Page 2 - Specifications
Installation Manual ASCO 5350 Page 2 ASCO Power Technologies 381333-315 D Specifications Power Requirements: 120-220 V ac nominal (90-264 V ac) auxiliary 24 V dc nominal (9-36 V dc) can be a battery or UL rated Class 1 dc power supply max. power 10 watts ac or 5 watts dc Dimensions: 7.77” H x 9.95” ...
Page 3 - Installation; -1 Communication Architecture; DANGER
ASCO 5350 Installation Manual 381333-315 D ASCO Power Technologies Page 3 Installation The ASCO 5350 ATS Remote Annunciator can be panel mounted or attached to an electrical or masonry gang box. Refer to the installation drawing 834970 and wiring diagram 834969 at the back of this manual. 1 Panel Mo...
Page 4 - Functional Test; Initial
Installation Manual ASCO 5350 Page 4 ASCO Power Technologies 381333-315 D Functional Test After installing the ATS Remote Annunciator communication must be established to configure it. A Windows -based laptop computer is needed. You must have access to the other end of the communication cable that i...
Page 5 - Login; Annunciator; -1 Annunciator Name; NOTICE
ASCO 5350 Installation Manual 381333-315 D ASCO Power Technologies Page 5 ATS Remote Annunciator Configuration The ATS Remote Annunciator must be configured. First log in. The ATS Remote Annunciator sends HTML files to the client computer. Internet Explorer interprets these HTML files, formats them,...
Page 6 - -9 Click Update to Save Configurations !
Installation Manual ASCO 5350 Page 6 ASCO Power Technologies 381333-315 D 2-3 IP Address, Subnet Mask, Gateway 1. The default IP address parameter is: 169.254.1.200. If the ATS Remote Annunciator is on a LAN enter the appropriate IP address of the LAN. The default subnet mask parameter is: 255.255.0...
Page 7 - ATS Configuration; Configuration; -1 Single ATS connected to one CM
ASCO 5350 Installation Manual 381333-315 D ASCO Power Technologies Page 7 ATS Configuration The ATS Remote Annunciator must be configured for all the ATSs that will be monitored and controlled. First log in. The ATS Remote Annunciator sends HTML files to the client computer. Internet Explorer interp...
Page 9 - -2 Multiple ATSs connected to one CM; -3 Configuring Power Manager Alarms
ASCO 5350 Installation Manual 381333-315 D ASCO Power Technologies Page 9 5. When all ATS configurations are made, click Save to upload the configuration to the ATS Remote Annunciator. An Uploaded Successfully screen should appear. See Figure 22. The ATS Remote Annunciator should now be monitoring t...
Page 10 - Diagnostics; Packets; Alarm
Installation Manual ASCO 5350 Page 10 ASCO Power Technologies 381333-315 D Diagnostics Diagnostics can be used to check communication packets and to check for ATS alarms (to determine why the Alarm light is on). If necessary, reconnect the laptop computer that was used to configure the ATS Remote An...
Page 12 - Index
Index ASCO 5350 Page 12 Copyright 2014 ASCO Power Technologies. All rights reserved. 381333-315 D Index A address controller, 8 IP, 2, 4, 5, 6 alarm buzzer, 3, 8, 10 alarm light, relay alarm silence button, refer to User’s Guide 381333-314 annunciator, configuration, 14 ATS configuration, 7 ATS cont...