Liebert Nfinity UPS Guide Specification 4kVA –20kVA (208/120 or 240/120) 4/03 Rev 2 SL-23956 2 D. Automatic Restart - After a utility AC power outage and complete battery discharge, the UPS will automatically restart and resume supplying power to the critical load. In addition, the battery charger w...

Page 3 - : To within 1% of steady state output voltage within 96

Liebert Nfinity UPS Guide Specification 4kVA –20kVA (208/120 or 240/120) 4/03 Rev 2 SL-23956 3 B. Voltage Regulation : +/- 3% steady state. C. Frequency Regulation : 60 Hz, +/- 0.5%. D. Frequency Slew Rate : field selectable from 0.5 to 5.0 Hz maximum per second. E. Bypass Frequency Synchronization ...

Page 4 - The UPS is cooled by forced air via internally mounted fans.

Liebert Nfinity UPS Guide Specification 4kVA –20kVA (208/120 or 240/120) 4/03 Rev 2 SL-23956 4 1.5 USER DOCUMENTATION The specified UPS system is supplied with one (1) user's manual. Manuals include installation drawings and instructions, a functional description of the equipment with block diagrams...