EC2-391_65136_EN_R01.doc Replacement for 00 2 / 4 PCN: 865 022 21.09.2007 EC2-391 Display Case and Coldroom Controller Operating Instructions GB Recommended Sensor Positions in Detail: (1) ECN-Pxx coil-in temperature sensor: Position on the first return bend of the evaporator. (2) ECN-Pxx coil-out t...
EC2-391_65136_EN_R01.doc Replacement for 00 3 / 4 PCN: 865 022 21.09.2007 EC2-391 Display Case and Coldroom Controller Operating Instructions GB List of Parameters / DISPLAY PARAMETERS Min Max Unit Def. Custom /1 Value to show 0 9 - 0 0 = Thermostat control temperature with Temp. alignment °C 1 = Ai...
EC2-391_65136_EN_R01.doc Replacement for 00 4 / 4 PCN: 865 022 21.09.2007 EC2-391 Display Case and Coldroom Controller Operating Instructions GB Formula for Mean Factors A0, r8, r9 Temperature calculation by the following formula: Temperature = Air in * (1 - Mean Factor / 100) + Air out * Mean Facto...