Page 2 - SAVE THESE INSTRUCTIONS; Fluorinated Greenhouse Gas Requirements—European Union; CAUTION; become isolated by service valves.
I MPORTANT S AFETY G UIDELINES SAVE THESE INSTRUCTIONS Fluorinated Greenhouse Gas Requirements—European Union Stationary air conditioning, refrigeration, heat pump equipments and stationary fire protection systems in the European Community market and operating with fluorinated greenhouse gases (f-ga...
Page 3 - TABLE OF CONTENTS; XDCF C
i TABLE OF CONTENTS I MPORTANT S AFETY G UIDELINES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . I NSIDE F RONT C OVER 1.0 L IEBERT XDCF C OMPONENT L OCATIONS AND M ODEL N UMBER N OMENCLATURE . . . . . . . . 1 2.0 G ENERAL PRODUCT INFORMATION . . . . . . . . . . . . . . . . . ....
Page 4 - ii; FIGURES
ii FIGURES Figure 1 Liebert XDCF component locations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 Figure 2 Model number nomenclature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ...
Page 5 - Liebert XDCF Component Locations and Model Number Nomenclature; Figure 1; Gasket along edge of deflector
Liebert XDCF Component Locations and Model Number Nomenclature 1 1.0 L IEBERT XDCF C OMPONENT L OCATIONS AND M ODEL N UMBER N OMENCLATURE Figure 1 Liebert XDCF component locations FrontGrille InsulationStrip Top Deflector Panel(2 pieces) Supply PortConnection Return PortConnection MountingBracket Po...
Page 6 - Figure 2; XD
Liebert XDCF Component Locations and Model Number Nomenclature 2 Figure 2 Model number nomenclature XD 10 B 0 Model Size Revision level Liebert Xtreme heat density system Example: XD-CF10-BP—0 CF Module for BladeFrame EX — - = Domestic Packaging E = Export Packaging P P = Coupling T = Top B = Bottom
Page 7 - General product information; ENERAL; The Liebert XDCF; References; Lower Module; NOTE; control in the conditioned space.
General product information 3 2.0 G ENERAL PRODUCT INFORMATION The Liebert XDCF ™ is a self-contained module designed to cool Egenera’s BladeFrame EX cabinets and equipment without exhausting heat into the room.Liebert XDCF modules consist of a sheet-metal frame, coil and filter dryer. It has no mov...
Page 8 - Product / System Description; Figure 3; Equipment Inspection; sales representative.; R-134a refrigerant from the Liebert XDCF.
General product information 4 2.4 Product / System Description Upper and lower modules may be mounted on the rear of the Egenera BladeFrame. Each module, when attached to a fully loaded BladeFrame EX rack, has a nominal cooling capacity of 10kW (2.8 tons; 34,000 BTUh). Performance is based on: • Ent...
Page 9 - Unpacking the Liebert XDCF; before it is at the installation location.; NOTICE; freezing temperatures and contact damage.; Figure 4
General product information 5 2.6 Unpacking the Liebert XDCF The unit is shipped in a protective package. Do not remove the packaging from the Liebert XDCF before it is at the installation location. • When unpacking and handling the Liebert XDCF, care should be taken to prevent damaging the coils. •...
Page 10 - Mechanical Considerations; ECHANICAL; below, illustrates the unit’s dimensions and the location of pipes.; Figure 6; shows the attachment; Figure 5; Liebert
Mechanical Considerations 6 3.0 M ECHANICAL C ONSIDERATIONS The Liebert XDCF is engineered to fit on the rear of the Egenera BladeFrame enclosure. Figure 5 , below, illustrates the unit’s dimensions and the location of pipes. Figure 6 shows the attachment positions of each module. Figure 5 Overall d...
Page 11 - Installation; NSTALLATION
Installation 7 4.0 I NSTALLATION 4.1 References This document must be used together with site-specific documentation and documentation for other parts of the system. 4.2 Installation Considerations Liebert XDCF modules must be securely mounted to the rear of the Egenera BladeFrame cabinet. No cuttin...
Page 12 - Mounting Lower Liebert XDCF Module; Preparing the Lower Module for Attachment; top of the Liebert XDCF module (see; Liebert XDCF module (see; Figure 7; and; Figure 7; Positioning Stud; FRONT
Installation 8 4.3 Mounting Lower Liebert XDCF Module The lower Liebert XDCF module attaches to the Egenera BladeFrame cabinet with a mounting bracket, four bolts and a metal stud.Before the Liebert XDCF is mounted, the mounting bracket and a two-piece deflector panel must be attached to its top sur...
Page 13 - Attaching Lower Liebert XDCF Module; the locator hole on the ledge as shown in; Figure 8; rear of the Egenera BladeFrame cabinet. For the hole locations, see; side of the Liebert XDCF (see; fasteners joining the two-piece deflector.; Attaching Upper Liebert XDCF Module
Installation 9 4.3.2 Attaching Lower Liebert XDCF Module Liebert XDCF modules mount on the rear of the Egenera BladeFrame cabinet, near the power mod- ules. The cabinet and Liebert XDCF have prefabricated mounting holes and studs to ease mounting.1. Set the lower Liebert XDCF module on the left side...
Page 14 - Attaching Liebert XD Flex Pipe Support Panel; the right edge of the lower Liebert XDCF module; Steps a; Figure 9
Installation 10 Attaching Liebert XD Flex Pipe Support Panel Use of only the lower Liebert XDCF module requires attaching a Liebert XD Flex Pipe support panel and three pipe retainers. The retainers keep the refrigerant pipes behind the Egenera cabinet. If an upper Liebert XDCF module will be used, ...
Page 15 - Preparing the Upper Module for Attachment; Coil; Captive
Installation 11 4.4 Attaching Upper Liebert XDCF Module The upper Liebert XDCF module attaches to the Egenera BladeFrame cabinet with a mounting angle and four bolts.Before the Liebert XDCF is mounted, the mounting angle and a two-piece deflector panel must be attached to the bottom of the Liebert X...
Page 16 - Attaching Upper Liebert XDCF Module
Installation 12 4.4.2 Attaching Upper Liebert XDCF Module The upper Liebert XDCF module mounts on the rear of the Egenera BladeFrame cabinet, above the lower Liebert XDCF module. The cabinet and Liebert XDCF have prefabricated mounting holes and studs to ease mounting.1. Attach the mounting angle to...
Page 17 - Piping Connections and Piping Access Points; nection locations, refer also to; European Union Fluorinated Greenhouse Gas Requirements; erant inside the Liebert XDCF.; Figure 12 Liebert XDCF supply and return piping access points; release pressurized R-134a refrigerant from the Liebert XDCF.; Supply Pipe; Pipe locations and
Piping Connections and Piping Access Points 13 5.0 P IPING C ONNECTIONS AND P IPING A CCESS P OINTS Refer to site specific drawings for general locations of the piping connections. For Liebert XDCF con- nection locations, refer also to Figure 12 . 5.1 European Union Fluorinated Greenhouse Gas Requir...
Page 18 - Recommended Piping Size; XDC according to; . Elbows and restrictions must be minimized to get good fluid flow.; Table 1; Connecting Liebert XD Flex Pipes to Liebert XDCF Modules; Tools Required; Table 1; This operation requires two people.
Piping Connections and Piping Access Points 14 5.3 Recommended Piping Size Connect the main pipes between the Liebert XDCF branch piping and the Liebert XDP or Liebert XDC according to Table 1 . Elbows and restrictions must be minimized to get good fluid flow. Connect the branch pipes between the ma...
Page 19 - Figure 13 Liebert XD prefabricated piping assembly; Steps 5; Supply Main; Flex Pipe
Piping Connections and Piping Access Points 15 Figure 13 Liebert XD prefabricated piping assembly 5. Thread the return couplers together, the larger of the two couplers (Liebert XD Flex Pipe and return main). 6. Use one of the adjustable wrenches to hold the fixed side of the female coupler on the L...
Page 20 - two adjustable wrenches. Refer to; Return Flex pipe
Piping Connections and Piping Access Points 16 Figure 15 Liebert XD system with prefabricated piping assembly and Liebert XD Flex Pipe 5.6 Disconnecting a Liebert XDCF With Liebert XD Flex Pipe From a Liebert XD System Tools Required • Two adjustable wrenches, maximum adjustment size of 2-1/2 inches...
Page 21 - Figure 16 Profile view of the Liebert XD system; through; the Liebert XD Flex Pipes.; Insulation; Liebert XDP or Liebert XDC.
Piping Connections and Piping Access Points 17 Figure 16 Profile view of the Liebert XD system 7. Place the protective dust cap and plug back onto both ends of the coupler on the Liebert XDCF and the port pipe. Figure 17 Piping mains without Liebert XDCF and Liebert XD Flex Pipe 8. Repeat Steps 5 th...
Page 22 - Checklist for Proper Installation; HECKLIST; properly
Checklist for Proper Installation 18 6.0 C HECKLIST FOR P ROPER I NSTALLATION ___ 1. Liebert XDCF modules are securely attached to the cabinet.___ 2. Piping from Liebert XDP or Liebert XDC, with isolation valves, properly connected to each Liebert XDCF module. ___ 3. Flex piping connections to prefa...
Page 23 - Maintenance; AINTENANCE; Fluorinated Greenhouse Gas Requirements
Maintenance 19 7.0 M AINTENANCE Minimal maintenance is required to keep the Liebert XDCF operating at optimal levels. The unit should be cleaned and checked for damage. Suggested maintenance includes: • Cooling fins—Clean any dust and debris from the cooling fins, taking care not to bend them. 7.1 F...
Page 24 - Specifications; PECIFICATIONS; Table 2
Specifications 20 8.0 S PECIFICATIONS Table 2 Liebert XDCF specifications Models XD-CF-10-TPE-0, XD-CF Top EXP XD-CF-10-TP-0, XD-CF Top XD-CF-10-BPE-0, XD-CF BTM EXP XD-CF-10-BP-0, XD-CF BTM Cooling capacity, maximum 10kWH / 2.8 Tons / 34,000 BTUh Conditions 55°F (13°C) entering fluid temperature, 5...
Page 25 - NOTES
Page 28 - Precision Cooling
Ensuring The High AvailabilityOf Mission-Critical Data And Applications. Emerson Network Power, the global leader in enabling business-criticalcontinuity, ensures network resiliency and adaptability througha family of technologies—including Liebert power and coolingtechnologies—that protect and supp...