Page 3 - Table 1
i CONTENTS 1.0 I NTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . 1 2.0 I NSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . 2 3.0 P IN C ONFIGURATION . . . . . . . . . . . . . . . . . . . . 4 4.0 J UMPER S ETUP . . . . . . . . . . . . . . . . . . . . . . . 5 5.0 C ONTACTING T ...
Page 5 - NTRODUCTION; Inspecting Shipment on Receipt
Introduction 1 1.0 I NTRODUCTION The Liebert Intellislot™ Interface for Relay Contacts card provides contact closures for remote monitoring of alarm conditions in your Liebert UPS. Delivering On Battery, On Bypass, Low Battery, Summary Alarm, UPS Fault and On UPS signals, the easy-to-install card in...
Page 6 - NSTALLATION; Parts and Tools Required; CARD AND SLOT ORIENTATION
Installation 2 2.0 I NSTALLATION Parts and Tools Required • Intellislot Interface for Relay Contacts card and required cable assembly • #2 (medium) Phillips or small flat-head screwdriver Instructions 1. Turning off the UPS prior to installation is suggested, although not required. 2. Locate the Int...
Page 7 - Option 1
Installation 3 6. Select either interface Option 1 or 2 below (also see Step 7 and 3.0 - Pin Configuration ). Option 1: Hardwire (terminal block pins) - Use these guidelines for terminal block specifications: Option 2: DB25 pins a. Disconnect the Hardwire Adapter board by removing the two mounting s...
Page 8 - IN
Pin Configuration 4 3.0 P IN C ONFIGURATION Table 1 Relay contact card pin configuration Terminal Block Pin DB25 Pin Function Operation 1 1 UPS Fault Closed if no UPS failure* — 2 Not Used — 3 Not Used 4 4 UPS Fault Closed if UPS fails* 5 5 Summary Alarm** Closed if SUMMARY ALARM** occurs* 6 6 Summa...
Page 9 - UMPER; Refer to; and the figure below for jumper setup.; Table 2; Connection; Jumper
Jumper Setup 5 4.0 J UMPER S ETUP Refer to Table 2 and the figure below for jumper setup. Table 2 Jumper connections # Connection Description JP01 Pin 9 to Pin 17 Allows all relay COMMONS to be tied together. JP02 Pin 7 to Pin 17 Allows all relay COMMONS and the ANY MODE SHUTDOWN GROUND to be tied t...
Page 10 - ONTACTING; Liebert has a team of specially trained technicians waiting to; INSTALLATION SITE
Contacting Technical Support 6 5.0 C ONTACTING T ECHNICAL S UPPORT Liebert has a team of specially trained technicians waiting to quickly assist you with any installation or troubleshooting problems. Refer to the back of this manual for the Technical Support phone number.To successfully diagnose you...
Page 12 - The Company Behind the Products; ONITORING; NTELLISLOT; SER
The Company Behind the Products With over a million installations around the globe, Liebert is the world leader in computer protection systems. Since its founding in 1965, Liebert has developed a complete range of support and protection systems for sensitive electronics: • Environmental systems—clos...