Page 2 - Instruction Manual Supplement; Introduction; Product Overview
Instruction Manual Supplement D103638X012 DVC6200 SIS Digital Valve Controller August 2014 2 Introduction Product Overview The FIELDVUE DVC6200 SIS digital valve controller is designed to control the pneumatic actuator of a safety valve. Itreceives a current signal from a host and uses instrument ai...
Page 3 - Reference Documentation; Device Identification
Instruction Manual Supplement D103638X012 DVC6200 SIS Digital Valve Controller August 2014 3 Reference Documentation HART Smart Communications Protocol Specification Revision 7.4; a group of documents specifying the HARTCommunication Protocol, physical layers, and Data Link Layers as defined by the ...
Page 4 - Product Interfaces; Control Valve Interface; Host interface
Instruction Manual Supplement D103638X012 DVC6200 SIS Digital Valve Controller August 2014 4 Product Interfaces Control Valve Interface The DVC6200 SIS digital valve controller is mechanically attached to the valve’s actuator by means of a mountingbracket. The valve's position is conveyed to the tra...
Page 5 - Internal Jumpers And Switches; Write Protection
Instruction Manual Supplement D103638X012 DVC6200 SIS Digital Valve Controller August 2014 5 Internal Jumpers And Switches The input to the DVC6200 SIS is determined by the PtPt/MultiDrop switch on the printed wiring board. The DVC6200 SIS also has a pair of “Output” terminals that can either func...
Page 6 - Dynamic Variables
Instruction Manual Supplement D103638X012 DVC6200 SIS Digital Valve Controller August 2014 6 Dynamic Variables Four Dynamic Variables are implemented. Default Meaning Units PV Analog Input mA, % SV* Travel Setpoint % TV* Pressure PSI, BAR, KPA, Kg/cm 2 FV* Travel % * User selectable The SV, TV, and ...
Page 7 - Unit Codes; Device Status
Instruction Manual Supplement D103638X012 DVC6200 SIS Digital Valve Controller August 2014 7 Unit Codes Variable Units Code Units 0 No Units 6 Pounds per square inch, psi 7 Bar 10 ($0A) Kilograms per square centimeter, kg/cm 2 12 ($0C) Kilopascals, kPa 32 ($20) Celsius, _ C 33 ($21) Fahrenheit, _ F ...
Page 8 - Universal Commands
Instruction Manual Supplement D103638X012 DVC6200 SIS Digital Valve Controller August 2014 8 Universal Commands The DVC6200 SIS field device implements all Universal Commands. Commands 14, 15, 17, 48 are listed below toindicate their unique responses. Command 0: Read Unique IdentifierCommand 1: Read...
Page 9 - Command 14: Read Primary Variable Transducer Information
Instruction Manual Supplement D103638X012 DVC6200 SIS Digital Valve Controller August 2014 9 Command 14: Read Primary Variable Transducer Information The transducer limits reported in this command are either 420 milliamps, or 0100%, and reflect the units code mostrecently supplied in command 44. N...
Page 10 - Command 15: Read Primary Variable Output Information
Instruction Manual Supplement D103638X012 DVC6200 SIS Digital Valve Controller August 2014 10 Command 15: Read Primary Variable Output Information This command returns the upper/lower range values for the primary variable which is defined to be the loop currentsignal. These are the loop current valu...
Page 11 - Command 17: Write Message
Instruction Manual Supplement D103638X012 DVC6200 SIS Digital Valve Controller August 2014 11 Command 17: Write Message This command allows you to write a 24 character informational message into the device. However, per common implementation of Emerson devices, writing a specific string to the Messa...
Page 12 - Command 48: Read Additional Status
Instruction Manual Supplement D103638X012 DVC6200 SIS Digital Valve Controller August 2014 12 Command 48: Read Additional Status This command was significantly revised in HART 7, but can operate in backward compatible mode for HART 5 masterswhich do not supply data bytes in the request. Supplying da...
Page 13 - Additional Device Status
Instruction Manual Supplement D103638X012 DVC6200 SIS Digital Valve Controller August 2014 13 Additional Device Status Command 48 returns 9 bytes of data, with the following status information: Byte Bit Name of Status Bit Meaning 0 7 Flash Integrity Failure Active if there is a failure associated wi...
Page 16 - CommonPractice Commands; Supported Commands
Instruction Manual Supplement D103638X012 DVC6200 SIS Digital Valve Controller August 2014 16 CommonPractice Commands The DVC6200 SIS field device supports the following common practice commands: Supported Commands Command 33: Read Device VariablesCommand 35: Write Primary Variable Range ValuesComm...
Page 17 - Command 33: Read Device Variables
Instruction Manual Supplement D103638X012 DVC6200 SIS Digital Valve Controller August 2014 17 Command 33: Read Device Variables This command is used to read the value of up to four selected Device Variables. The Device Variables and Variable Units Codes are listed on page 6 and 7. Byte Format Descri...
Page 18 - Command 35: Write Primary Variable Range Values
Instruction Manual Supplement D103638X012 DVC6200 SIS Digital Valve Controller August 2014 18 Command 35: Write Primary Variable Range Values In the DVC6200 SIS, the Primary Variable is defined to be the Analog Input (loop current). This command is used to write the ranging values reported in Comman...
Page 19 - Command 42: Perform Master Reset
Instruction Manual Supplement D103638X012 DVC6200 SIS Digital Valve Controller August 2014 19 Command 42: Perform Master Reset This reset command has two options. If no data bytes are supplied, respond immediately and then perform a “warm”reset. This is not equivalent to power up in that restart mod...
Page 20 - Command 50: Read Dynamic Variable Assignments
Instruction Manual Supplement D103638X012 DVC6200 SIS Digital Valve Controller August 2014 20 Command 50: Read Dynamic Variable Assignments This command returns a list of four device variable codes, taken from the Device Variables table on page 6, which arereturned in Command 3. These Dynamic Variab...
Page 21 - Command 52: Set Device Variable Zero
Instruction Manual Supplement D103638X012 DVC6200 SIS Digital Valve Controller August 2014 21 Command 52: Set Device Variable Zero This command is used to force one of the pressure inputs to read 0. To use this for pressure, apply 0 psi to the sensor.Then, send this command, specifying the affected ...
Page 22 - Command 54: Read Device Variable Information; Device-Specific Commands
Instruction Manual Supplement D103638X012 DVC6200 SIS Digital Valve Controller August 2014 22 Command 54: Read Device Variable Information This command is used to identify each of the Device Variables, in the range of IDs 0…10 inclusive. Responds with theSensor Serial Number, Sensor Range Units, Sen...
Page 23 - Annex A Compatibility Checklist
Instruction Manual Supplement D103638X012 DVC6200 SIS Digital Valve Controller August 2014 23 Annex A Compatibility Checklist Manufacturer, Model, and Revision Fisher Controls DVC6200 SIS Device Revision 2 Device Type Pneumatic Control Valve Positioner HART Protocol Revision 7.4 User switchable betw...
Page 26 - Field Device Identification Values:
Instruction Manual Supplement D103638X012 DVC6200 SIS Digital Valve Controller August 2014 26 Published Data, used for the Gateway’s OPC and Modbus outputs, falls into the following categories: Field Device Identification Values: Values that define the identity of the DVC6200 SIS. These include: D ...
Page 27 - Detailed Device Alerts:
Instruction Manual Supplement D103638X012 DVC6200 SIS Digital Valve Controller August 2014 27 Any of these choices [Dynamic Variable, Device Variable ID, or Device Variable Name(s)] can be substituted for the “#”sign in the Variable Identifier fields below. Variable Identifier Comments / Explanation...