Page 2 - CONTENTS
2 IP2046/IM Nov 2006 CONTENTS Page 1. Introduction 3 2. The MSP400RH ultrasonic level transmitter 3 2.1 Type numbering system 3 2.2 Pressure Equipment Directive 4 2.3 Specifications 4 3. Installation 6 3.1 Location of the MSP400RH transmitter 6 3.1.1 General considerations 6 3.1.2 Liquid surface con...
Page 6 - must not; must; not
6 IP2046/IM Nov 2006 3.0 Installation Important safety notice : The MSP400 is designed for safe area use only, and must not be installed in a hazardous area, even if the power is supplied through a barrier device. General a. Installation must be carried out by suitably trained personnel in accordanc...
Page 15 - all
15 IP2046/IM Nov 2006 4.4 Setting up for the chosen application - the Main Menu. Refer now to the main menu structure chart in Appendix A. It is important to note that MSP400 programming is most easily accomplished by first selecting the dutythe transmitter is to perform.Once a duty is selected (see...
Page 17 - TIP
17 IP2046/IM Nov 2006 4.4.3 Setting the correct bottom reference Screen display: b.rEF Factory default value:MSP400RH-B28 11 MSP400RH-N28 36 The MSP400 leaves the factory with the bottom reference pre-programmed to the maximum range of theinstrument, either 11m or 36ft. To change the bottom referenc...
Page 28 - together
28 IP2046/IM Nov 2006 4.6 Loop Test : See also Appendix A3 “tESt” The MSP400 has the facility to cycle through it’s programmed operating range without any change in theliquid level, causing the current output and relays to cycle through their normal operation.Also, the MSP400 can be programmed to fi...
Page 36 - LEUEL; duty; PV
36 IP2046/IM Nov 2006 APPENDIX A1 MAIN MENU : PROGRAMMING b.rEF 4 PB1 4 20 PB1 20 d PB1 Display Bottom Ref. Display 4mA Level Display 20mA Level Display Damping PB2 Edit Bottom Ref. PB2 Edit 4mA Level PB2 Edit 20mA Level PB2 Edit Damping PB2 Display Bottom Ref. PB2 Display 4mA Level PB2 Display 20mA...
Page 37 - APPENDIX A1
37 IP2046/IM Nov 2006 APPENDIX A1 Cont’d / ... SEt 4 PB1 Display PV for 4mA Flash “4” with PV PB2 r1. On Display RL1 On Pt Edit RL1 On Pt PB2 Display RL1 On Pt PB2 PB1 r1. On PB2 PB2 r1.OFF Display RL1 Off Pt Edit RL1 Off Pt PB2 Display RL1 Off Pt PB2 PB1 r1.OFF PB2 PB2 PB3 PB2 PB3 Display PV for 4m...
Page 39 - CyCLE; LOOP
39 IP2046/IM Nov 2006 APPENDIX A3 COMMISSIONING / LOOP TEST MENU PB1 Loop Test (tESt) PB2&3 for 2 sec PV Eng Setup (Eng) PB2 for 2 second PV PB2 Diagnostics (diAg) PB2 CyCLE Set Distance =Bottom Ref Toggle Ramping On/Off PB2 CyCLE PB2 PB2 LOOP Recall Fixed Current Edit desired current value PB2 ...
Page 42 - DEFAULT VALUE LISTING : ENGINEERING PARAMETERS
42 IP2046/IM Nov 2006 DEFAULT VALUE LISTING : ENGINEERING PARAMETERS Default value shown are for the metric model MSP400RH-B28.Where different, values for the imperial model MSP400RH-N28 are shown in brackets. Loop Test PB2&3 for 2 sec PV Eng Setup PB2 for 2 sec PV PB2 PB1 t.HoLd t.HoLd LE PB1 L...
Page 48 - Instruction & maintenance leaflet
Instruction & maintenance leaflet IP2046IM, Rev. AA November 2006 MSP400RH The Emerson logo is a trade mark and service mark of Emerson Electric Co. Rosemount is a registered trademark of Rosemount Inc. Mobrey is a registered trademark of Mobrey Ltd.All other marks are the property of their resp...