Emerson MODBUS IP - Manuals
Emerson MODBUS IP – Manual in PDF format online.
Manuals:
Manual Emerson MODBUS IP
Summary
i TABLE OF CONTENTS 1.0 L IEBERT E QUIPMENT C OMPATIBILITY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 1.1 What’s New in This Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 1.2 Connectivity to Lie...
ii Table 18 Liebert XDC ™ - Status and Coil . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58 Table 19 Liebert XDC ™ - Input and Holding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59 Table 20 Liebert XDP ™ - Status...
iii Table 51 Liebert Nfinity ® - Input and Holding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 140 Table 52 Liebert NX ™ - Status and Coil . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 141 Table 53 Liebert NX ™ - Input...
iv Table 79 Extra Notes to Table 78 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 235 Table 80 Liebert Challenger 3000 ™ , Liebert Challenger ITR ™ , Liebert CW ™ , Liebert Deluxe System/3 ™ , Liebert DS ™ , Liebert DSE ™ , Liebert HPM ™ , Lieber...
Liebert Equipment Compatibility - What’s New in This Manual 1 Liebert ® IntelliSlot ® Modbus/BACnet IP 1.0 L IEBERT E QUIPMENT C OMPATIBILITY 1.1 What’s New in This Manual Emerson Network Power ® has introduced a new Liebert IntelliSlot ® card platform—the Liebert IntelliSlot Unity ™ card. This plat...
Liebert Equipment Compatibility - Compatibility with Liebert Equipment Liebert ® IntelliSlot ® Modbus/BACnet IP 2 1.3 Compatibility with Liebert Equipment Table 1 Liebert Equipment and Compatible Liebert IntelliSlot ® Cards Product Supported Refer to Tables: Controller / Protocol Compatible Card Par...
Modbus Communications - Implementation Basics 5 Liebert ® IntelliSlot ® Modbus/BACnet IP 2.0 M ODBUS C OMMUNICATIONS 2.1 Implementation Basics Modbus protocol provides control and data acquisition, through query and response, between master and slave devices. This protocol comprises the rules for co...
Modbus Communications - RTU Framing Liebert ® IntelliSlot ® Modbus/BACnet IP 6 2.3.2 Function Code The function code field tells the addressed slaves what function to perform. Function codes are designed to invoke a specific action by the slave device. The function code ranges from 1 to 127.Liebert ...
Modbus 485 and Modbus IP Protocols - Thermal Management Products 7 Liebert ® IntelliSlot ® Modbus/BACnet IP 3.0 M ODBUS 485 AND M ODBUS IP P ROTOCOLS 3.1 Thermal Management Products Table 6 Liebert Challenger 3000 ™ , Liebert Challenger ITR ™ , Liebert CW ™ , Liebert Deluxe System/3 ™ , Liebert DS ™...
Modbus 485 and Modbus IP Protocols - Thermal Management Products Liebert ® IntelliSlot ® Modbus/BACnet IP 12 Condenser Circuit Unspecified General Event 10494 — 1 Active on Alarm 3, 4, 5, 6 Input Undervoltage 1 10500 — 1 Active on Alarm 6 Input Undervoltage 2 10501 — 1 Active on Alarm 6 Input Underv...
Modbus 485 and Modbus IP Protocols - Thermal Management Products 13 Liebert ® IntelliSlot ® Modbus/BACnet IP Table 8 Liebert Challenger 3000 ™ , Liebert Challenger ITR ™ , Liebert CW ™ , Liebert Deluxe System/3 ™ , Liebert DS ™ , Liebert DSE ™ , Liebert HPM ™ , Liebert PeX ™ - Input and Holding Cont...
Modbus 485 and Modbus IP Protocols - Thermal Management Products 25 Liebert ® IntelliSlot ® Modbus/BACnet IP Instantaneous Power 1 30860 — 1 - W 6 Instantaneous Power 2 30861 — 1 — W 6 Instantaneous Power 3 30862 — 1 — W 6 Instantaneous Power 4 30863 — 1 — W 6 Instantaneous Power 5 30864 — 1 — W 6 I...
Modbus 485 and Modbus IP Protocols - Thermal Management Products Liebert ® IntelliSlot ® Modbus/BACnet IP 26 Table 10 Liebert Challenger 3000 ™ , Liebert Challenger ITR ™ , Liebert CW ™ , Liebert Deluxe System/3 ™ , Liebert DS ™ , Liebert DSE ™ , Liebert HPM ™ , Liebert PeX ™ - Glossary Controller L...
Modbus 485 and Modbus IP Protocols - Thermal Management Products 39 Liebert ® IntelliSlot ® Modbus/BACnet IP Table 11 Liebert CRV ™ - Status and Coil Controller Liebert iCOM ® v4 Data Label Status Coil Number of Bits Scale Notes / Units Supply Air Over Temperature 10001 — 1 — Active on Alarm Supply ...
Modbus 485 and Modbus IP Protocols - Thermal Management Products 49 Liebert ® IntelliSlot ® Modbus/BACnet IP Table 14 Liebert HPC ™ (Chiller) - Status and Coil Controller Liebert iCOM ® v4 Data Label Status Coil Number of Bits Notes Extra Notes Compressors Compressor Not Stopping 10001 — 1 Active on...
Modbus 485 and Modbus IP Protocols - Thermal Management Products 55 Liebert ® IntelliSlot ® Modbus/BACnet IP Table 16 Extra notes key to Table 15 Number Description 1 This point is supported on iCOM_SC31 2 This point is supported on iCOM_SC101 Table 17 Liebert HPC ™ (Chiller) - Glossary Controller L...
Modbus 485 and Modbus IP Protocols - Thermal Management Products Liebert ® IntelliSlot ® Modbus/BACnet IP 58 Table 18 Liebert XDC ™ - Status and Coil Controller Liebert iCOM ® v4 Data Description Status Coil Number of Bits Scale Notes / Units Pump 1 Loss of Flow 10001 — 1 — Active on Alarm Pump 2 Lo...
Modbus 485 and Modbus IP Protocols - Thermal Management Products Liebert ® IntelliSlot ® Modbus/BACnet IP 60 System Status 30422 — 1 — 1 = Normal Operation 2 = Startup 8 = Normal with Warning 16 = Normal with Alarm 32 = Abnormal Operation System Control Mode 30423 — 1 — 0 = Internal (Auto) 1 = Exter...
Modbus 485 and Modbus IP Protocols - Thermal Management Products Liebert ® IntelliSlot ® Modbus/BACnet IP 64 Hot Aisle Over Temp Threshold 30459 40459 1 — Units : deg C Hot Aisle Over Temp Threshold 30460 40460 1 — Units : deg F Hot Aisle Under Temp Threshold 30461 40461 1 — Units : deg C Hot Aisle ...
Modbus 485 and Modbus IP Protocols - Thermal Management Products 75 Liebert ® IntelliSlot ® Modbus/BACnet IP Table 23 Liebert DS ™ and Liebert PeX ™ - Status and Coil Controller Liebert iCOM ™ v3 Data Description Status Coil Number of Bits Scale Notes / Units Sleep on Monday 10001 1 1 — — Sleep on T...
Modbus 485 and Modbus IP Protocols - Thermal Management Products 81 Liebert ® IntelliSlot ® Modbus/BACnet IP Table 25 Liebert XDF ™ - Status and Coil Controller Liebert iCOM ® v3 Data Description Status Coil Number of Bits Scale Notes / Units Temperature Indication 1 10011 11 1 — — Unit Control — 25...
Modbus 485 and Modbus IP Protocols - Thermal Management Products 85 Liebert ® IntelliSlot ® Modbus/BACnet IP Table 28 Liebert DataMate ™ , Liebert Mini-Mate Plus ™ , Liebert Mini-Mate2 ™ - Input and Holding - L0B Controller Small Systems - L0B Liebert Products Liebert DataMate Liebert Mini-Mate Plus...
Modbus 485 and Modbus IP Protocols - Thermal Management Products Liebert ® IntelliSlot ® Modbus/BACnet IP 90 Table 31 Liebert Atlas Air ™ , Liebert Atlas PEC ™ , Liebert LECS 15 ™ - Input and Holding - C10 2-step Controller C10 Liebert Products Liebert Atlas Air Liebert Atlas PEC Liebert LECS 15 Ava...
Modbus 485 and Modbus IP Protocols - Power Distribution and Power Conditioning Products Liebert ® IntelliSlot ® Modbus/BACnet IP 94 3.2 Power Distribution and Power Conditioning Products Table 33 Liebert Datawave ™ , Liebert FPC ™ , Liebert PPC ™ - Input and Holding - PMP, PM2 Options for Liebert FP...
Modbus 485 and Modbus IP Protocols - Power Distribution and Power Conditioning Products 97 Liebert ® IntelliSlot ® Modbus/BACnet IP Table 35 Liebert FDC ™ , Liebert FPC ™ , Liebert RDC ™ , Liebert RX ™ - Status and Coil Controller Liebert iCOM ® v4 Liebert Products Liebert FDC, Liebert FPC, Liebert ...
Modbus 485 and Modbus IP Protocols - Power Distribution and Power Conditioning Products Liebert ® IntelliSlot ® Modbus/BACnet IP 112 Table 38 Liebert STS ™ , Liebert STS/PDU ™ - Input and Holding - STS Controller STS Liebert Products Liebert STS Liebert STS/PDU Available Points Data Description Inpu...
Modbus 485 and Modbus IP Protocols - Power Distribution and Power Conditioning Products Liebert ® IntelliSlot ® Modbus/BACnet IP 114 Table 39 Liebert STS2 ™ , Liebert STS2/PDU ™ - Input and Holding - STS2 Controller STS2 Liebert Products Liebert STS2 Liebert STS2/PDU Available Points Data Descriptio...
Modbus 485 and Modbus IP Protocols - UPS Systems Liebert ® IntelliSlot ® Modbus/BACnet IP 118 3.3 UPS Systems Table 40 Liebert APM ™, Liebert NXC ™ , Liebert NXR ™ - Status and Coil Data Label Status Coil Number of Bits Scale Notes / Units System Status Battery Auto Test In Progress 10001 — 1 — Acti...
Modbus 485 and Modbus IP Protocols - UPS Systems Liebert ® IntelliSlot ® Modbus/BACnet IP 124 System Output Power Factor Phs B The system output power factor of phase B System Output Power Factor Phs C The system output power factor of phase C System Output Power The sum total power of all system ou...
Modbus 485 and Modbus IP Protocols - UPS Systems Liebert ® IntelliSlot ® Modbus/BACnet IP 136 Table 46 Liebert GXT2 ™ and Liebert GXT3 ™ - Status and Coil Data Description Status Coil Number of Bits Scale Notes / Units Audible Alarm Enabled 10002 2 1 — — Automatic Battery Test Enabled 10003 3 1 — — ...
Modbus 485 and Modbus IP Protocols - UPS Systems Liebert ® IntelliSlot ® Modbus/BACnet IP 138 Output Current L1 30164 — 1 — A Input Maximum Voltage L1 30180 — 1 — V Input Minimum Voltage L1 30181 — 1 — V Output Maximum Voltage L1 30182 — 1 — V Output Minimum Voltage L1 30183 — 1 — V Black Out Count ...
Modbus 485 and Modbus IP Protocols - UPS Systems 139 Liebert ® IntelliSlot ® Modbus/BACnet IP Table 50 Liebert Nfinity ® - Status and Coil Data Description Status Coil Number of Bits Scale Notes / Units Automatic Battery Test Enabled 10003 3 1 — — Battery Charger On 10044 — 1 — — Inverter Ready 1004...
Modbus 485 and Modbus IP Protocols - UPS Systems 141 Liebert ® IntelliSlot ® Modbus/BACnet IP Table 52 Liebert NX ™ - Status and Coil Data Description Status Coil Number of Bits Scale Notes / Units Economode 10005 5 — — — DC-To-DC Converter On 10042 — — — — Battery Charge Compensation 10046 — — — — ...
Modbus 485 and Modbus IP Protocols - UPS Systems 145 Liebert ® IntelliSlot ® Modbus/BACnet IP Table 54 Liebert NX 225-600kVA UPS - Input and Holding 3 Data Description Input Holding Register # of Reg Scale Notes/Units Identification Modbus Protocol Version — 40002 1 — XX.YY Manufacturer — 40003 1 — ...
Modbus 485 and Modbus IP Protocols - UPS Systems Liebert ® IntelliSlot ® Modbus/BACnet IP 148 Table 55 Liebert NXL ™ - 60Hz, UL version (Model 40) - Status and Coil Data Label Status Coil # of Bits Notes NXL Type Battery Self Test 10082 — 1 Active on Alarm N+1, 1+N, 1+1, SMS Battery Low Shutdown 100...
Modbus 485 and Modbus IP Protocols - UPS Systems 181 Liebert ® IntelliSlot ® Modbus/BACnet IP EcoModeSchedule 14 Schedule Operation State - ECO Mode 31019 — 1 — 0 = disabled 1 = enabled Schedule Action - ECO Mode 31020 — 1 — 0 = stop 1 = start Schedule Day of Week - ECO Mode 31021 — 1 — 0 = Unknown ...
Modbus 485 and Modbus IP Protocols - UPS Systems Liebert ® IntelliSlot ® Modbus/BACnet IP 190 Table 61 Liebert PowerSure ™ Interactive (before July 2008) - Status and Coil Data Description Status Coil Number of Bits Scale Notes / Units Audible Alarm Enabled 10002 2 1 — — Automatic Battery Test Enabl...
Modbus 485 and Modbus IP Protocols - UPS Systems Liebert ® IntelliSlot ® Modbus/BACnet IP 194 Table 65 Liebert Series 300 ™ UPS - Status and Coil Data Description Status Coil Number of Bits Scale Notes / Units Automatic Restart Enabled 10001 1 1 — — Battery Charge Compensation 10046 — 1 — — Inverter...
Modbus 485 and Modbus IP Protocols - UPS Systems 195 Liebert ® IntelliSlot ® Modbus/BACnet IP Table 66 Liebert Series 300 ™ UPS - Input and Holding Data Description Input Register Holding Register # of Reg. Scale Notes / Units Number of Input Lines 30004 40004 1 — Bits 12 - 15 Number of Bypass Lines...
Modbus 485 and Modbus IP Protocols - UPS Systems 199 Liebert ® IntelliSlot ® Modbus/BACnet IP Table 69 Liebert Series 610 ™ SCC UPS - Status and Coil Data Description Status Coil Number of Bits Scale Notes / Units Auto Retransfer Primed 10049 — 1 — — Load On Inverter 10073 — 1 — — Load On Bypass 100...
Modbus 485 and Modbus IP Protocols - UPS Systems Liebert ® IntelliSlot ® Modbus/BACnet IP 200 Table 70 Liebert Series 610 SCC UPS - Input and Holding Data Description Input Register Holding Register # of Reg. Scale Notes / Units Number of Input Lines 30004 40004 1 — Bits 12 - 15 Number of Bypass Lin...
Modbus 485 and Modbus IP Protocols - UPS Systems 201 Liebert ® IntelliSlot ® Modbus/BACnet IP Table 71 Liebert HiPulse ™, Liebert SICE 7200 ™ - Input and Holding - SMM/SSM Controller Multi Module Series - SMM Liebert Products Liebert HiPulse Liebert SICE 7200 Available Points Data Description Input ...
Modbus 485 and Modbus IP Protocols - UPS Systems 205 Liebert ® IntelliSlot ® Modbus/BACnet IP Table 73 Liebert Npower ™ - Input and Holding - IMP Controller Single Module Series - SMS Liebert Products Liebert Npower - SMS Available Points Data Description Input Register Holding Register # of Reg. Sc...
Modbus 485 and Modbus IP Protocols - Battery Monitoring Products 207 Liebert ® IntelliSlot ® Modbus/BACnet IP 3.4 Battery Monitoring Products Table 74 Alber ® BDSU ™ - Status and Coil Data Description Status Coil Number of Bits Notes / Units Battery Entity Battery Discharging Battery 1 - 32 10001-10...
Modbus 485 and Modbus IP Protocols - Battery Monitoring Products Liebert ® IntelliSlot ® Modbus/BACnet IP 208 Thermal Runaway Charger Current Level One Event String 1 - 32 13297-13328 — 1 Active on Alarm Thermal Runaway Charger Current Level Two Event String 1 - 32 13329-13360 — 1 Active on Alarm Gr...
BACnet Communications - BACnet Protocol Implementation Conformance Statement Liebert ® IntelliSlot ® Modbus/BACnet IP 214 4.0 BAC NET C OMMUNICATIONS 4.1 BACnet Protocol Implementation Conformance Statement The Liebert IntelliSlot ® Web IS-IPBML, IS-WEBADPT, IS-UNITY ™ and the IS-UNITY-DP ™ cards pr...
BACnet Communications - BACnet Protocol Implementation Conformance Statement 217 Liebert ® IntelliSlot ® Modbus/BACnet IP 4.1.4 Object Properties The following object properties are supported. Device Object The Device object represents the agent (the card) rather than the managed device. NOTE All pr...
BACnet Communications - BACnet Protocol Implementation Conformance Statement Liebert ® IntelliSlot ® Modbus/BACnet IP 218 Analog Object Units Possible values of the Units property include the BACnet Engineering Units defined in the BACnet standard, plus these additional proprietary units values: Ana...
BACnet Communications - BACnet Protocol Implementation Conformance Statement 219 Liebert ® IntelliSlot ® Modbus/BACnet IP Binary Object Properties Multistate Object Properties Binary Object Property Binary Input Binary Output Binary Value Comments Object_Identifier x x x — Object_Name x x x — Object...
BACnet Communications - Thermal Management Products Liebert ® IntelliSlot ® Modbus/BACnet IP 220 4.2 Thermal Management Products Table 76 Liebert Challenger 3000 ™ , Liebert Challenger ITR ™ , Liebert CW ™ , Liebert Deluxe System/3 ™ , Liebert DS ™ , Liebert DSE ™ , Liebert HPM ™ , Liebert PeX ™ - B...
BACnet Communications - Thermal Management Products Liebert ® IntelliSlot ® Modbus/BACnet IP 226 Low Static Pressure Binary_Value 565 5631_1 RD Active on Alarm 3, 5, 6 Static Pressure Sensor Out of Range Binary_Value 566 5910_1 RD Active on Alarm 5, 6 EconoPhase Pump Unspecified General Event Binary...
BACnet Communications - Thermal Management Products 235 Liebert ® IntelliSlot ® Modbus/BACnet IP Fluid 1 Fluid Input Temperature Analog_Value 871 5897_1 RD Units: deg C 6 Fluid Input Temperature Analog_Value 10871 5897_1_deg_F RD Units: deg F 6 Fluid Output Temperature Analog_Value 872 5898_1 RD Uni...
BACnet Communications - Thermal Management Products 243 Liebert ® IntelliSlot ® Modbus/BACnet IP Reheat Reheater Lockout MultiState_Value 316 5582_1 RW 1 = disabled 2 = enabled 2, 3, 4, 5, 6 Humidifier Humidifier Lockout MultiState_Value 328 5583_1 RW 1 = disabled 2 = enabled 2, 3, 4, 5, 6 Air Econo...
BACnet Communications - Thermal Management Products Liebert ® IntelliSlot ® Modbus/BACnet IP 276 Table 90 Extra Notes Number Description 1 This point is supported on: FDM v32 iCOM Controller Version 2.02.xxx 2 This point is supported on: FDM v101 iCOM Controller Version 2.03.xxx Table 91 Liebert HPC...
BACnet Communications - UPS Systems 299 Liebert ® IntelliSlot ® Modbus/BACnet IP 4.3 UPS Systems Table 98 Liebert APM ™ , Liebert NXC ™ , Liebert NXR ™ - Binary Data Data Label Object Type Instance Object Name Access Notes System Status Battery Auto Test In Progress Binary_Value 1 4172_1 RD Active o...
BACnet Communications - UPS Systems Liebert ® IntelliSlot ® Modbus/BACnet IP 302 MMS Output Apparent Power Analog_Value 69 4812_1 RD Units: kVA MMS Output Power Analog_Value 70 4811_1 RD Units: kW System Output Apparent Power Analog_Value 71 4209_1 RD Units: kVA System Output Power Analog_Value 72 4...
BACnet Communications - UPS Systems 303 Liebert ® IntelliSlot ® Modbus/BACnet IP Table 101 Liebert APM ™ , Liebert NXC ™ , Liebert NXR ™ - Glossary Data Label Data Description Battery Auto Test In Progress Automatic battery test is in progress Battery Capacity Low Battery capacity is low Battery Cha...
BACnet Communications - UPS Systems Liebert ® IntelliSlot ® Modbus/BACnet IP 306 Table 102 Liebert APS ™ - Binary Data Data Label Object Type Instance Object Name Access Notes Input Rectifier Failure Binary_Value 1 4295_1 RD Active on Alarm System Input Power Problem Binary_Value 2 4122_1 RD Active ...
BACnet Communications - UPS Systems Liebert ® IntelliSlot ® Modbus/BACnet IP 308 Table 103 Liebert APS ™ - Analog Data Data Label Object Type Instance Object Name Access Notes Input System Input RMS L1-N Analog_Value 1 4096_1 RD Units: VAC System Input RMS L2-N Analog_Value 2 4098_1 RD Units: VAC Sy...
BACnet Communications - UPS Systems Liebert ® IntelliSlot ® Modbus/BACnet IP 310 Table 104 Liebert APS ™ - Multistate Data Data Label Object Type Instance Object Name Access Notes Protocol Server Class MultiState_Value 1 4553_1 RD 1 = UPS 2 = AIR 3 = PMP 4 = PDU Bypass Bypass Qualification Status Mu...
BACnet Communications - UPS Systems Liebert ® IntelliSlot ® Modbus/BACnet IP 312 Table 105 Liebert APS ™ - Glossary Data Label Data Description Accumulated Discharge Time The highest accumulated battery discharge time among installed battery modules. Accumulated Discharge Time Total accumulated disc...
BACnet Communications - UPS Systems Liebert ® IntelliSlot ® Modbus/BACnet IP 316 Table 106 Liebert NXL ™ - 60Hz, UL version (Model 40) - Binary Data Data Label Object Type Instance Object Name Access Notes Liebert NXL Type Input System Input Power Problem Binary_Value 1 4122_1 RD Active on Alarm SMS...
BACnet Communications - UPS Systems 321 Liebert ® IntelliSlot ® Modbus/BACnet IP Table 107 Liebert NXL ™ - 60Hz, UL version (Model 40) - Analog Data Data Label Object Type Instance Object Name Access Notes Liebert NXL Type Input System Input RMS A-B Analog_Value 1 4097_1 RD Units: VAC SMS, 1+N, N+1 ...
BACnet Communications - UPS Systems 327 Liebert ® IntelliSlot ® Modbus/BACnet IP Table 108 Liebert NXL ™ - 60Hz, UL version (Model 40) - Multistate Data Data Label Object Type Instance Object Name Access Notes Liebert NXL Type Input Input Qualification Status MultiState_Value 1 4735_1 RD 1 = Fail 2 ...
BACnet Communications - UPS Systems 333 Liebert ® IntelliSlot ® Modbus/BACnet IP Table 109 Liebert NXL ™ - 60Hz, UL version (Model 40) - Glossary Data Label Data Description Auto Restart In Progress Auto restart is in progress Auto Restart Inhibited - Ext Auto restart inhibited due to an external si...
BACnet Communications - UPS Systems 341 Liebert ® IntelliSlot ® Modbus/BACnet IP Table 110 Liebert NXL ™ - 50 Hz, CE version (Models 48 and 49)—Binary Data Data Label Object Type Instance Object Name Access Notes Input System Input Power Problem Binary_Value 1 4122_1 RD Active on Alarm System Input ...
BACnet Communications - UPS Systems 345 Liebert ® IntelliSlot ® Modbus/BACnet IP Table 111 Liebert NXL ™ - 50 Hz, CE version (Models 48 and 49)—Analog Data Data Label Object Type Instance Object Name Access Notes Input System Input RMS A-B Analog_Value 1 4097_1 RD Units: VAC System Input RMS B-C Ana...
BACnet Communications - UPS Systems Liebert ® IntelliSlot ® Modbus/BACnet IP 348 Table 112 Liebert NXL ™ - 50 Hz, CE version (Models 48 and 49)—Multistate Data Data Label Object Type Instance Object Name Access Notes Input Input Qualification Status MultiState_Value 1 4735_1 RD 1 = Fail 2 = Marginal...
BACnet Communications - UPS Systems 355 Liebert ® IntelliSlot ® Modbus/BACnet IP Table 113 Liebert NXL ™ - 50 Hz, CE version (Models 48 and 49)—Glossary Data Label Data Description Auto Restart In Progress Auto restart is in progress Auto Restart Inhibited - Ext Auto restart inhibited due to an exte...
BACnet Communications - UPS Systems 363 Liebert ® IntelliSlot ® Modbus/BACnet IP Notes
While every precaution has been taken to ensure the accuracyand completeness of this literature, Liebert Corporation assumes noresponsibility and disclaims all liability for damages resulting from use ofthis information or for any errors or omissions.© 2013 Liebert CorporationAll rights reserved thr...
Emerson Manuals
-
Emerson LD195EM8
User Manual
-
Emerson EWR20V4
User Manual
-
Emerson EWR20V4
Manual
-
Emerson SLC195EM8
User Manual
-
Emerson SLC195EM8
Manual
-
Emerson CR202EM9
User Manual
-
Emerson HD14070
User Manual
-
Emerson RLC320EM9
User Manual
-
Emerson LC320EM9
User Manual
-
Emerson LC320EM9
Manual
-
Emerson PD6922
User Manual
-
Emerson PD6922
Manual
-
Emerson EPT427D
User Manual
-
Emerson EPT427D
Manual
-
Emerson 400 VMC
User Manual
-
Emerson 400 VMC
Manual
-
Emerson CF960CK
User Manual
-
Emerson MICRO MOTION 2700
Installation Manual
-
Emerson CF787AP00
User Manual
-
Emerson CF787AP00
Manual