 2 Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 1.9 Digital Outputs The digital outputs section of the Auxiliary I/O screen allows an operator to con fi gure the auxiliary digital outputs, see Figure 18-2. The digital output can be con- fi gured to activate (go High, 12...
18 – 3 Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 1.9 Section 18 • Auxiliary Input / Output Figure 18-2. Auxiliary I/O Screen - Digital Outputs (Page 2) Figure 18-3. Auxiliary I/O Screen - Analog Inputs (Page 3)
19 – 1 Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 1.9 Section 19 • Configuration Overview The con fi guration screen is where most of the Vission 20/20 features are enabled and con fi gured. The initial setup of the Vission 20/20 will generally start here, see Figure 19-1...
19 – 4 Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 1.9 Section 19 • Configuration Compressor Control Vilter compressors typically run in one of two control modes, suction pressure or process temperature con-trol, see Figure 19-2. Suction Pressure Control:• This de fi nes t...
19 – 5 Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 1.9 Section 19 • Configuration Discharge Superheat Monitor:• Enables the discharge superheat safety algorithms. Discharge superheat monitor works only with R717. Discharge superheat monitor and suction superheat monitor fe...
19 – 6 Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 1.9 Section 19 • Configuration Motor Current Device The Vission 20/20 can read the motor current in a couple of different ways. The following selections de fi nes the method, see Figure 19-2. Current Transformer:• This de ...
20 – 2 Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 2.0 Section 20 • Data Backup Load:• Selecting load allows the operator to load data from a USB fl ash drive to the Vission 20/20 using the in- formation provided further down the screen. The bottom button will be labeled “...
20 – 3 Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 2.0 Section 20 • Data Backup Figure 20-2. Data Backup Screen - Migrate and Factory Reset Migrate Loading data from an older version of the Vission 20/20 software to a newer one can be complicated due to dif-ferences in dat...
20 – 4 Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 2.0 Section 20 • Data Backup Figure 20-3. Data Backup Screen - Setpoints Report Setpoints Report The setpoints report screen offers the operator the abil-ity to generate setpoints report for all screens. The re-ports are s...
21 – 1 Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 2.0 Section 21 • Maintenance Overview The maintenance screen is a convenient place to keep track of the maintenance performed and any upcom-ing maintenance recommended by Vilter. Based on this page, banners will be display...
21 – 3 Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 2.0 Section 21 • Maintenance Figure 21-3. Maintenance Screen - Chart
22 – 1 Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 2.0 Section 22 • User Access Overview The user access screen is where all operators go to log in. In the Vission 20/20, each screen has a security level, whereby allowing operators, technicians and/or supervi-sors the abil...
22 – 2 Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 2.0 Section 22 • User Access Login The login tab is where an operator will enter the users name and password in order to gain access to Vission 20/20 screens. Operators:• All operators that have been added to the Vission 2...
22 – 3 Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 2.0 Section 22 • User Access Operator Name:• This entry box is for the operator’s username who is to be added, removed or modi fi ed. The operator can either select the username from the operators win-dow or enter the user...
22 – 4 Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 2.0 Section 22 • User Access Table 22-1. Security Access Levels Security Access Levels Page User Level *Note Event List Level 0 - Input/Output States Level 0 - Trend Chart Level 0 - Help Level 0 - Alarms & Trips Level ...
23 – 2 Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 2.0 Section 23 • Help Screen Back:• Pressing the back button will rewrite the fi le/folder list with the previous folder level. Display Window:• This window displays the context of the manual.Fullscreen:• Pressing this but...
24 – 1 Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 2.0 Section 24 • Twin Screw Control Overview The Vission 20/20 is capable of operating a twin screw compressor from a number of different manufacturers. The Vission 20/20 currently operates as a twin screw controller in th...
24 – 2 Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 2.0 Section 24 • Twin Screw Control Operation Once the twin screw is con fi gured, its operation is very similar as the single screw and all options that are available for single screw con fi guration are also available fo...
24 – 3 Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 2.0 Section 24 • Twin Screw Control Figure 24-3. Slide Calibration - Twin Screw Bump Pop-Up Window Limit” setpoint to de fi ne an area within the mechani- cal stops for normal slide travel. These software limits purpose is...
24 – 4 Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 2.0 Section 24 • Twin Screw Control Twin Screw Oil Pressure The twin screw compressor has two separate oil pressure settings. They are named “Prelub Oil Pressure” and “Run Oil Pressure” in the Alarm and Trips Menu. Both of...
24 – 5 Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 2.0 Section 24 • Twin Screw Control Figure 24-5. Timers Menu - Twin Screw Control setpoints are forced into the Run Oil Pressure Alarm and Trip settings. By default, the Prelub Oil Pressure Alarm and Trip setpoints and the...
25 – 1 Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 2.0 Section 25 • Cool Compression Control Overview The cool compression compressor operation is similar to the standard single screw compressor units, except there is no external oil cooler to the unit. A blanket of liquid...
25 – 3 Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 2.0 Section 25 • Cool Compression Control • Auto load will be disengaged when one of the follow- ing conditions occur; • Pressure ratio reaches a value of 2.0 or greater.• Compressor has been running for 10 minutes (de fi ...
25 – 4 Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 2.0 Section 25 • Cool Compression Control Operational Differences from Single Screw Once the Cool Compression is con fi gured, most setup options available for a single screw are also available for Cool Compression. Howeve...
26 – 1 Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 2.0 Section 26 • Remote Oil Cooler Overview This screen allows the operator to view and adjust Remote Oil Cooler setpoint settings associated with Remote Oil Cooler operation, see Figure 26-1. This screen will only be acti...
26 – 3 Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 2.0 Section 26 • Remote Oil Cooler Maximum Speed:• This setpoint de fi nes the maximum speed in per- centage for Remote Oil Cooler VFD Fan at which it should run for continuous step delay time to increase Remote Oil Cooler...
A - 1 Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 2.0 Appendix A • Vission 20/20 Troubleshooting Guide Table A. Vission 20/20 Troubleshooting Guide Problem Solution Vission 20/20 does not boot up, no lights light on any boards. Check that 120VAC is run to circuit breaker C...
B - 1 Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 2.0 Appendix B • Vission 20/20 Application Procedures Contents Vission 20/20 Compressor Control Setup ............................................................................................... B-3 Vission 20/20 Compres...
B - 3 Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 2.0 Appendix B • Vission 20/20 Application Procedures Vission 20/20 Compressor Control Setup SCOPE Vission 20/20 programs – version 4550.1 and later. Pulldown The Pulldown feature provides a method of slowly pull-ing the su...
B - 4 Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 2.0 Appendix B • Vission 20/20 Application Procedures SETPOINT SELECTION EXAMPLE The following example is to illustrate the selection of setpoints for the Pulldown feature. The values picked are NOT representative of actual...
B - 5 Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 2.0 Appendix B • Vission 20/20 Application Procedures Pulldown OPERATION EXAMPLE Assumptions:• Compressor is off • Pulldown is selected • “Initiate Pulldown at Next Start” is selected • Current suction pressure = 80 PSIG• A...
B - 7 Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 2.0 Appendix B • Vission 20/20 Application Procedures Vission 20/20 Compressor Control Setpoints Setup SCOPE Vission 20/20 programs – version 4550.1 and later COMPRESSOR SETPOINT #1 AND SETPOINT #2 The Vission 20/20 allows ...
B - 8 Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 2.0 Appendix B • Vission 20/20 Application Procedures Figure B-3. Compressor Control Setpoint 1 and Setpoint 2 Setup
B - 9 Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 2.0 Appendix B • Vission 20/20 Application Procedures CONTROL MODE DROPDOWN BOX In Figure B-4, the Control Mode dropdown box allows selection of the active setpoints. To change from Setpoint 1 to Setpoint 2 being the active...
B - 10 Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 2.0 Appendix B • Vission 20/20 Application Procedures Figure B-5. Alarm and Trip Safety Setpoints for Setpoint 1 and Setpoint 2 SERIAL OR ETHERNET OPERATION AND SETPOINT 1 AND SETPOINT 2 SELECTION Refer to Table B-4, for r...
B - 11 Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 2.0 Appendix B • Vission 20/20 Application Procedures Vission 20/20 Compressor Sequencing Setup SCOPE Vission 20/20 programs – version 4550.1 and later OVERVIEW Compressor sequencing in the Vission 20/20 panel is carried o...
B - 12 Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 2.0 Appendix B • Vission 20/20 Application Procedures master compressor ONLY. (The slave compressor(s) load and unloading is setup in the master Compressor Sequencing menu). The Auto-cycle settings can also be setup for th...
B - 13 Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 2.0 Appendix B • Vission 20/20 Application Procedures The master compressor controls the slave compressors based on the master compressor control setpoints as well as the setpoints entered in the master compressor sequenci...
B - 14 Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 2.0 Appendix B • Vission 20/20 Application Procedures Unload Rate 2 Offset (Outer)• De fi nes the outer pressure setpoint offset to moni- tor compressor unload. If Suction pressure / proc temp goes surpasses the Control Se...
B - 16 Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 2.0 Appendix B • Vission 20/20 Application Procedures (decrease) the slave compressor capacity . When a slave compressor has been unloaded to its MIN CAP setpoint, and the suction pressure is still less than a value of unl...
B - 17 Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 2.0 Appendix B • Vission 20/20 Application Procedures Auto sequencing can be started (from the master com-pressor) by selecting the green Unit Start button and pressing the “Auto Seq” button. WALK-THROUGH OF SEQUENCING LOA...
B - 18 Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 2.0 Appendix B • Vission 20/20 Application Procedures In this example, during unloading cycle when suction pressure falls below a value less than con fi gured unload rate 1 value (20 – 2 = 18 psig) for the time period of t...
B - 19 Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 2.0 Appendix B • Vission 20/20 Application Procedures Database Backup Procedure Upgrading the program in the 20/20 panel normally in-volves replacing the fl ashcard. Note that all compressor operation setpoints, calibratio...
B - 21 Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 2.0 Appendix B • Vission 20/20 Application Procedures Flashcard Replacement Procedure Before powering down to replace the fl ashcard, copy down all of the follow operating setpoints and con fi gu- ration information. RECOR...
B - 26 Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 2.0 Appendix B • Vission 20/20 Application Procedures Compressor Control Control setpoint level 0 Set/Change/Modify within supervisor set constraints All control setpoints level 1 All remaining control setpoints are modi f...
B - 27 Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 2.0 Appendix B • Vission 20/20 Application Procedures Remote Control and Monitoring of 20/20 Panel INTRODUCTION This document provides the reader with guidelines to successfully communicate to and integrate with the Vilter...
B - 28 Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 2.0 Appendix B • Vission 20/20 Application Procedures Figure B-12. Serial Communication Ports on Single Board Computer P12 = RS485 Serial Modbus RTU connector *P14, P18 = USB Serial Modbus RTU connectorsP8 = Ethernet RJ45 ...
B - 30 Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 2.0 Appendix B • Vission 20/20 Application Procedures Figure B-14. Selecting USB Port for Serial Communication The Vission 20/20 panel allows designating the USB port to be used for serial Modbus RTU communication from the...
B - 31 Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 2.0 Appendix B • Vission 20/20 Application Procedures NETWORK TOPOLOGY RS422/RS485 Networking Topology Many articles have been written about the different to-pologies of RS422/RS485 networks. Vilter recommends that a daisy...
B - 32 Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 2.0 Appendix B • Vission 20/20 Application Procedures USING THE DEVICE AS A NETWORK ISOLATOR/ REPEATER (Reference Figure B-17)1. A DC power supply is required to power the device ( +10vDC to +30vDC) 2. Dip switches on each...
B - 34 Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 2.0 Appendix B • Vission 20/20 Application Procedures ETHERNET NETWORK TOPOLOGY The con fi guration of the plant Ethernet network might be dictated by the plant IT department. One com-mon con fi guration is the star type t...
B - 35 Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 2.0 Appendix B • Vission 20/20 Application Procedures ADDITIONAL NETWORK CONFIGURATIONS FOR ACCESS VIA INTERNET There are many network con fi gurations that will allow access to the Vilter 20/20 panels via an internet conn...
B - 36 Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 2.0 Appendix B • Vission 20/20 Application Procedures Example 2 In Figure B-21, this example shows a PC connected to the internet, running a VNC client program which accesses the Vission 20/20 panels by specifying an IP ad...
B - 37 Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 2.0 Appendix B • Vission 20/20 Application Procedures Example 4 In Figure B-23, this example shows a hybrid network. An off campus PC and smartphone is connected to the in-ternet, running VNC client programs which accesses...
B - 38 Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 2.0 Appendix B • Vission 20/20 Application Procedures REMOTE COMPRESSOR CONTROL VIA COMMUNICATIONS A compressor control scheme that is accomplished via communications must follow some general rules. The Vission 20/20 panel...
B - 42 Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 2.0 Appendix B • Vission 20/20 Application Procedures Figure B-25. Con fi guration screen - Page 1 CONFIGURATION SCREEN SETUP FOR REMOTE CONTROL THROUGH COMMUNICATIONS (Reference the “Communication” section of Figure B-25)...
B - 43 Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 2.0 Appendix B • Vission 20/20 Application Procedures registers within the Modbus range of 40500 through 40513 can occur. If Remote Lock is ON, then writes within this region cannot occur. These registers are the compresso...
B - 44 Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 2.0 Appendix B • Vission 20/20 Application Procedures Modbus Register 40502 - Remote Capacity Control Selection • 0 = Auto Capacity Control. This selection de fi nes that the 20/20 will control compressor capacity from its...
B - 45 Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 2.0 Appendix B • Vission 20/20 Application Procedures NOTE Both Process Temp Control and Suction Pressure Control must both be enabled from the Con fi guration screen to do this. Modbus Register 40503 - Auto Capacity Contr...
B - 46 Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 2.0 Appendix B • Vission 20/20 Application Procedures scale) away from the current position, then en-ergize the capacity slide for a time that is propor-tional to the amount it is away from the new target position. To say ...
B - 47 Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 2.0 Appendix B • Vission 20/20 Application Procedures power is restored, which means it will not accept any “writes” via communication, within the Compressor Command register region, until someone walks up to the panel and...
B - 49 Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 2.0 Appendix B • Vission 20/20 Application Procedures Phoenix Contact PSM-ME-RS485/RS485-P Isolator The Phoenix Contact isolator/repeater is used to electri-cally isolate the RS485 signal from the network and to improve th...
B - 50 Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 2.0 Appendix B • Vission 20/20 Application Procedures Test 1 The fi rst test measured the noise on the active net- work WITHOUT the Phoenix Contact PSM-ME isolator installed in the network, see Figure B-26. The Phoenix Con...
B - 51 Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 2.0 Appendix B • Vission 20/20 Application Procedures Vessel Level Control Setup for 20/20 Panel INTRODUCTION This document provides guidelines to successfully setup a vessel level control function in the Vilter 20/20 con-...
B - 52 Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 2.0 Appendix B • Vission 20/20 Application Procedures Step 2: Selection and Naming of Auxiliary Analog Outputs used for Level Control Navigate to page 5 of the Con fi guration screen and se- lect the analog output(s) that ...
B - 53 Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 2.0 Appendix B • Vission 20/20 Application Procedures Step 3: Selection and Naming of Auxiliary Analog Inputs used for Level Control Navigate to page 4 of the Con fi guration screen and se- lect the analog inputs(s) that w...
B - 54 Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 2.0 Appendix B • Vission 20/20 Application Procedures Step 4: Instrument Calibration Screen Setup of Auxiliary Analog Inputs. Now that the auxiliary analog inputs have been selected and named, the scaling for the inputs ne...
B - 55 Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 2.0 Appendix B • Vission 20/20 Application Procedures Step 5: Auxiliary I/O (Analog Inputs) Alarm and Trip Setup If an alarm or trip setpoint for the vessel level is desired, then navigate to Auxiliary I/O page 3 and setup...
B - 56 Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 2.0 Appendix B • Vission 20/20 Application Procedures Step 6: Setup of Analog Output for Vessel Level Control – PID Level Control Navigate to Auxiliary I/O page 6 and setup analog output control for vessel level. Figure B-...
B - 57 Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 2.0 Appendix B • Vission 20/20 Application Procedures With the above setting, the response of the Aux1: Chiller Level 4,20 Output is seen to be; % Level Input Aux1 Analog Output 50 % = 4 ma (fully closed position) 45 % = 8...
B - 59 Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 2.0 Appendix B • Vission 20/20 Application Procedures VPLUS (AC Motor) Setup Procedure for 20/20 Panel INTRODUCTION This document provides guidelines to setup AC Motor VPLUS oil cooling system control on the Vission 20/20 ...
B - 61 Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 2.0 Appendix B • Vission 20/20 Application Procedures VISSION 20/20 SOFTWARE SETUPStep 1: Con fi guration Screen Selection of Installed Boards Log on and navigate to the Con fi guration screen, page number 6. Insure that a...
B - 62 Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 2.0 Appendix B • Vission 20/20 Application Procedures Step 2: Setup and selection of Oil Cooling from page 2 of the Con fi guration screen The oil cooling VPLUS algorithm must be enabled from the con fi guration screen. Th...
B - 63 Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 2.0 Appendix B • Vission 20/20 Application Procedures Step 3: Setup and selection of VPLUS / Motorized Valve Con fi guration. The oil cooling VPLUS control parameters must now be setup. Navigate to the last page of the Com...
B - 66 Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 2.0 Appendix B • Vission 20/20 Application Procedures Figure B-42. Temperature Controller Wiring Removed After removing the temperature controller wiring, the wiring diagram will look like Figure B-42.
B - 67 Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 2.0 Appendix B • Vission 20/20 Application Procedures HARDWARE WIRING Interconnect wiring between the Vission 20/20 panel and the VPLUS panel now needs to be done. 1. First make sure that the VPLUS panel and the Vission 20...
B - 69 Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 2.0 Appendix B • Vission 20/20 Application Procedures VISSION 20/20 SOFTWARE SETUP Step 1: Con fi guration Screen Selection of Installed Boards Logon and navigate to the Con fi guration screen, page number 6. Insure that a...
B - 70 Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 2.0 Appendix B • Vission 20/20 Application Procedures Step 2: Setup and selection of Oil Cooling from page 2 of the Con fi guration screen The oil cooling VPLUS algorithm must be enabled from the con fi guration screen. Th...
B - 73 Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 2.0 Appendix B • Vission 20/20 Application Procedures Vilter Address Ethernet IP Address Modbus Address Data Type Value Mode Lower Range Higher Range Digital Inputs 0 N50:0 40001 Compressor Interlock INT 0 = OFF, 1 = ON Re...
B - 76 Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 2.0 Appendix B • Vission 20/20 Application Procedures 83 N54:3 40253 Pressure Ratio F-INT Read 84 N54:4 40254 Volume Ratio F-INT Read 85 N54:5 40255 Superheat Discharge Temp. F-INT Read 86 N54:6 40256 Superheat Suction Tem...
B - 78 Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 2.0 Appendix B • Vission 20/20 Application Procedures 104 N55:15 40415 Refrigerant ENUM "0 = R11 1 = R122 = R133 = R224 = R1135 = R1146 = R134a7 = R290 - Propane8 = R404a9 = R50010 = R50211 = R50312 = R50713 = R71714 =...
B - 80 Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 2.0 Appendix B • Vission 20/20 Application Procedures 126 N57:4 40554 Cap Dec Proportional Band Setpoint #1 F-INT Read-Write 0.5 20.0 127 N57:5 40555 Setpoint #2 (Pressure, Temp) F-INT Read-Write (-15.0, -100.0) (200.0, 15...
B - 81 Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 2.0 Appendix B • Vission 20/20 Application Procedures 148 N58:8 40578 Stop Delay Time Setpoint #2 INT Read-Write 0 300 149 N58:9 40579 Minimum Slide Position Setpoint #2 INT Read-Write 0 100 Pumpdown 150 N59:0 40590 Stop P...
B - 83 Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 2.0 Appendix B • Vission 20/20 Application Procedures 189 N62:2 40642 Slide Valve Setpoint #1 Enabled INT 0 = Disabled, 1 = Enabled Read 190 N62:3 40643 Slide Valve Setpoint #2 Enabled INT 0 = Disabled, 1 = Enabled Read 19...
B - 86 Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 2.0 Appendix B • Vission 20/20 Application Procedures 265 N65:6 40836 High Filter Diff. Run Press. Alarm F-INT Read 266 N65:7 40837 High Filter Diff. Run Press. Trip F-INT Read 267 N65:8 40838 High Motor Amps Alarm F-INT R...
B - 87 Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 2.0 Appendix B • Vission 20/20 Application Procedures 288 N66:17 40917 High Superheat Temp Safety Changeover (minutes) INT Read Compressor Scheduling (Military Time) 289 N67:0 41000 Sunday Event #1 Control Mode ENUM Read-W...
Emerson Manuals
-
Emerson LD195EM8
User Manual
-
Emerson EWR20V4
User Manual
-
Emerson EWR20V4
Manual
-
Emerson SLC195EM8
User Manual
-
Emerson SLC195EM8
Manual
-
Emerson CR202EM9
User Manual
-
Emerson HD14070
User Manual
-
Emerson RLC320EM9
User Manual
-
Emerson LC320EM9
User Manual
-
Emerson LC320EM9
Manual
-
Emerson PD6922
User Manual
-
Emerson PD6922
Manual
-
Emerson EPT427D
User Manual
-
Emerson EPT427D
Manual
-
Emerson 400 VMC
User Manual
-
Emerson 400 VMC
Manual
-
Emerson CF960CK
User Manual
-
Emerson MICRO MOTION 2700
Installation Manual
-
Emerson CF787AP00
User Manual
-
Emerson CF787AP00
Manual