Emerson FG-110 – Manual in PDF format online.
Manuals:
Manual Emerson FG-110
Summary
Softing Linking Device – Manual for Configuration, Installation and Maintenance V1.31 page 3 of 85 Table of Contents 1 General Notes 7 1.1 Scope of Delivery 7 1.2 Safety Notes 7 1.3 Intended Use 7 1.4 System Requirements 7 1.4.1 Operating Systems 7 2 Hardware Installation 8 2.1 Overview Hardware – F...
Softing Linking Device – Manual for Configuration, Installation and Maintenance page 4 of 85 V1.3 4.5 <Configuration> 23 4.5.1 <Configuration><Settings> 23 4.5.1.1 <Configuration><Settings><General Settings> 23 4.5.1.2 <Configuration><Settings><Inte...
Softing Linking Device – Manual for Configuration, Installation and Maintenance page 6 of 85 V1.3 5.8.2.7 Block types first approach 72 5.8.3 Schedule View 73 5.9 Handling Host devices 73 6 Error handling and troubleshooting 74 7 Appendix A - Bus Parameter Configuration 76 7.1 Bus parameters relevan...
Softing Linking Device – Manual for Configuration, Installation and Maintenance General Notes V1.31 page 7 of 85 1 General Notes Please read this document thoroughly from beginning to end before starting installation to protect users from injury and to prevent misuse or damage to the Linking Device....
Softing Linking Device – Manual for Configuration, Installation and Maintenance Hardware Installation page 8 of 85 V1.3 2 Hardware Installation 2.1 Overview Hardware – FG-110 FF Fig 2.1-1 Overview Hardware – FG-110 FF power and data connections 2.2 LED Block – Meaning PWR The "PWR" LED indic...
Softing Linking Device – Manual for Configuration, Installation and Maintenance Hardware Installation V1.31 page 9 of 85 2.3 Power Supply The Linking Device is powered by 24 V DC. The power supply plug connector is included in the delivery. The power supply socket connector on the front panel is lab...
Softing Linking Device – Manual for Configuration, Installation and Maintenance Hardware Installation V1.31 page 11 of 85 Stahl. You will find this manual on the CD-ROM or on the internet web page http://www.r- stahl.com 2.6 FF H1 fieldbus connection The fieldbus terminals are mounted in 4 sets of t...
Softing Linking Device – Manual for Configuration, Installation and Maintenance Hardware Installation page 12 of 85 V1.3 Fig 2.7-1 Mounting the Linking Device ready for use: the SOFTING Foundation Fieldbus Interface Module FIM 110 The Linking Device is convection-cooled. It therefore needs to be ins...
Softing Linking Device – Manual for Configuration, Installation and Maintenance Ethernet Network Configuration V1.31 page 13 of 85 3 Ethernet Network Configuration 3.1 Linking Device IP address Configuration The Linking Device is delivered with a pre-configured IP address 192.168.177.177. It must be...
Softing Linking Device – Manual for Configuration, Installation and Maintenance Linking Device FG-110 FF - Internal Web Server page 14 of 85 V1.3 4 Linking Device FG-110 FF - Internal Web Server The internal web server of the Linking Device FG-110 FF offers the possibilities to configure the Linking...
Softing Linking Device – Manual for Configuration, Installation and Maintenance Linking Device FG-110 FF - Internal Web Server page 18 of 85 V1.3 Fig 4.3-1 System - actual Information of the Linking Device state 4.3.2 <Diagnostics><Internet Protocol> The table <Internet Protocol> l...
Softing Linking Device – Manual for Configuration, Installation and Maintenance Linking Device FG-110 FF - Internal Web Server page 22 of 85 V1.3 Fig 4.3-6 Modbus TCP Statistics 4.4 <Monitor> Click <Monitor> Options to display the point pages and point data. 4.4.1 <Monitor> <Poi...
Softing Linking Device – Manual for Configuration, Installation and Maintenance Linking Device FG-110 FF - Internal Web Server V1.31 page 27 of 85 4.5.1.4 <Configuration><Settings><User Account> The Linking Device is shipped with default user password. Under this menu item you can ...
Softing Linking Device – Manual for Configuration, Installation and Maintenance Linking Device FG-110 FF - Internal Web Server page 30 of 85 V1.3 Press the button <Save Configuration> another window appears on the screen which enables you to search for a folder in your directory on your PC or ...
Softing Linking Device – Manual for Configuration, Installation and Maintenance Linking Device FG-110 FF - Internal Web Server V1.31 page 31 of 85 If the Linking Device is connected to a network and if you want to use this feature, you can select a timeserver at your facility or one near you geograp...
Softing Linking Device – Manual for Configuration, Installation and Maintenance Linking Device FG-110 FF - Internal Web Server page 32 of 85 V1.3 Another window appears with a table where the valid Points for this point page are listed. Over the table there is an input box with the name of the point...
Softing Linking Device – Manual for Configuration, Installation and Maintenance Linking Device FG-110 FF - Internal Web Server V1.31 page 35 of 85 - Device: Devices (PD Tags) on segment In the table below is shown the function block type (Block Type), function block name (Block Name) and the descrip...
Softing Linking Device – Manual for Configuration, Installation and Maintenance Linking Device FG-110 FF - Internal Web Server page 38 of 85 V1.3 4.5.5.2 <Configuration><Modbus><Mapping> Fig 4.5-17 Change settings of the Modbus Mapping The functions of the Modbus mapping in the Lin...
Softing Linking Device – Manual for Configuration, Installation and Maintenance FF-CONF Configure your plant page 40 of 85 V1.3 5 FF-CONF Configure your plant By choosing the FF-CONFsetup.exe you will start the installation routine of the FF-CONF program. To start FF-CONF it is not necessary to acti...
Softing Linking Device – Manual for Configuration, Installation and Maintenance FF-CONF Configure your plant page 42 of 85 V1.3 5.1.2.3 View 5.1-4 View – shows you the displayed contents of the project With <View> you can activate the desired contents like the Network Livelist, Schedule View o...
Softing Linking Device – Manual for Configuration, Installation and Maintenance FF-CONF Configure your plant V1.31 page 43 of 85 Build All <Build All> Build all first checks the configuration and then builds a download domain if there are no error messages which prevent generation of the downl...
Softing Linking Device – Manual for Configuration, Installation and Maintenance FF-CONF Configure your plant page 44 of 85 V1.3 5.1.2.6 Online When FF-CONF is started with a new or an existent project FF-CONF is in mode offline. You can configure devices or build your Function Block application in t...
Softing Linking Device – Manual for Configuration, Installation and Maintenance FF-CONF Configure your plant V1.31 page 45 of 85 Here you define the cycles of the auto save and the handling with Tag names. If you want to add or to change the project description you can do it here even so the project...
Softing Linking Device – Manual for Configuration, Installation and Maintenance FF-CONF Configure your plant page 46 of 85 V1.3 Fig 5.1-13 The changed mouse pointer allows you to move the whole configuration picture 5.1.4.2 <Function Block Application> The tab <Function Block Application>...
Softing Linking Device – Manual for Configuration, Installation and Maintenance FF-CONF Configure your plant page 48 of 85 V1.3 Fig 5.1-15 Content of Device Types, the icons to process them and filters to select Device Types Meaning of the icons below the contents: ● - to sort by Device Name ● - to ...
Softing Linking Device – Manual for Configuration, Installation and Maintenance FF-CONF Configure your plant V1.31 page 51 of 85 Fig 5.1-19 The H1_Device_1 properties of the marked device are shown 5.1.7 Filtering the contents Here you find the possibility to set filters and so you may select the co...
Softing Linking Device – Manual for Configuration, Installation and Maintenance FF-CONF Configure your plant page 52 of 85 V1.3 5.2.2 Objects within the Network Configuration PC Here you are working online or offline to build your Network Configuration and commission your installation. HSE Subnet Et...
Softing Linking Device – Manual for Configuration, Installation and Maintenance FF-CONF Configure your plant page 54 of 85 V1.3 After a short time you see the screen to work with. Fig 5.3-2 Basic screen to load an existent or a new project The above screenshot shows the start screen of FF-CONF if yo...
Softing Linking Device – Manual for Configuration, Installation and Maintenance FF-CONF Configure your plant V1.31 page 55 of 85 Fig 5.4-1 Select a .cff file for adding an H1 device to the list of Device Types. The device library contains the description of H1 device types. The description of a devi...
Softing Linking Device – Manual for Configuration, Installation and Maintenance FF-CONF Configure your plant page 56 of 85 V1.3 Exception: HSE Devices cannot be removed. You get the notification: 5.5 Project handling In the menu item <Network Configuration> you start the main configuration wor...
Softing Linking Device – Manual for Configuration, Installation and Maintenance FF-CONF Configure your plant V1.31 page 57 of 85 5.5.2 Save project You can save the project manually whenever you want. You have two options to do this: Fig 5.5-3 Save your project manually If you save your project at o...
Softing Linking Device – Manual for Configuration, Installation and Maintenance FF-CONF Configure your plant page 58 of 85 V1.3 5.6 Network configuration The most important part of the project handling is the Network Configuration. You can configure a network in two ways: ● You adapt the network con...
Softing Linking Device – Manual for Configuration, Installation and Maintenance FF-CONF Configure your plant V1.31 page 59 of 85 5.6.3 Add a Linking Device (HSE) To add a Linking Device to the configuration press the green button to the left of the selected Linking Device in the list Device Types. F...
Softing Linking Device – Manual for Configuration, Installation and Maintenance FF-CONF Configure your plant V1.31 page 61 of 85 The H1 link object represents the port of the linking device with the H1 VFD and the bus parameters common for every device on this link. 5.6.5 Add H1 Device (Field Device...
Softing Linking Device – Manual for Configuration, Installation and Maintenance FF-CONF Configure your plant page 62 of 85 V1.3 5.7 Network Livelist The commissioning of your plant needs to adapt the data of your Network Configuration to the installation which really exists (Network Livelist). You m...
Softing Linking Device – Manual for Configuration, Installation and Maintenance FF-CONF Configure your plant V1.31 page 63 of 85 When you first change from <Network Configuration> to the <Network Livelist> you click on the menu item <View> <Network Livelist>. Beside the menu ...
Softing Linking Device – Manual for Configuration, Installation and Maintenance FF-CONF Configure your plant page 64 of 85 V1.3 In the same way you can pull down the tab Network configuration . So you get two windows in variable size and positions. This way you have the best possibilities to compare...
Softing Linking Device – Manual for Configuration, Installation and Maintenance FF-CONF Configure your plant V1.31 page 65 of 85 Device assignment is a time consuming action. During assignment, the device within the network configuration view gets a yellow bullet. The physical device within Network ...
Softing Linking Device – Manual for Configuration, Installation and Maintenance FF-CONF Configure your plant page 66 of 85 V1.3 Copy and paste groups and applications To realize big installation without any problem, and to record all the blocks and connections repeatedly use the possibility to copy ...
Softing Linking Device – Manual for Configuration, Installation and Maintenance FF-CONF Configure your plant V1.31 page 67 of 85 ● Select the Function Block application tab. ● Select the blocks tab. The blocks tab contains all configured blocks. These can be filtered. ● Set the profiles filter, for ...
Softing Linking Device – Manual for Configuration, Installation and Maintenance FF-CONF Configure your plant page 68 of 85 V1.3 5.8.2.3 Configure connections Fig 5.8-4 Configure connections Configure a connection by pressing the link buttons: 1. select output pin (H1_Device _3_PID_3.BKCAL_OUT) 2. se...
Softing Linking Device – Manual for Configuration, Installation and Maintenance FF-CONF Configure your plant V1.31 page 69 of 85 Fig 5.8-5 Click FB Parameter View Next you see the block parameters and can changes the values. Fig 5.8-6 Change values of the block parameters First select the parameter ...
Softing Linking Device – Manual for Configuration, Installation and Maintenance FF-CONF Configure your plant page 70 of 85 V1.3 general information . Independently from the block tag the type of the block is shown in brackets. Fig 5.8-7 Rename blocks Fig 5.8-8 Choose a block to see or edit parameter...
Softing Linking Device – Manual for Configuration, Installation and Maintenance FF-CONF Configure your plant V1.31 page 71 of 85 5.8.2.6 Changing parameters online It is also possible to call the parameter view of all blocks of a device by selecting the device and pressing the icon <Open paramete...
Softing Linking Device – Manual for Configuration, Installation and Maintenance FF-CONF Configure your plant page 72 of 85 V1.3 5.8.2.7 Block types first approach You can also enter the instance of a block type without device association to a function block application by clicking the *button of a s...
Softing Linking Device – Manual for Configuration, Installation and Maintenance FF-CONF Configure your plant V1.31 page 73 of 85 The same situation appears after copying a function block application or a whole group of function block applications because this copy action removes the device associati...
Softing Linking Device – Manual for Configuration, Installation and Maintenance Appendix A - Bus Parameter Configuration page 76 of 85 V1.3 7 Appendix A - Bus Parameter Configuration This section will help you configure the bus parameters of an H1 device or H1 link of a linking device correctly. It ...
Softing Linking Device – Manual for Configuration, Installation and Maintenance Appendix A - Bus Parameter Configuration V1.31 page 77 of 85 V(MRD) MaxResponseDelay SlotTimes, V(MRD) × V(ST). Both parameters are specified in octet durations. The attributes MaxResponseDelay and SlotTime should be set...
Softing Linking Device – Manual for Configuration, Installation and Maintenance Appendix A - Bus Parameter Configuration page 78 of 85 V1.3 can be granted only when the remaining time is higher than DefMinTokenDelegTime. The parameter is specified in octet durations. TargetTokenRotTime This paramete...
Softing Linking Device – Manual for Configuration, Installation and Maintenance Glossary V1.31 page 79 of 85 8 Glossary Explains specialist terms of the organisation, configuration, device types and the handling of FF-CONF. 8.1 General remarks of the user manual Term Definitions Comment, other term ...
Softing Linking Device – Manual for Configuration, Installation and Maintenance ATEX and IECex Certifications - Excerpt from the Instruction Manual page 82 of 85 V1.3 9 ATEX and IECex Certifications - Excerpt from the Instruction Manual 9.1 Preface This excerpt from the instruction manual does only ...
Softing Linking Device – Manual for Configuration, Installation and Maintenance ATEX and IECex Certifications - Excerpt from the Instruction Manual V1.31 page 83 of 85 9.4 General requirements a) If the notes stated in this excerpt are not observed or in case of inappropriate handling of the device,...
Softing Linking Device – Manual for Configuration, Installation and Maintenance page 84 of 85 V1.3 k) To circuits of Zone 2 only such equipment may be connected that is suitable for operation in this zone and has been certified accordingly (suitable documents have been provided). l) The devices have...
Emerson Manuals
-
Emerson LD195EM8
User Manual
-
Emerson EWR20V4
User Manual
-
Emerson EWR20V4
Manual
-
Emerson SLC195EM8
User Manual
-
Emerson SLC195EM8
Manual
-
Emerson CR202EM9
User Manual
-
Emerson HD14070
User Manual
-
Emerson RLC320EM9
User Manual
-
Emerson LC320EM9
User Manual
-
Emerson LC320EM9
Manual
-
Emerson PD6922
User Manual
-
Emerson PD6922
Manual
-
Emerson EPT427D
User Manual
-
Emerson EPT427D
Manual
-
Emerson 400 VMC
User Manual
-
Emerson 400 VMC
Manual
-
Emerson CF960CK
User Manual
-
Emerson MICRO MOTION 2700
Installation Manual
-
Emerson CF787AP00
User Manual
-
Emerson CF787AP00
Manual