Page 3 - TABLE OF CONTENTS; Properly Grounded (Earthed) Equipment Provides Multiple
i TABLE OF CONTENTS I MPORTANT S AFETY I NSTRUCTIONS . . . . . . . . . . . . . . . . . . . . . 1 G LOSSARY OF S YMBOLS . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 I NTRODUCTION AND S YSTEM D ESCRIPTION . . . . . . . . . . . . . . . 4 System Description . . . . . . . . . . . . . . . . ....
Page 5 - SAVE THESE INSTRUCTIONS; WARNING
1 I MPORTANT S AFETY I NSTRUCTIONS SAVE THESE INSTRUCTIONS This manual contains important instructions that should be followed during installation and operation of the 2U Hardwire POD™. This product is designed for commercial / industrial use only, with Liebert UPS systems. It is not intended for us...
Page 6 - Specifications on page 15
2 ! CAUTION This device receives power from multiple sources. Before servicing this device, remove all connections and cut power from the utility branch input. Before servicing the UPS, follow “Maintenance of UPS” instructions in the user manual for your UPS. ! CAUTION This device is for use in a cl...
Page 7 - Equipment grounding conductor
3 G LOSSARY OF S YMBOLS Equipment grounding conductor Bonded to ground Electric phase Indicates AC input Indicates AC output
Page 8 - System Description; Figure 1; CAUTION
4 I NTRODUCTION AND S YSTEM D ESCRIPTION Congratulations on your choice of the Liebert 2U Hardwire POD™ . The 2U Hardwire POD provides maintenance bypass capability as well as power output distribution. The Liebert 2U Hardwire POD can be used on UPS in the rack mount or tower configuration.The Liebe...
Page 9 - Figure 3
5 R ACK M OUNT I NSTALLATION 1. Rack mount installation of the 2U POD is possible with the use of the rack mounting brackets (shipped with the POD). See Figure 3 . 2. The rack mount brackets allow you to rack mount the POD in a 19" enclosure (23" to 19" rack adapters are available as opt...
Page 10 - GXT 2U UPS; Figure 4; This manual provides instructions for the 2U POD only.
6 I NSTALLATION ON GXT 2U UPS 1. Unpack the 2U POD carefully, noting the packing method. Retain the box and packing material for possible future shipments. 2. Visually inspect the 2U POD for freight damage. Report damage to the carrier and your local dealer or Liebert representative. 3. Verify that ...
Page 11 - Electrical Installation Considerations; Figure 5; Table 1; FRONT VIEW
7 H ARDWIRE C ONNECTIONS Electrical Installation Considerations The front and bottom of the POD provide alternate conduit entry points for both the UTILITY and LOAD connections. Figure 5 Conduit entry ! CAUTION This UPS must be installed by competent electrical personnel and wired in accordance with...
Page 12 - compartments by opening the top and rear of the POD. Each access; Figure 6; Electrical Connections; The wiring compartments provide terminal blocks to connect Line,; details the standard current ratings.
8 Wiring access doors on each end of the POD allow access to the wiring compartments by opening the top and rear of the POD. Each access door is retained using two Phillips head screws. The center screw and center panel should not be removed. Figure 6 Removing wiring access doors Electrical Connecti...
Page 13 - Wiring Instructions
9 Wiring Instructions 1. Remove the wiring access doors by removing the two Phillips head screws that secure them. 2. Determine which of the two available conduit entry points are to be used. Knock out the conduit entry hole for the location and size of conduit to be used. 3. Connect conduit bushing...
Page 14 - Figure 7
10 A PPLY F EED P OWER 1. Next attach the POD to the securing brackets (see Figure 7). The POD can be installed to face one of three different directions utiliz- ing the same mounting procedures. Select the direction of mount- ing to accommodate the conduit entry connections. Figure 7 Attaching POD ...
Page 16 - Utility; the connected loads if in UPS position.; UPS Available; from utility power back to UPS output power.; Figure 8
12 I NDICATOR L AMPS Utility This amber lamp is illuminated when utility power is present. It sig- nals that you may transfer the loads to maintenance bypass (UTILITY mode) operation via the rotary switch. During a utility power outage, this light will be off and the UPS will supply battery back-up ...
Page 17 - PERATION; Transfer to Maintenance Bypass; Troubleshooting; Transfer to UPS; shooting
13 O PERATION Transfer to Maintenance Bypass To transfer to maintenance bypass (UTILITY) from UPS, follow the following steps:1. Ensure the Utility lamp (amber lamp) is illuminated. If the lamp is not illuminated, refer to the Troubleshooting section. 2. Transfer the rotary switch from UPS to UTILIT...
Page 18 - ROUBLESHOOTING
14 T ROUBLESHOOTING Problem Cause Solution UTILITY lamp (amber) not illuminated. UTILITY not present. Call qualified service personnel to restore power. Utility Branch Circuit Breaker may be open. Verify that the branch circuit breaker is closed. 2U Hardwire POD input power not connected to UTILITY....
Page 19 - PECIFICATIONS; Product Warranty Registration; Quick Links; See Model Label on POD
15 S PECIFICATIONS This POD is intended for use with a UPS meeting all of the following requirements:• UPS input cord is compatible with the rating and type of receptacle on the POD labeled “CONNECT UPS LINE CORD HERE.” • UPS output receptacle is compatible with the POD input power con- nector label...
Page 22 - The Company Behind the Products; OWER; U Hardwire PODTM
Technical Support / Service Web Site www.liebert.com Monitoring 800-222-5877 [email protected] Outside the US: 614-841-6755 Single-Phase UPS 800-222-5877 [email protected] Outside the US: 614-841-6755 Three-Phase UPS 800-543-2378 [email protected] Environmental Systems 800-543-2778 Outsid...