Emerson Liebert MicroPOD Maintenance Bypass and Output Distribution Accessory- Manuals
Emerson Liebert MicroPOD Maintenance Bypass and Output Distribution Accessory– User Manual in PDF format online.
Manuals:
User Manual Emerson Liebert MicroPOD Maintenance Bypass and Output Distribution Accessory
Summary
3 INTRODUCTION Congratulations on your choice of the Liebert POD. The Liebert POD provides maintenance bypass capability as well as power output distribution. The Liebert POD provides an isolated path of power for your UPS system for preventative maintenance as well as service. SYSTEM DESCRIPTION Th...
5 COMPRESSION FIELD CONNECTIONS POD Model Number Wire Size Recommended External Overcurrent Protection Torque MP115HW #14 AWG - #8AWG 15A MP120HW #12 AWG - #8AWG 20A MP130HW #10 AWG - #8AWG 30A MP130HWH #10 AWG - #8AWG 30A MP215HW #14 AWG - #8AWG 15A MP220HW #12 AWG - #8AWG 20A Max. torque: 2 Nm / 1...
6 SPECIFICATIONS Transfer Time: (to and from maintenance bypass) < 6 milliseconds Operating Ambient Temperature: 0 to +40 degrees C Storage Ambient Temperature: -20 to +60 degrees C Weight: 12 Lbs. (max.) Humidity: 0 to 95% non-condensing Agency/Standards: UL, c-UL listed TROUBLESHOOTING PROBLEM ...