Emerson Liebert NX 10-30kVA- Manuals
Emerson Liebert NX 10-30kVA– User Manual in PDF format online.
Manuals:
User Manual Emerson Liebert NX 10-30kVA
Summary
i TABLE OF CONTENTS I MPORTANT S AFETY I NSTRUCTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 G LOSSARY OF S YMBOLS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 1.0 I NSTALLA...
ii 3.4 External Battery Cabinet Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20 3.4.1 Matching Battery Cabinets . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20 3.4.2 Connecting the Batterie...
iii 6.0 I NSTALLATION D RAWINGS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44 7.0 O PERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58 7.1 General Description . . . ....
iv 9.9 Battery Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80 9.9.1 Battery Undervoltage Pre-Warning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80 9.9.2 Battery End-of-Di...
vi TABLES Table 1 Input dry contacts at X3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15 Table 2 Maintenance bypass cabinet interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ....
1 I MPORTANT S AFETY I NSTRUCTIONS SAVE THESE INSTRUCTIONS This manual contains important instructions that should be followed during installation of your Liebert NX™ UPS and batteries.Read this manual thoroughly, paying special attention to the sections that apply to your installation, before worki...
2 Battery Cabinet Precautions The following warning applies to all battery cabinets supplied with UPS systems. Additional warn- ings and cautions applicable to battery cabinets may be found in 3.0 - Battery Installation . ! CAUTION This equipment is fitted with RFI suppression filters.Ground leakage...
Installation 4 1.0 I NSTALLATION Liebert’s NX ™ Uninterruptible Power Supply system provides continuous, high-quality AC power to your business-critical equipment, such as telecommunications and data processing equipment. The NX UPS supplies power that is free of the disturbances and variations in v...
Installation 5 1.2.1 Storing for Delayed Installation If the equipment will not be installed immediately, it must be stored indoors where the humidity is no higher than 90% and the temperature is no higher than 104°F (40°C). The storage area must protect the NX from excessive moisture (see 10.2 - UP...
Installation 6 1.4.3 Special Considerations for 1+N Systems 1. Consider the grounding configuration of your system before finalizing module placement. For optimal ground performance, the NX modules should be close together. 2. For optimal load-sharing performance, the UPS output cables should be app...
Installation 7 1.6.1 Clearances There are no ventilation grilles on the sides or rear of the UPS. The sides must be accessible during installation. After installation, the unit may be placed with the rear against a wall and optional cabi- nets on either side.To enable routine tightening of power ter...
Installation 8 1.6.4 Optional Cabinets If your NX installation includes a Maintenance Bypass Cabinet, the NX must be positioned to allow the Maintenance Bypass Cabinet to be bolted to left side of the NX (see Figure 1 ). Cables from the Maintenance Bypass Cabinet must be brought through the bottom s...
Electrical Connections 9 2.0 E LECTRICAL C ONNECTIONS The UPS requires both power and control cabling once it has been mechanically installed. All control cables must run separate from power cables in metal conduits or metal ducts that are electrically bonded to the metalwork of the cabinets to whic...
Electrical Connections 10 2.1.2 UPS Input Configuration Figure 2 illustrates the NX in a split bypass (dual-input) configuration. In this configuration the Static Bypass and the Maintenance Bypass lines are supplied from a separate feed from the Main input. Both sources must be protected externally ...
Electrical Connections 11 2.1.4 Cable Connections The rectifier input, bypass and output are easily accessible from the left side of the unit for installa- tion. All require lug type terminations. They are connected to busbars on the left side of the NX and below the switch, as shown in Figure 3 . T...
Electrical Connections 12 2.1.5 Safety Ground The safety ground busbar is located below the neutral input and output busbars as shown in Figure 5 below. The safety ground cable must be connected to the ground busbar and bonded to each cabinet in the system.All cabinets and cable conduit should be gr...
Electrical Connections 13 2.1.7 Cabling Procedure Once the equipment has been positioned and secured for operation, and the battery and ground col- lars have been connected (see 2.1.4 - Cable Connections ), connect the power cables as described below. (Study the reference drawing in 6.0 - Installati...
Electrical Connections 14 Internal UPS Battery Connections The UPS internal batteries will be connected at the factory, EXCEPT the Anderson connections between the shelves and to the fuses. Observe the battery cable polarity. Be sure that the battery connector is made with the cor- rect polarity. 11...
Electrical Connections 15 Figure 7 Auxiliary terminal block detail (Monitoring Board) 2.3 Dry Contacts The UPS provides input dry contacts and output dry contacts. 2.3.1 Input Dry Contacts There are several input dry contacts at the X3 slot. Figure 8 Input dry contacts Table 1 Input dry contacts at ...
Electrical Connections 16 2.3.2 Maintenance Bypass Cabinet Interface J26 and J30 are the MBC interface. 2.3.3 BCB Box Interface J10 is the BCB box interface. Figure 9 Jumper connection for BCB interface Table 2 Maintenance bypass cabinet interface Position Name Description J26.1 T_IT 1 Input transfo...
Electrical Connections 17 2.3.4 Output Dry Contacts There are three output dry contact relays at the X1 slot (see Figure 10 and Table 4 ). Figure 10 Output dry contacts and EPO wiring for firmware before M170 2.3.5 EPO Input—Optional Firmware Before M200 The UPS has an Emergency Power Off (EPO) func...
Electrical Connections 18 Firmware M200 or Later The UPS has an Emergency Power Off (EPO) function operated by a button on the control panel or by a remote contact provided by the user. The EPO button is under a hinged, clear plastic shield.The X2 slot, shown in Figure 11 , is the remote EPO input i...
Battery Installation 19 3.0 B ATTERY I NSTALLATION 3.1 Introduction Liebert recommends that the batteries in external cabinets match the internal batteries in the NX in manufacturer and type.If using multiple sets of batteries connected in parallel to provide the required battery backup run times, f...
Battery Installation 20 3.4 External Battery Cabinet Installation 3.4.1 Matching Battery Cabinets Two sizes of optional battery cabinets are available. Refer to Figures 13 and 14 . The same model bat- tery cabinet may be installed in parallel in multiple cabinet strings for additional capacity. Batt...
Battery Installation 22 3.4.3 Installation Considerations Position —Liebert battery cabinets come in versions specific to either the left or right side of the UPS. Control wires and power cables are cut to different lengths for the different versions. If the sys- tem includes a matching maintenance ...
Battery Installation 23 Figure 15 Internal cable wiring from battery cabinet to Liebert NX Figure 16 Battery tray and supports Power cables from batteries Power cables from output power switch Power cables exit battery cabinet, enter Liebert NX Power cables run across top of Liebert NX Power cables ...
Battery Installation 24 3.4.4 Connecting the Battery Cabinet to the UPS After the battery cabinet equipment has been positioned and secured for operation and the batteries have been connected, connect the power cables as described below. (See Figure 36 .) 1. Verify that all incoming high and low vol...
Maintenance Bypass Cabinet 25 4.0 M AINTENANCE B YPASS C ABINET The Maintenance Bypass Cabinet is designed to operate in UPS mode, bypass mode and maintenance mode. The mode is selected using the Bypass Switch. Figure 17 Single UPS with external Maintenance Bypass Cabinet—typical configuration 4.1 B...
Maintenance Bypass Cabinet 26 4.3 Bypass Mode When the Maintenance Bypass Cabinet is in the Bypass mode, it provides an alternate path for power to the connected equipment. Should the UPS need to be taken out of service for limited maintenance or repair, manual activation of the bypass will cause an...
Maintenance Bypass Cabinet 27 4.6.2 Power Cable Installation Refer to Tables 35 , 36 and 38 when selecting cables. 4.6.3 Input/Output Wiring Follow the steps below to connect the input wiring: 1. Locate the input wiring access (top or bottom access), remove the conduit landing plate and punch the ap...
Maintenance Bypass Cabinet 28 7. Connect the system input cables between the Maintenance Bypass Cabinet 'UPS Input' Busbars (A-B-C N terminals) and UPS input busbars (A-B-C N terminals) and tighten the connections to 44 lb-in. (5 N-m) (M6 bolt). 8. Connect the system outnput cables between the Maint...
Maintenance Bypass Cabinet 29 4.7 Bolting Cabinets Together 1. Line up cabinets so that mounting holes are aligned. 2. Using supplied hardware, bolt the cabinets together. The bolts may be inserted from either the UPS side or from the MBS side, whichever is more convenient. NOTE UPS wiring must be c...
Option Installations 30 5.0 O PTION I NSTALLATIONS 5.1 Load Bus Synchronization The Load Bus Synchronizer (LBS) keeps the output of two independent UPS systems or parallel UPS systems in synchronization even when the systems are operating in different modes and even when either or both systems are o...
Option Installations 31 5.2 Configuring Parallel System Operation 5.2.1 General The NX uses intelligent and reliable decentralized technology to achieve parallel operation of two or more modules of the same rating.The 1+N system is used to: • Increase the reliability of the system to ensure adequate...
Option Installations 32 5.2.2 Features of Parallel System • The hardware and firmware for parallel UPS module operation is standard in the NX, and the configuration can be set up by changing the settings in configuration software. • It is easy to install the parallel cables in a ring, providing high...
Option Installations 33 5.2.3 Operating Principles Redundancy Paralleling The 1+N parallel redundant system can noticeably improve system reliability. In normal condition, none of the UPS modules work at full load. That means that even if the load is increased, the system will not transfer to bypass...
Option Installations 34 5.3.5 Power Cables Wiring of power cables is similar to that of single-module system (See 2.1 - Power Cabling ). The bypass sources of all modules should be the same, and the outputs should be connected altogether cor- rectly.Power cables will be supplied by customer. Power c...
Option Installations 35 Figure 24 Auxiliary dry contact cables for output breaker in multi-module system Figure 25 Dry contacts, multiple UPS modules with distribution panel ! CAUTION The auxiliary control wire must be installed to ensure proper operation of the system. NOTE For startup procedure, s...
Option Installations 36 5.3.7 Emergency Power Off (EPO) The external emergency stop facility is identical to that described for the single-unit installation— that an individual emergency stop button is provided for each unit. Figure 26 Connecting EPO push button 5.4 Battery Circuit Breaker Box The b...
Option Installations 37 Figure 27 Battery circuit breaker box connections NOTE 1. The signal cables in this figure must be shielded and double-insulated.2. Connect the Pes (Protection Earth) of the UPS cabinet and BCB box to the same point. DPN U3813078 Rev. N (7.9mm) (Typ. 4 places) .31" dia. ....
Option Installations 38 5.5 Battery Start With this option, the NX UPS can be started with power supplied only by the batteries (at charged condition). This type of start, in the absence of utility power, allows independent utilization of battery power and provides for higher availability in some ci...
Option Installations 39 5.10 OC Web Card—SNMP/HTTP Network Interface Card This network interface card provides all real-time data and status information as SNMPv1 traps for connection to a 10/100-baseT Ethernet connection. The same card also will transmit the same status information and all measured...
Option Installations 40 5.10.1 Configuring Baud Rates The default baud rate for Intellislots is 9600. To communicate with the OCWEB-LB, Modbus/Jbus, or the MultiLink cards, the baud rate must be set to 2400.To change the baud rate (refer to Table 8 ): 1. Use the Navigation keys directly below the LC...
Option Installations 41 Figure 28 OC Web card display
Option Installations 42 5.11 Relay Card The relay card provides voltage-free contact closures for remote monitoring of alarm conditions.Delivering On Battery, On Bypass, Low Battery, Summary Alarm, UPS Fault and On UPS sig- nals, the easy-to-install card integrates with AS/400 computers (additional ...
Option Installations 43 5.12 MultiPort 4 Card The MultiPort 4 card provides four sets of voltage-free contact closures for remote monitoring of alarm conditions UPS operation On Battery and battery low condition. A typical applicaton is to allow a maximum of four computer systems to simultaneously m...
Installation Drawings 44 6.0 I NSTALLATION D RAWINGS The diagrams in this section illustrate the key mechanical and electrical characteristics of the NX UPS System cabinets. Figure 30 Dimensional view- front and left side views 1. All dimensions are in millimeters.2. A minimum of 24 inches clearance...
Installation Drawings 45 Figure 31 Dimensions continued—top and bottom views Figure 32 Main components—typical unit Rear stabiliz- ing foot Air Exhaust Power Cable Entry Area Top and Bottom Air 10mm dia. threaded mounting holes 4 (typ). See Notes 8 and 9 above. TOP VIEW BOTTOM VIEW MonitorBoard(U2) ...
Installation Drawings 46 Figure 33 Cable connections NOTES 1. All dimensions are millimeters.2. Top and bottom cable entry available through removable access plates. Remove, punch to accommodate conduit size and replace. 3. Control wiring and power wiring must be run in separate conduit. Output and ...
Installation Drawings 47 Figure 34 Location of internal batteries Battery 417mm 687mm 186mm
Installation Drawings 48 Figure 35 Battery connections + - + - + - + - + - + - + - - + + - + - + - + - + - + - + - - + + - + - + - + - + - + - + - - + - N + W501 3pcs W500 18pcs W510 to W511 W502 to W503 W503 to W502 W504 to W505 W511 to W510 W507 to W506 W509 to W508 W 506 t o W 5 07 TOP LAYER MIDD...
Installation Drawings 49 Figure 36 Battery cabinet interconnection Table 11 Liebert -supplied interconnect wiring Run From To Conductors A UPS battery terminal block External 27" or 59" battery cabinet Positive, midpoint, negative B Battery cabinet terminal block UPS monitor board Battery br...
Installation Drawings 50 Figure 37 Maintenance Bypass interconnection Table 12 Liebert-supplied interconnect wiring for Maintenance Bypass Cabinet Run From To Conductors A Utility AC source Maintenance Ph A, B, C bypass/ transformer cabinet B Utility AC source Maintenance Neutral bypass/ transformer...
Installation Drawings 51 Figure 38 NX 1+1 parallel cabinet interconnections Table 13 Liebert-supplied interconnect wiring Run From To Conductors Cabinet Type A Utility AC Source Paralleling Cabinet PH A, B, C - Bypass BR0, CR1, DR1 B Utility AC Source Paralleling Cabinet Neutral - Bypass BR0, CR1, D...
Installation Drawings 52 Figure 39 Lineup detail—SlimLine distribution cabinet to NX Table 14 Liebert-supplied interconnect wiring—SlimLine distribution cabinet to NX Run From To Conductors A Distribution Cabinet Load AC Connection Isolated Ground B Distribution Cabinet Load AC Connection Neutral Di...
Installation Drawings 53 Figure 40 Lineup detail—1+N Type A connection to NX Table 15 Interconnect wiring—1+N Type A connection to NX RUN FROM TO CONDUCTORS A1-A4 Utility AC Source UPS #1-UPS #4 Module AC Input Ph A, B, C - UPS Input B1-B4 Utility AC Source UPS #1-UPS #4 Module AC Input Neutral - UP...
Installation Drawings 54 Figure 41 Lineup detail—1+N Type B1 connection to NX Table 16 Interconnect wiring—1+N Type B1 connection to NX Run From To Conductors A Utility AC Source Paralleling Cabinet Ph A, B, C - System Input B Utility AC Source Paralleling Cabinet Ground - System Input C Utility AC ...
Installation Drawings 55 Figure 42 Lineup detail—1+N Type C connection to NX Table 17 Interconnect wiring—1+N Type C connection to NX Run From To Conductors A Utility AC Source Paralleling Cabinet Ph A, B, C-system Input B Utility AC Source Paralleling Cabinet Ground - System Input C1-C4 Paralleling...
Installation Drawings 57 Figure 44 Suggested placement, multiple NX units with auxiliary cabinets Battery Cabinet Battery Cabinet Liebert NX UPS Battery Cabinet Multi-Module Paralleling Cabinet Liebert NX UPS Liebert NX UPS Front of Units Liebert NX UPS Liebert NX UPS Liebert NX UPS Multi-Module Par...
Operation 58 7.0 O PERATION 7.1 General Description The standard NX consists of the UPS and internal batteries in a compact, single cabinet.As shown in Figure 45 , the AC utility source is input at CB1 and the rectifier converts the AC utility into DC power. The inverter converts that DC power from ...
Operation 59 Normal Mode Operating in normal mode, the NX’s rectifier derives power from a utility AC source and supplies reg- ulated DC power to the inverter, which regenerates precise AC power to supply the connected equip- ment. The rectifier also uses the utility source power to charge the batte...
Operator Control and Display Panel 60 8.0 O PERATOR C ONTROL AND D ISPLAY P ANEL 8.1 Operator Control Panel The control panel and LCD on the front of the Liebert NX lets the operator: • turn the UPS on or off• transfer into the various operating modes• silence alarms• check the status of the UPS and...
Operator Control and Display Panel 61 8.2 Mimic Display Indicators The Mimic display on the front panel consists of six indicators arranged in a single-line diagram depicting the various paths of UPS power, as shown in Figure 48 . Figure 48 Mimic display indicators location The current operational s...
Operator Control and Display Panel 62 8.3 Control Buttons The Control Buttons on the front panel may be used to shut down the UPS completely, turn the inverter on or off, restart the UPS after a fault and silence the alarm, as shown in Figure 49 . The function of each button is described in Table 19...
Operator Control and Display Panel 63 8.5 LCD Overview The LCD on the front panel has five main sections, as shown in Figure 51 . Press the F1 key below the LCD to scroll through these sections. • UPS system information - view UPS name and model, date and time, overall status (see Table 21 ). • LCD ...
Operator Control and Display Panel 64 8.6 Navigation Keys The navigation keys on the front panel—F1 through F4 and Help—are used to access the LCD to view the current status and other information about the NX.Navigation key icons on the LCD appear above each key to indicate its operation (see Table ...
Operator Control and Display Panel 65 8.8 LCD Menus and Data Items The LCD menus provide access to the following categories of information and settings for the UPS. Selecting a menu changes the information displayed in the UPS data items portion of the LCD. The menu choices are listed below and desc...
Operator Control and Display Panel 66 8.9 Language Selection The LCD menus and data display are available in 12 languages (Chinese, Dutch, English, French, German, Italian, Japanese, Polish, Portuguese, Russian, Spanish and Swedish). To select a differ- ent language: • From the main menu, press the ...
Operator Control and Display Panel 67 Table 22 Descriptions of UPS menus and data window items Menu Type Item Type Explanation Mains (input) L-N voltage (V) Phase voltage L-N current (A) Phase current Frequency (Hz) Input frequency L-L voltage (v Line-line voltage Power factor Power factor TX Input ...
Operator Control and Display Panel 68 Settings Display contrast Adjust the LCD display contrast Date format set Choose the format for date display: M/D/Y, D/M/Y, M/D/Y, Y/M/D Date & time Set the date and time Comm1 baud rate Communication baud rate setting for Intellislot 1 Comm2 baud rate Commu...
Operator Control and Display Panel 69 8.11 UPS Status Messages The NX displays status changes as they occur in the current status window of the LCD , then stores that data in the history log , as shown in Figure 53 . • Current Status Window: The status messages are displayed chronologically and incl...
Operator Control and Display Panel 70 8.12 Types of LCD Screens This section provides a quick guide to the main types of LCD screens. 8.12.1 Opening Display As the UPS begins powering up, the opening display appears, as shown in Figure 54 . Figure 54 Opening display 8.12.2 Default Screen After the U...
Operator Control and Display Panel 71 8.12.3 UPS Help Screen Press the HELP key below the LCD to display the Help window shown in Figure 56 . (Press the HELP key again to exit the Help window.) Figure 56 Help screen 8.12.4 Screen Saver Window If there has been no interaction with the NX’s LCD for 2 ...
Operator Control and Display Panel 72 8.13 Pop-Up Windows Pop-up prompt windows appear when the user must confirm a choice or perform an operation. This section describes the pop-up windows. 8.13.1 From Bypass to Inverter Mode With Power Interruption If the bypass voltage or frequency exceeds the sy...
Operating Instructions 73 9.0 O PERATING I NSTRUCTIONS 9.1 NX Operating Modes The NX can operate in any of four modes, as shown in Table 23 . This section provides instructions on switching between modes, resetting the UPS, switching the inverter On and Off and performing other operations. Table 23 ...
Operating Instructions 74 9.1.1 Power Switches The UPS can be isolated by means of power switches, mounted inside the cabinet and accessible after opening the front door.The location of the UPS power switches is shown in Figure 58 . Figure 58 Power switches - 10kVA NX The UPS unit power switches are...
Operating Instructions 75 9.2 UPS Start Up The NX must be fully installed and commissioned before start up, and external power isolators must be closed. Once those general conditions are met, the UPS may be started. 9.2.1 Start-Up Procedure To start the UPS from a fully powered-down condition:1. Ope...
Operating Instructions 76 5. Turn the rotary switch to NORMAL, then press the INVERTER ON control button for 2 seconds. The inverter will start and the inverter indicator will flash green. After the inverter is ready, the UPS transfers from bypass to inverter, the bypass indicator turns off and the ...
Operating Instructions 77 9.3 Switching the UPS from Normal to Maintenance Bypass Follow the procedure below to transfer the load from the inverter output to the Maintenance Bypass line of the UPS. This procedure assumes that UPS is operating normally.1. Press the INVERTER OFF button on the right si...
Operating Instructions 78 9.5 Powering Down the UPS and Maintaining Power to Load If the UPS needs to be shut down completely while maintaining power to the load, follow these steps:1. Perform Steps 1 through 5 in 9.3 - Switching the UPS from Normal to Maintenance Bypass . 2. Close the external main...
Operating Instructions 79 9.6 Emergency Shutdown With EPO This circuit has been designed to switch off the UPS in emergency conditions (i.e., fire, flood, etc.). The system will turn off the rectifier, inverter and stop powering the load immediately (including the inverter and bypass), and the batte...
Operating Instructions 80 9.9 Battery Protection 9.9.1 Battery Undervoltage Pre-Warning Before the end of discharge, the NX displays a battery undervoltage pre-warning. After this pre-warn- ing, the battery has the capacity for 5 minutes discharging with full load (default time). The NX can be user-...
Operating Instructions 81 9.11 Inserting One Module into a Multi-Module System This procedure outlines how to integrate a UPS module that has been previously isolated from other modules of a group of paralleled UPS modules. It is assumed that the installation is complete, the sys- tem has been commi...
Operating Instructions 82 9.12 Shutting Down a Multi-Module System Without System Bypass Switch 1. Open the UPS door to gain access to the main power switches, SW1 and CB1of a UPS in the system. 2. Turn the rotary switch to BYPASS position. Rotating any UPS Rotary Switch (SW1) to the Bypass position...
Operating Instructions 83 9.14 Commissioning a Parallel System Check the input and output wiring of each UPS module. Ensure that the phase rotation sequence of the main inputs and the bypass inputs and outputs of each UPS module are the same. Ensure the parallel cables are connected firmly.It is ass...
Operating Instructions 84 The procedure can be performed only after the installation has been completed (which includes the maintenance bypass cabinet), after the system has been placed in operation by authorized personnel and after the external power switches have been closed. See Figure 60 for mor...
Operating Instructions 85 9.16 Parallel System Start Up 1. Start each UPS normally as described in 9.2 - UPS Start Up 2. Turn on the inverter of each UPS module one at a time.3. Apply the load after the last UPS module transfers to inverter. The total load can be determined through the LCD of either...
UPS Specifications 86 10.0 UPS S PECIFICATIONS These specifications describe requirements for the Liebert NX UPS. 10.1 Conformity and Standards The UPS has been designed to conform to the following standards: • IEEC1000-4-5• ASME• CSA 22.2, No. 107.1• FCC Part 15, Class A• ISO 9001• National Electri...
UPS Specifications 87 10.4 UPS Electrical Characteristics Table 27 UPS terminal Input (for single-input unit) Unit Rating Nominal Input Current Maximum Input Current OCP Current OCP Device Rating Bolt Size Maximum Recommended Lug Lug T&B One Hole 54000 Lug T&B One Hole REDDY 10 28 35 42 45 6...
UPS Specifications 88 10.4.1 Battery Manufacturers and Models Either of two manufacturers’ batteries will be installed in the NX 10-30 kVA 208V as shipped. Below are the battery makers and the models they supply. 10.4.2 Input Rectifier 10.4.3 DC Intermediate Circuit Table 28 Approved batteries Batte...
UPS Specifications 89 10.4.4 Inverter Output 10.4.5 Bypass Input Table 31 Inverter output Rated Power 10kVA 15kVA 20kVA 30kVA Rated voltage, VAC 120/208 Supply 3-phase, 4-wire plus ground Frequency, Hz 50 / 60 Rated Power, kW 8 12 16 24 Three -phase transient overload, min. load 10 minutes - 105-125...
Specifications and Technical Data 90 11.0 S PECIFICATIONS AND T ECHNICAL D ATA 11.1 Lug Size and Torque Requirements Use commercially available solderless lugs for the wire size required for your application. Refer to Table 33 . Connect wire to the lug using tools and procedures specified by the lug...
Specifications and Technical Data 91 Table 35 Maintenance bypass cabinet electrical data (single input) kVA Type Maintenance Bypass I/P Voltage (VAC) Bypass Cabinet Max Input Current Cabinet Input OCP CB Size (A) O/P Voltage (VAC) Nominal O/P Current Rating (A) Output OCP CB Size (A) 30 A, J 208 104...
Specifications and Technical Data 92 10 A, J 208 35 50 208 28 40 10 B, K 480 16 20 208 28 40 10 B, K 600 12 15 208 28 40 10 B, K 220 34 50 208 28 40 10 C, L 480 16 20 480 12 15 10 C, L 600 13 20 600 10 15 10 C, L 220 35 50 220 26 40 10 D, M 480 16 20 208 28 40 10 D, M 600 13 15 208 28 40 10 D, M 208...
Specifications and Technical Data 93 Table 37 Multi-module bypass cabinet electrical data System Size Type kVA System I/P Voltage (VAC) System Max Input Current System Input OCP CB Size (A) O/P Voltage (VAC) Nominal O/P Current Rating (A) Output OCP CB Size (A) 1+1 A00, BR0 30 208 104 125 208 83 125...
Specifications and Technical Data 94 Table 38 Maintenance bypass cabinet lug sizes Input Unit Rating Nominal System Input Voltage Bolt Size Maximum Recommended Lug Lug T&B One Hole 54000 Lug T&B One Hole REDDY 30 600 6M (1/4") 54105 62204 30 480 6M (1/4") 54106 62204 30 240 6M (1/4...
Specifications and Technical Data 95 Table 39 Battery cabinet physical characteristics Battery Cabinet Type Dimensions WxDxH in. (mm) Net Weight Without Batteries, lb. (kg) Short Narrow 27.2x31.4x63 (690x825x1600) 551 (250) Short Wide 58.5x31.4x63 (1488x825x1600) 889 (400) Table 40 Maintenance Bypas...
Specifications and Technical Data 96 11.2 Cable Lengths: Floor to Connection Point Inside UPS To help calculate the total cable length required, refer to Table 43 for the distance from the floor to selected connection points inside the NX. Determine the cable length required to reach the NX, then ad...
UPS Status Messages 97 A PPENDIX A - UPS S TATUS M ESSAGES Table 44 shows all event messages as they appear in the current status area of the LCD or the his- tory log, along with a description and recommended actions, if any. For further information on the current status area and the history log, se...
EmersonNetworkPower.com Ensuring The High Availability0f Mission-Critical Data And Applications. Emerson Network Power, the global leader in enabling business-criticalcontinuity, ensures network resiliency and adaptability througha family of technologies—including Liebert power and coolingtechnologi...
Emerson Manuals
-
Emerson LD195EM8
User Manual
-
Emerson EWR20V4
User Manual
-
Emerson EWR20V4
Manual
-
Emerson SLC195EM8
User Manual
-
Emerson SLC195EM8
Manual
-
Emerson CR202EM9
User Manual
-
Emerson HD14070
User Manual
-
Emerson RLC320EM9
User Manual
-
Emerson LC320EM9
User Manual
-
Emerson LC320EM9
Manual
-
Emerson PD6922
User Manual
-
Emerson PD6922
Manual
-
Emerson EPT427D
User Manual
-
Emerson EPT427D
Manual
-
Emerson 400 VMC
User Manual
-
Emerson 400 VMC
Manual
-
Emerson CF960CK
User Manual
-
Emerson MICRO MOTION 2700
Installation Manual
-
Emerson CF787AP00
User Manual
-
Emerson CF787AP00
Manual